Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
IEC 60185 specifies current transformer (CT) technical requirements. CTs are the “eyes” of protection relays — if a CT saturates under fault current, the secondary waveform distorts, and the relay cannot “see” the true primary fault current.
Three selection parameters: (1) Rated primary current — not sized for normal load, but for maximum fault current where the CT must remain unsaturated (error ≤5–10%). (2) Accuracy Limit Factor (ALF) — the key protection CT parameter. ALF=10 means the CT maintains accuracy (Class 5P composite error ≤5%) at 10× rated current. (3) Secondary burden — relay input impedance + connecting cable resistance. Actual burden must not exceed rated burden, or the CT saturates prematurely.
Quick CT sizing:
System max fault current Is = 40 kA
Rated primary Ipn = 2,000 A
Required ALF = Is/Ipn = 40/2 = 20
→ Need ALF ≥ 20: specify 5P20 or higherMost dangerous mistake: Open-circuiting a CT secondary under load — the secondary winding generates extreme induced voltage (exceeding several kV), sufficient to destroy insulation and injure personnel. A CT secondary circuit must never, under any circumstances, be open-circuited while energized.
TN Lab — CT selection goes far beyond ratio. ALF and burden are what determine protection reliability.