Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
IEC TR 61818:2003 is a Technical Report that serves as an application guide for low-voltage fuses. Unlike normative standards that prescribe mandatory requirements, this Technical Report provides informative guidance based on accumulated industry experience. It covers fuses manufactured according to the IEC 60269 series, including gG (general-purpose), gM (motor-circuit), aM (motor starting), gR (semiconductor protection), and gB (mineral insulated cable protection) fuse-links.
The report addresses practical aspects including selection criteria based on load characteristics, ambient temperature derating, discrimination between series-connected fuses, back-up protection coordination with circuit breakers, protection against overcurrents in various installation contexts, and the impact of power quality on fuse performance. It serves as an essential reference for electrical design engineers, maintenance personnel, and safety professionals involved in low-voltage power distribution.
Correct fuse selection requires a systematic evaluation of electrical, thermal, and operational parameters. Each selection factor must be carefully weighed against the specific requirements of the installation.
The rated voltage of the fuse must exceed the maximum system voltage, including tolerance. A common engineering practice is to select a fuse with rated voltage at least 1.1 times the nominal system voltage. For rated current, the continuous load current must be derated for enclosure conditions and ambient temperature. Typically, enclosed installations require 15-25% derating, while high ambient temperature environments require an additional 10-15% reduction. The breaking capacity must exceed the maximum prospective fault current at the point of installation, verified against the worst-case bolted fault condition.
| Selection Parameter | Key Consideration | Engineering Guidance |
|---|---|---|
| Rated voltage | Must exceed maximum system voltage | Select fuse with V€ ≥ 1.1 × Vnominal |
| Rated current | Based on load current with derating | Derate 15-25% for enclosed; 10-15% for high ambient temp |
| Breaking capacity | Must exceed max prospective fault current | Verify against worst-case bolted fault at installation point |
| Load type | Resistive, inductive, capacitive, or electronic | gG for general loads; aM for motor starting; gR for semiconductor |
| Ambient temperature | Affects continuous current rating | Apply temperature correction factors per manufacturer data |
| Enclosure conditions | Heat dissipation limitations | Sealed enclosures require additional 10-15% current derating |
Different load types impose distinct current characteristics that directly influence fuse selection. For resistive loads such as heating elements, the steady-state current is relatively constant and gG fuse-links provide adequate protection. Motor circuits present more complex requirements due to starting currents reaching 6-8 times rated current for 5-10 seconds. For direct-on-line starting, aM fuse-links are preferred as they withstand starting surges without nuisance blowing while still providing short-circuit protection. Semiconductor protection demands ultra-fast gR fuse-links with I²t values carefully matched to the device surge rating.
Proper fuse coordination ensures that only the faulted circuit is isolated, maintaining supply continuity to healthy sections. The report provides detailed guidance on achieving selective coordination through careful matching of fuse characteristics.
Selective coordination between series-connected fuses requires that the upstream fuse does not operate for faults downstream. The standard rule of thumb is a ratio of 1.6:1 between upstream and downstream fuse ratings for gG types under similar conditions. However, this ratio depends on fault current level — at high fault currents, the I²t energy of the downstream fuse must be less than the pre-arcing I²t of the upstream fuse. For critical applications, coordination studies should use actual time-current curves and I²t characteristics from manufacturer data rather than nominal ratios. Engineers should also consider that the minimum discrimination ratio increases to 2:1 when fuses are operating at different ambient temperatures or when upstream fuses are in enclosed holders.
In modern distribution systems, fuses are often used in series with circuit breakers. Back-up protection arrangements use the fuse to provide short-circuit protection while the breaker handles overloads. The fuse must be selected so that its let-through energy (I²t) does not exceed the breaker’s withstand rating. For molded-case circuit breakers (MCCBs), the fuse should operate for fault currents above the breaker’s interrupting rating. The crossover point — where breaker and fuse characteristics intersect — must be clearly identified to avoid a protection blind zone. Type 2 coordination per IEC 60947-4-1 between fuses and contactors requires that the fuse limits I²t below the contactor weld threshold.
| Coordination Type | Configuration | Key Parameter | Typical Ratio / Requirement |
|---|---|---|---|
| Fuse-Fuse (discrimination) | Series gG fuses | Pre-arcing I²t ratio | ≥ 1.6:1 nominal; ≥ 2:1 for different conditions |
| Fuse-Breaker (backup) | Fuse upstream of MCCB | Let-through I²t vs MCCB withstand | Fuse clears at > MCCB interrupting capacity |
| Fuse-Contactor | Type 2 coordination | I²t below contactor weld threshold | Coordinated per IEC 60947-4-1 |
| Motor circuit | aM fuse + overload relay | Overload relay class vs fuse curve | Fuse rated for start current; relay for FLC |
IEC TR 61818 provides guidance on limiting fault energy through proper fuse selection. Current-limiting fuses that operate within their current-limiting range can reduce peak fault current to 5-10% of the prospective value. This characteristic is particularly valuable for arc flash energy reduction. Engineers should verify that the fuse’s current-limiting threshold (typically 30-50 times rated current) is below the minimum expected fault current at the installation point. The incident energy reduction achieved by current-limiting fuses can lower arc flash category from Category 3 or 4 to Category 1 or 0, dramatically improving worker safety and reducing PPE requirements.
1. What is the difference between gG and aM fuse-links?
A gG (general-purpose) fuse-link provides full-range overcurrent protection, covering both overloads and short-circuits. An aM (motor-circuit) fuse-link provides only short-circuit protection and must be paired with a separate overload relay for motor protection. The aM type has a higher continuous current rating relative to its physical size, allowing it to withstand motor starting currents without nuisance blowing.
2. How do ambient temperature and enclosure conditions affect fuse rating?
Fuses are typically rated at 25 °C ambient. For every 10 °C above this, the continuous current capability decreases by approximately 5-8% for gG types. In sealed enclosures, heat accumulation can reduce effective rating by 15-25%. Manufacturers provide temperature derating curves that should be applied during selection. For outdoor installations in tropical climates, a minimum of 20% derating is recommended.
3. Can IEC 61818 be used for DC fuse applications?
Yes, the report covers DC applications up to 1500 V DC. DC fuse selection requires additional considerations because DC arcs are more difficult to extinguish than AC arcs. The fuse must have a DC voltage rating at least equal to the system voltage, and the breaking capacity must be verified for DC fault conditions. The time constant of the DC circuit (L/R ratio) significantly influences fuse performance.
4. What is the recommended approach for verifying fuse discrimination in existing installations?
Field verification of discrimination involves measuring or calculating the minimum and maximum fault currents at each downstream point, comparing fuse operating times using published time-current curves, and confirming that the upstream fuse total clearing I²t exceeds the downstream fuse pre-arcing I²t with adequate margin. Software tools using actual manufacturer data are recommended for complex distribution systems.