Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
IEC 60186 specifies voltage transformer requirements. If CTs are the “eyes” of protection, VTs are the “ears” — distance protection, directional overcurrent, and synchro-check devices all depend on VT voltage signals.
Ferroresonance: a VT-unique risk. In unearthed-neutral systems, VT inductance and line-to-earth capacitance can form a series resonant circuit. After a single-phase fault clears, the transient can excite ferroresonance — voltages reaching 2–3× rated, lasting seconds, capable of thermally overloading the VT or blowing its fuse. Mitigation: a damping resistor (typically 25–100 Ω, 100–500 W) connected across the open-delta secondary winding.
Voltage Factor: The nameplate parameter that determines survival. 1.2 Un continuous (effectively earthed systems), 1.5 Un / 30 s (unearthed), or 1.9 Un / 8 h (healthy-phase voltage rise during a line-to-earth fault on an unearthed system). Selecting the wrong voltage factor means the VT suffers thermal runaway from overexcitation during a system earth fault.
TN Lab — VT selection goes beyond ratio. Ferroresonance protection and voltage factor are the VT-unique parameters that matter most.