This standard, formally designated as ASTM D1865/D1865M, establishes a definitive test method for evaluating the hardness of mineral aggregate surfacing materials used in built-up roofing (BUR) systems. The primary objective is to provide a reliable, empirical index of an aggregate’s ability to resist physical degradation during handling, transport, and application. By standardizing the mechanical stresses applied to the sample, this test allows manufacturers and specifiers to predict the in-service durability and functional integrity of the roofing surfacing.
The core testing apparatus consists of a clean 1.2 m [4 ft] length of 50 mm [2 in.] iron pipe, equipped with removable screw caps on both ends. This pipe is mounted on a suitable stand that allows for rotation about an axis perpendicular to its length. Supporting equipment includes a 500 g balance sensitive to 0.01% of capacity, a riffle-type sample splitter, and a mechanical sieve shaker.
Specimen Preparation: The aggregate sample is first dried at 110 °C [230 °F]. Using the riffle splitter, the dried material is fractionated to recover a test specimen of approximately 227 g [0.5 lb]. This specimen must pass through the 9.5 mm [3/8 in.] sieve but be fully retained on the 6.3 mm [1/4 in.] sieve, ensuring a uniform starting particle size.
| 🟦 Sieve Designation | 📏 Standard Opening |
|---|---|
| 9.5 mm [3/8 in.] | 9.5 mm |
| 6.3 mm [1/4 in.] | 6.3 mm |
| 3.35 mm (No. 6) | 3.35 mm |
The prepared 227 g sample is placed inside the iron pipe and securely capped. The apparatus is then mechanically rotated, causing the aggregate to free-fall the entire 1.2 m length of the pipe for a total of 400 drops. After the test cycle, the material is removed and sieved over a 3.35 mm (No. 6) sieve. The proportion of material passing this sieve indicates the degree of breakdown caused by the mechanical handling simulation.
| ⚙️ Test Parameter | 📐 Standard Specification |
|---|---|
| Drop Height | 1.2 m [4 ft] |
| Total Drop Cycles | 400 |
| Test Sample Mass | ~227 g [0.5 lb] |
| Pipe Dimensions | 50 mm [2 in.] dia. x 1.2 m [4 ft] |
| Balance Sensitivity | 0.01 % of capacity |
This test provides a standardized index of the aggregate’s resistance to physical breakdown during handling. Aggregates that break down easily can create dust, lose their reflective properties, and compromise the protective function of the roofing surface.
Bulk samples are obtained according to Practice D75/D75M. The aggregate is dried at 110 °C [230 °F] and fractionated using a riffle-type splitter. A specimen weighing approximately 227 g [0.5 lb] that passes a 9.5 mm sieve but is retained on a 6.3 mm sieve is isolated for the test.
The test simulates handling breakdown by placing the prepared aggregate sample inside a 1.2 m [4 ft] steel pipe and rotating it to cause the material to fall the entire length of the pipe. This process is repeated a total of 400 times to assess the aggregate’s durability against impact and attrition.
The result offers a comparative index of the aggregate’s hardness. A lower percentage of material passing the 3.35 mm (No. 6) sieve after the 400 drops indicates a harder aggregate more capable of withstanding the physical rigors of handling, transport, and installation without significant degradation.