Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
CSA C22.2 No. 144.1-16 (2018) establishes the minimum safety and performance requirements for ground-fault circuit interrupters (GFCIs) intended for use in accordance with the Canadian Electrical Code, Part I (C22.1). This standard applies to devices rated at up to 250 V and up to 60 A (depending on the class), designed to protect against ground-fault hazards in residential, commercial, and industrial installations. It covers both permanently wired and cord-connected GFCI devices, including receptacle types, portable units, and circuit-breaker types.
The standard defines several classes of GFCI based on the intended level of protection:
| Class | Nominal Trip Level | Primary Application |
|---|---|---|
| Class A | 6 mA | Personnel protection (general use) |
| Class B | 20 mA | Protection of submersible pumps (historical) |
| Class C | 20 mA | Swimming pool and spa equipment |
| Class D | 6 mA | Fire alarm systems (initiating circuits) |
| Class E | 6 mA | Electric vehicle supply equipment |
The standard requires that all GFCI devices be clearly marked with their class, voltage rating, and current rating. In current practice, Class A devices are most common for residential and commercial installations requiring personnel protection.
For Class A GFCIs, the standard mandates a tripping time of not greater than 7 ms at a ground-fault current of 150 mA, and a maximum opening time of 25 ms at 6 mA. The table below summarizes the required trip performance for Class A devices:
| Ground-Fault Current (mA) | Maximum Trip Time (ms) |
|---|---|
| 6 | 25 |
| 10 | 12 |
| 20 | 8 |
| 50 | 7 |
| 150 | 7 |
Devices must also withstand a 500 A surge (8/20 μs waveform) without nuisance tripping, and must remain operational after exposure to voltage surges as defined in the standard.
CSA C22.2 No. 144.1-16 requires robust construction, including: temperature-rise limits under rated load, resistance to impact and vibration, moisture resistance, and dielectric strength (minimum 1500 V between ungrounded conductors and ground). All GFCIs must have clearly legible permanent marking indicating the manufacturer, model number, class, electrical ratings, and a caution statement regarding testing. Marking must be in English and French.
When selecting and installing GFCI devices under the Canadian Electrical Code, compliance with CSA C22.2 No. 144.1-16 is mandatory for all devices subject to certification. Installers should verify that the device label carries the appropriate certification mark (e.g., CSA, cUL) and the standard number.
For retrofit applications, the standard allows Class A GFCIs to be used in place of older Class B devices in residential settings. However, pool equipment installations still require Class C GFCIs if the equipment is rated above 15 A.
Manufacturers seeking certification of GFCI devices to CSA C22.2 No. 144.1-16 must submit samples to an accredited testing laboratory (e.g., CSA Group, UL, Intertek) for evaluation. Testing covers: all trip level and timing conditions, endurance (6000 cycles at rated load), short-circuit withstand, ambient temperature effects, and the surge withstand test. In addition, the standard mandates a one-time assessment of the production line to ensure consistent trip calibration.
Devices certified before the 2016 edition may still be compliant but should be reviewed for changes introduced in the 2018 reaffirmation, particularly regarding marking updates and clarified weather-resistance provisions for outdoor GFCIs.
For regulatory acceptance, each device shipped into Canada must have the bilingual safety warning and the certification mark. The standard is referenced in the Canadian Electrical Code, making compliance a legal requirement for all electrical installations subject to provincial or territorial adoption.
All technical information in this article reflects the requirements of CSA C22.2 No. 144.1-16 (2018) and the Canadian Electrical Code as of 2026.