ANSI Z21.11.3-2016 applies to newly produced unvented gas-fired room heaters operating on natural gas, manufactured gas, mixed gas, liquefied petroleum gases (LP-Gas), or LP-Gas-air mixtures. The standard specifically excludes appliances intended for vented connection (covered by ANSI Z21.11.2) and ranges, clothes dryers, or gas logs designed solely for decorative vented fireplaces.
The 2016 edition establishes a maximum input rating of 40,000 Btu/hr (11.7 kW) for general installation, with a stricter limit of 10,000 Btu/hr (2.9 kW) for heaters listed for bedroom use. A defining feature of this standard is the universal mandate for an Oxygen Depletion Safety (ODS) system on all certified appliances.
The ODS system is the primary safety interlock for unvented heaters. The standard requires a calibrated pilot burner and thermocouple assembly that automatically interrupts the gas supply to the main burner and pilot if ambient oxygen levels fall below approximately 18%. The test procedure simulates oxygen depletion at various elevations to ensure repeatable shutdown performance.
To prevent hazardous indoor air quality, the standard mandates a maximum CO/CO₂ ratio of 0.02. This means the carbon monoxide concentration in the flue products must not exceed 20,000 ppm for every 1% of CO₂. The standard outlines specific test protocols:
| Performance Parameter | Requirement (Natural Gas) | Requirement (LP-Gas) |
|---|---|---|
| Maximum Input Rating (General) | 40,000 Btu/hr (11.7 kW) | 40,000 Btu/hr (11.7 kW) |