Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
ANSI Z21.17-1998, jointly published as CSA 2.7-M98, establishes uniform requirements for the construction, performance, and safe operation of domestic gas conversion burners. These burners are intended for field installation in existing heating appliances—such as furnaces, boilers, and warm-air heaters—to convert them from one gas to another (e.g., natural gas to LP-gas) or to replace a worn or inefficient burner assembly. This standard is widely referenced by manufacturers, testing laboratories, and code authorities across North America. The following article provides a detailed overview of its scope, key technical provisions, implementation guidance, and compliance notes.
The standard covers domestic gas conversion burners that are designed for attachment to, or installation in, appliances originally certified for use with a different gas type or requiring a replacement burner. The scope explicitly includes:
The standard aligns with the broader Z21 series of safety requirements for gas-fired appliances and is referenced in model building codes such as the NFPA 54 (National Fuel Gas Code) and the International Fuel Gas Code (IFGC).
ANSI Z21.17-1998 prescribes a comprehensive set of criteria covering construction, materials, performance, and safety. Below are the major categories.
| Test Parameter | Natural Gas (Btu/h) | LP-Gas (Btu/h) | Acceptance Criteria |
|---|---|---|---|
| Maximum Input Rating | 400,000 | 300,000 | ±5% of nameplate at rated pressure |
| Minimum Input (turn-down ratio) | — | — | Stable flame without lifting or flashback |
| Gas Supply Pressure (max.) | 14 in. w.c. (3.5 kPa) | 14 in. w.c. (3.5 kPa) | No malfunction or hazardous condition |
| Gas Supply Pressure (min.) | 5 in. w.c. (1.25 kPa) | 11 in. w.c. (2.74 kPa) | Flame stability and proper ignition |
| Flame Safeguard Response | — | — | Main gas valve closes within 90 seconds of flame loss |
| Over-Temperature Limit | — | — | Limit control stops burner before appliance exceeds rated temperature |
Table 1: Representative performance requirements common to conversion burners under ANSI Z21.17-1998.
The standard requires that conversion burners be equipped with:
Successful application of ANSI Z21.17-1998 in product design and field installation requires close attention to several critical areas.
The conversion burner must be matched to the appliance’s heat exchanger volume, draft characteristics, and clearance to combustibles. Manufacturers typically supply a range of orifice sizes and provide instructions for measuring input rate using gas meters. The standard mandates that the conversion kit include explicit instructions for input adjustment to within ±5% of the nameplate rating.
Proper primary air setting is vital for clean combustion. Too little air yields yellow tipping and soot; too much air can cause flame lifting or noise. The standard requires that the burner design allow a stable flame over the entire range of air shutter positions, with the adjustment mechanism secured after setting.
Because conversion burners are installed in existing appliances—some of which may be decades old—the standard includes provisions for venting safety. The burner must be compatible with the appliance’s draft hood, flue gas spillage must remain within acceptable limits (per ANSI Z21.47 / CSA 2.22), and the ignition system must reliably light each port.
Compliance with ANSI Z21.17-1998 is typically verified through a third-party testing agency (e.g., CSA Group, UL, or Intertek). The standard is recognized as an American National Standard and is referenced by US states and Canadian provinces under adopted fuel gas codes.
Each conversion burner must be permanently marked with:
Installation instructions must also include a statement that the conversion burner is to be installed by a qualified agency (usually a licensed gas fitter) in accordance with NFPA 54, CSA B149.1, or the local code.
Authorities having jurisdiction (AHJs) frequently check for:
The standard also requires that the burner’s installation instructions include a wiring diagram and troubleshooting guide. AHJs may reference ANSI Z21.17 to verify that the burner meets the minimum safety requirements regardless of the age of the host appliance.
ANSI Z21.17-1998 was superseded in subsequent years by Z21.17-2003, Z21.17-2010, and later editions. However, the 1998 edition remains in use for older equipment and as a reference for retrofit projects. Users should confirm that the edition adopted by their local code is appropriate for the installation.
Reference year: 2026