IEC 60282-3 specifies high-voltage fuses (1–72.5 kV). HV current-limiting fuses are the most “brutally simple yet effective” protection in distribution networks — their core advantage is interrupting fault current before it reaches the first peak (<5 ms).
| Parameter | Typical | Notes |
|---|---|---|
| Rated Voltage | 3.6–72.5 kV | Must ≥ system Um |
| Rated Current | 6.3–200 A | Fuse rating ≠ protected equipment rating |
| Breaking Capacity | 31.5–63 kA | Maximum symmetrical fault current safely interruptible |
| Cut-Off Current | Far below system peak | Current-limiting characteristic |
Fuse selection triad:
1. V_rated ≥ Um
2. In(fuse) ≥ I_load (but not oversized, or protection sensitivity drops)
3. I_breaking ≥ Ik" (max fault at installation point)
Typical transformer protection: 40MVA, 110/10kV → HV fuse 40A/123kV/31.5kATN Lab — HV fuses are the most “brutally simple yet effective” protection devices in distribution networks.