Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
The SAE J2318-2020 standard establishes uniform minimum test performance requirements for service, spring applied parking, and double diaphragm combination air brake actuators. These actuators are critical components in air brake systems for trucks, truck-tractors, buses, and trailers. Compliance with SAE J2318 ensures that actuators meet essential durability, functional, and environmental performance criteria when tested according to SAE J1469.
Leak testing is fundamental to actuator reliability. Both parking and service chambers must not exceed a maximum leakage rate of 23 cc/min (1.40 in³/min) under specified conditions. An alternate procedure measures pressure change with a maximum allowable drop of 10.34 kPa (1.5 psig).
| Chamber Tested | Maximum Leakage Rate | Alternate Pressure Change |
|---|---|---|
| Parking Chamber | 23 cc/min (1.40 in³/min) | 10.34 kPa (1.5 psig) |
| Service Chamber | 23 cc/min (1.40 in³/min) | 10.34 kPa (1.5 psig) |
The release and hold-off pressure for the parking chamber is measured at 5 mm stroke from the zero position, with a target maximum hold-off pressure of 483 kPa (70 psi) to avoid brake drag. Actual requirements may vary based on the vehicle air brake system design.
Force output testing verifies that the actuator delivers the required force at specified strokes and air pressures. Table 2 provides parking chamber force outputs, while Table 3 and Table 4 cover service chamber forces. Note that SAE J2318-2020 includes a critical correction: the Type 30 service force output at 276 kPa was corrected from 7451 N to 4751 N in the February 2020 revision.
Actuators must withstand extreme conditions. Low temperature testing includes leakage, release pressure, and force output checks. For service chambers, low temperature operational tests validate functionality in cold climates. Durability is assessed via elevated temperature cycle testing, repeated cycle tests, and vibration exposure. Corrosion resistance is evaluated per the standard’s procedures, and mechanical back-off release mechanisms are required for safety during maintenance.
The standard specifies a maximum leakage rate of 23 cc/min for both parking and service chambers, which can be measured directly or via an alternate pressure drop test not exceeding 10.34 kPa.
Force output is measured at defined strokes and air pressures as per SAE J1469, Section 7. For service chambers, specific force values are tabulated in the standard based on actuator type and size.
Hold-off pressure is tested by measuring the pressure at which the parking chamber releases, typically at 5 mm stroke from zero. The maximum allowable hold-off pressure is 483 kPa to prevent brake drag.
Low temperature tests include leakage, maximum release and hold-off pressure, force output for parking chamber, and an operational test for service chamber, all conducted at specified low temperatures to ensure actuator performance in cold environments.
For complete details, refer to the full SAE J2318-2020 document and the referenced SAE J1469 test procedure.