Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Aeronautical ground lighting (AGL) is fundamentally different from conventional building electrical installations. While standard buildings use parallel-connected loads with constant voltage and load-dependent current, AGL systems use constant current series circuits where all lamps are connected in series. The constant current regulator (CCR) adjusts the voltage to maintain a constant current regardless of load variations, with input voltages up to 5,000 V AC rms.
This topology creates unique safety challenges:
The standard applies the well-established protective measures of Safety Extra-Low Voltage (SELV) and Protective Extra-Low Voltage (PELV) to AGL secondary circuits. These measures are enabled by the transition from traditional incandescent lamps to LED technology, which requires significantly lower power and voltage.
Key requirements include:
| Characteristic | SELV System | PELV System |
|---|---|---|
| Circuit earthing | Not earthed (floating) | May be earthed |
| Exposed conductive parts | Not earthed | May be earthed |
| Protective separation | From all other circuits | From all other circuits |
| Application in AGL | Where maximum safety is required | Where functional earthing is needed |
| Touch voltage safety | Highest — no return path through earth | Very high — earth path exists |
| Typical lighting application | Runway edge lights, threshold lights | Apron Floodlights, signage |
IEC 62870 specifies both type tests and routine tests for AGL secondary circuits:
Type tests verify the design adequacy of the SELV/PELV power supply and include: dielectric strength testing, insulation resistance measurement, verification of protective separation, EMC emission and immunity testing, IP degree of protection verification, and marking durability tests.
Routine tests are performed on each production unit and include: dielectric strength test (at reduced voltage compared to type test), functional test, and visual inspection.
The standard references several complementary AGL standards:
| Parameter | Primary Series Circuit | SELV/PELV Secondary |
|---|---|---|
| Maximum voltage | 5,000 V AC rms | ≤ 50 V AC / ≤ 120 V DC (typical) |
| Current type | Constant current (CCR regulated) | Constant voltage or current |
| Protection method | Risk assessment + PPE per IEC 61821 | SELV/PELV per IEC 60364-4-41 |
| Fault tolerance | Faults tolerated for availability | Protective separation required |
| Personnel access | Electrically skilled persons only | Skilled persons (PELV) or ordinary (SELV) |
Standard RCDs (Residual Current Devices) are designed for parallel-connected IT, TT, or TN networks where the supply voltage is constant and load current varies with impedance. In a constant current series circuit, the voltage adjusts automatically to maintain constant current, and earth faults may be tolerated without automatic disconnection. The series circuit topology and the need for continuous lighting availability make conventional RCD protection impractical and potentially hazardous.
The safety demarcation line is the physical and electrical boundary between the primary series circuit (high voltage, constant current) and the secondary SELV/PELV circuit (low voltage, safe). It is typically located at the secondary terminals of the isolating transformer that feeds the lamp system. Everything on the primary side requires full PPE and skilled-person access; everything on the secondary side benefits from SELV/PELV protection. The standard requires clear marking at this boundary.
The standard references IEC 61000-6-4 (emission) and IEC 61000-6-2 (immunity) for industrial environments. The SELV/PELV power supply must meet applicable limits for conducted and radiated emissions, as well as immunity to electrostatic discharge, radiated RF fields, electrical fast transients, surges, and conducted disturbances. These requirements ensure reliable operation in the electromagnetically challenging airport environment.
The transition from incandescent to LED lamps in AGL has been a key enabler for IEC 62870. LED lamps require significantly less power than traditional incandescent lamps, making SELV/PELV secondary circuits technically and economically feasible. Lower power requirements mean lower secondary voltages, which in turn enables the use of standard SELV/PELV protective measures. This represents a fundamental shift in AGL safety philosophy — from “protect workers despite the hazard” (through PPE and procedures) to “eliminate the hazard at source” (through voltage limitation).