Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
ASTM D2308-07 (Reapproved 2020) defines the standard specification for thermoplastic polyethylene (PE) jackets used as the outer protective layer on medium-voltage electrical wire and cable. Covering voltage ratings from 2 kV to 35 kV, this specification ensures the jacket provides robust mechanical protection, environmental resistance, and stable electrical performance over a wide range of installation and service conditions. The standard is maintained by ASTM Subcommittee D09.07 on Electrical Insulating Materials.
The base polyethylene compound must be classified as Type I, Class C, Category 4 or 5, Grade E5 or J3 as defined in ASTM D1248. Class B materials are also acceptable if they demonstrate weathering performance equivalent to Class C. The jacket must be applied at a nominal thickness of at least 0.030 in. (0.76 mm) to ensure adequate protection for the insulated conductor.
The material is formulated to perform reliably in extreme climates. The standard specifies a continuous service temperature range from −55 °C to +75 °C, with a minimum permissible installation temperature of −40 °C. Physical property testing of jacket specimens removed from the cable or conductor must be conducted at a standard laboratory temperature of 20 to 28 °C (68 to 82 °F).
Mechanical integrity is validated through air-oven aging, defined as exposure to air at 100 °C for 24 or 48 hours to simulate long-term thermal degradation. The jacket must also demonstrate high resistance to environmental stress-cracking (ESCR), meeting the requirements for Grade E5 as detailed in Table 3 of ASTM D1248.
The electrical performance of the jacket material is strictly governed by Table 2 of the standard, which was editorially corrected in October 2020 to ensure accuracy. All requirements below are based on the properties of the jacket material itself, removed from the cable, and do not test the overall cable dielectric system unless otherwise combined.
| 🟦 General Parameter | 📏 Specification / Requirement |
|---|---|
| Voltage Class | 2 kV to 35 kV |
| Nominal Thickness | ≥ 0.030 in. (0.76 mm) |
| Material Grade (D1248) | E5 or J3 (Cat 4 or 5) |
| Service Temperature | −55 °C to +75 °C |
| Installation Temperature | −40 °C minimum |
| Environmental Crack (ESCR) | Grade E5 (per D1248) |
| Aging Condition | 100 °C / 24 to 48 h |
| Test Temperature | 20 to 28 °C (68 to 82 °F) |
| 🎯 Test Criteria | ⚡ Requirement / Method |
|---|---|
| Absorption Coefficient | Per ASTM D3349 |
| Physical Properties (Table 1) | Conform to D2308 limits |
| Electrical Properties (Table 2) | Conform to D2308 limits |
🔍 What is the intended voltage range for jackets covered under D2308?
The specification specifically covers jackets for wire and cable rated from 2 kV to 35 kV. It is designed for medium-voltage power cables requiring a robust thermoplastic outer layer capable of weathering and physical abuse.
💡 What is the minimum recommended installation temperature for this material?
The compound must be suitable for installation at temperatures as low as −40 °C, making it viable for use in cold climates without cracking. The maximum continuous service temperature is +75 °C.
⚡ How is environmental stress-cracking resistance verified for this jacket?
Environmental stress-cracking resistance (ESCR) must meet the strict requirements for Grade E5 as specified in Table 3 of ASTM D1248. This test is critical for ensuring jacket longevity when exposed to mechanical stress and chemical agents at elevated temperatures.
📌 What aging conditions are used to simulate thermal exposure during testing?
The standard defines laboratory aging as exposure of the jacket material to circulating air at 100 °C for either 24 or 48 hours, depending on the specific property being evaluated. This conditioning is performed to assess the material’s resistance to long-term thermal oxidation.