Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
ASTM D1523-00 (Reapproved 2006) defines the requirements for a crosslinked synthetic rubber compound intended for use as primary electrical insulation on wire and cable. It is suited for continuous operation at conductor temperatures up to 90°C in dry locations and at system voltages no greater than 2000 V. The standard stresses that the material must be tested in its applied form when possible, as its performance is intrinsically linked to its extrusion onto a conductor.
The insulation must comply with strict physical property thresholds before and after thermal aging. All referenced test methods are defined within ASTM D470.
| 🟦 Property | 📏 Unaged Requirement | 🎯 Aged Condition |
|---|---|---|
| Tensile Strength, min | 700 psi (4.8 MPa) | Air at 121°C for 168 h |
| Elongation at Rupture, min | See Table 1 of Standard | Heat & Pressure at 127°C for 42 h |
| Aging (Act of) | N/A | 121°C / 168 h or 127°C / 42 h |
Electrical performance is equally critical. The insulation must withstand AC potential tests and maintain a minimum insulation resistance level. Testing must follow a strict sequence when full electrical compliance is required.
| ⚡ Electrical Test | 🎯 Performance Criteria | 📐 Test Protocol |
|---|---|---|
| AC Voltage Withstand | Voltage per D470 Table 1A | Apply for 5 min to each conductor |
| Insulation Resistance | Constant ≥ 4000 (60°F) | Correct values per D470 Table 2 |
| DC Voltage Withstand | Per D470 | Performed in sequence per 5.4 |
The minimum average thickness of the insulation layer must be at least 90% of the values listed in Table 1A of ASTM D470. The insulation is primarily composed of synthetic rubber polymers and must be fully crosslinked to ensure thermal stability and mechanical robustness over its intended service life. In many instances, the insulation cannot be tested unless it has been formed around a conductor.
The insulation is rated for continuous operation at a maximum conductor temperature of 90°C in dry locations. Operating conditions should not exceed a system voltage of 2000 V.
Aging, as defined in Section 3.2.1, constitutes exposure of the material to air at 121°C for 168 hours or exposure to heat and pressure at 127°C for 42 hours.
The insulated conductor must exhibit an insulation resistance value corresponding to a minimum constant of 4000 when corrected to a temperature of 60°F (15.6°C). Correction factors are provided in Table 2 of ASTM D470.
The minimum average thickness of the insulation must be at least 90% of the thickness values specified for standard constructions in Table 1A of the referenced Test Methods D470.