IEC 62870-2015: Electrical Installations for Lighting and Beaconing of Aerodromes โ€” Safety Secondary Circuits

📌 Key Insight: IEC 62870 addresses a unique electrical safety challenge: aeronautical ground lighting (AGL) uses constant current series circuits operating at up to 5,000 V AC, where conventional protective devices (RCDs, overcurrent protection) cannot be applied. The standard introduces SELV/PELV-based protective provisions for secondary lamp supply systems.

1. ⚡ The Series Circuit Challenge in AGL Systems

Aeronautical ground lighting (AGL) is fundamentally different from conventional building electrical installations. While standard buildings use parallel-connected loads with constant voltage and load-dependent current, AGL systems use constant current series circuits where all lamps are connected in series. The constant current regulator (CCR) adjusts the voltage to maintain a constant current regardless of load variations, with input voltages up to 5,000 V AC rms.

This topology creates unique safety challenges:

  • Standard RCDs and overcurrent protective devices cannot be applied due to the series circuit structure
  • Insulation faults are often tolerated to maintain lighting availability — a critical requirement for aviation safety
  • Touch voltages can reach the full series circuit input voltage (up to 5 kV) depending on fault location
  • The rated voltage of individual equipment is defined by the constant current flowing through its impedance, not by a fixed supply voltage
⚠️ Critical Safety Context: IEC 61821 explicitly states that no work of any kind is normally permitted on live series circuits without first conducting a suitable Risk Assessment and using appropriate protective equipment. The introduction of lower-power LED-based lighting has made SELV/PELV secondary circuits feasible, significantly improving personnel safety during maintenance.

2. 🛡️ SELV/PELV Protective Measures

The standard applies the well-established protective measures of Safety Extra-Low Voltage (SELV) and Protective Extra-Low Voltage (PELV) to AGL secondary circuits. These measures are enabled by the transition from traditional incandescent lamps to LED technology, which requires significantly lower power and voltage.

Key requirements include:

  • Galvanic separation: The SELV/PELV secondary circuit must be electrically separated from the primary series circuit through an isolating transformer complying with IEC 61558-2-6
  • Voltage limits: SELV systems must not exceed the extra-low voltage limits under normal and single-fault conditions
  • Protective separation: Double insulation, reinforced insulation, or basic insulation with protective screening must separate the secondary circuit from the primary circuit
Table 1 — SELV vs. PELV in AGL Applications
Characteristic SELV System PELV System
Circuit earthing Not earthed (floating) May be earthed
Exposed conductive parts Not earthed May be earthed
Protective separation From all other circuits From all other circuits
Application in AGL Where maximum safety is required Where functional earthing is needed
Touch voltage safety Highest — no return path through earth Very high — earth path exists
Typical lighting application Runway edge lights, threshold lights Apron Floodlights, signage
🔧 Engineering Insight: The choice between SELV and PELV in AGL systems involves a trade-off between safety and practical installation requirements. SELV systems (floating, unearthed) provide the highest level of protection against electric shock because there is no earth return path, making a second fault necessary before hazardous currents can flow. PELV systems, while slightly less protective, are easier to implement for distributed lighting systems where functional earthing is required for EMC or operational reasons.

3. 🔍 Testing and Compliance Framework

IEC 62870 specifies both type tests and routine tests for AGL secondary circuits:

Type tests verify the design adequacy of the SELV/PELV power supply and include: dielectric strength testing, insulation resistance measurement, verification of protective separation, EMC emission and immunity testing, IP degree of protection verification, and marking durability tests.

Routine tests are performed on each production unit and include: dielectric strength test (at reduced voltage compared to type test), functional test, and visual inspection.

The standard references several complementary AGL standards:

  • IEC 61821: Maintenance of AGL constant current series circuits
  • IEC 61822: Constant current regulators for AGL
  • IEC 61823: AGL series transformers
  • IEC 61558-2-4 / -2-6: Safety of isolating transformers and safety isolating transformers
✅ System Design Recommendation: For system designers, Annex A provides a comparison of PELV and SELV characteristics to guide selection. The standard recommends that SELV be used as the default choice where possible, with PELV only adopted where functional requirements mandate earthing. In either case, the safety demarcation line — the physical boundary between the primary series circuit and the SELV/PELV secondary — must be clearly defined and documented in the installation design.
Table 2 — AGL Series Circuit Voltage Levels
Parameter Primary Series Circuit SELV/PELV Secondary
Maximum voltage 5,000 V AC rms ≤ 50 V AC / ≤ 120 V DC (typical)
Current type Constant current (CCR regulated) Constant voltage or current
Protection method Risk assessment + PPE per IEC 61821 SELV/PELV per IEC 60364-4-41
Fault tolerance Faults tolerated for availability Protective separation required
Personnel access Electrically skilled persons only Skilled persons (PELV) or ordinary (SELV)

4. 📋 FAQs

Q1: Why can’t standard RCDs be used in AGL series circuits?

Standard RCDs (Residual Current Devices) are designed for parallel-connected IT, TT, or TN networks where the supply voltage is constant and load current varies with impedance. In a constant current series circuit, the voltage adjusts automatically to maintain constant current, and earth faults may be tolerated without automatic disconnection. The series circuit topology and the need for continuous lighting availability make conventional RCD protection impractical and potentially hazardous.

Q2: What is the “safety demarcation line” in an AGL installation?

The safety demarcation line is the physical and electrical boundary between the primary series circuit (high voltage, constant current) and the secondary SELV/PELV circuit (low voltage, safe). It is typically located at the secondary terminals of the isolating transformer that feeds the lamp system. Everything on the primary side requires full PPE and skilled-person access; everything on the secondary side benefits from SELV/PELV protection. The standard requires clear marking at this boundary.

Q3: What EMC requirements apply to AGL SELV/PELV power supplies?

The standard references IEC 61000-6-4 (emission) and IEC 61000-6-2 (immunity) for industrial environments. The SELV/PELV power supply must meet applicable limits for conducted and radiated emissions, as well as immunity to electrostatic discharge, radiated RF fields, electrical fast transients, surges, and conducted disturbances. These requirements ensure reliable operation in the electromagnetically challenging airport environment.

Q4: How does the transition to LED affect AGL safety requirements?

The transition from incandescent to LED lamps in AGL has been a key enabler for IEC 62870. LED lamps require significantly less power than traditional incandescent lamps, making SELV/PELV secondary circuits technically and economically feasible. Lower power requirements mean lower secondary voltages, which in turn enables the use of standard SELV/PELV protective measures. This represents a fundamental shift in AGL safety philosophy — from “protect workers despite the hazard” (through PPE and procedures) to “eliminate the hazard at source” (through voltage limitation).

Leave a Reply

Your email address will not be published. Required fields are marked *