IEC 60270: Partial Discharge Measurement — The Gold Standard for HV Insulation Diagnostics

What Does 10 pC of Partial Discharge Mean? Decoding Insulation Health on the pC Scale

IEC 60270:2015 is the definitive standard for partial discharge (PD) measurement. PD measurement can detect localized defects months to years before insulation breakdown — unlike other diagnostic methods, PD directly measures discharge activity inside insulation.

Apparent Charge(pC)Insulation ConditionRecommended Action
<10 pCNormal — new equipment standardRoutine monitoring (typically annual)
10–50 pCAttention — localized defectShorten interval, trend tracking (3–6 months)
50–500 pCWarning — defect developingFurther diagnostics (DGA, tanδ), plan outage
>500 pCCritical — near breakdown thresholdSchedule immediate outage and repair
Apparent charge: q = C₀ × ΔV
Calibration pulse: ΔV=10V, C₀=5pF → q=50pC
Detector output: Vout = q × transfer impedance Z
Z depends on detector type (R, RC, RLC) and frequency

TN Lab — Partial discharge is the “early warning system” for HV insulation degradation. The pC is its universal language.