Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
IEC 62038 specifies safety requirements and associated test methods for mains-operated flexible cables, wires, and cords used for connecting electrical appliances and similar equipment to the supply network. Covering rated voltages up to 450/750 V, the standard addresses the full range of safety hazards: electric shock, fire propagation, mechanical damage, and thermal degradation. It applies to cords for household appliances, portable tools, temporary power distribution, and light-duty industrial equipment.
The standard defines a comprehensive suite of test methods including mechanical strength tests (tension, flexing, crushing, abrasion), heat resistance and fire propagation tests, insulation resistance and voltage withstand tests, and tests for resistance to moisture and chemicals. This article provides engineers and quality professionals with a detailed technical reference for the requirements and their practical application.
Insulation and sheath materials must meet minimum tensile strength and elongation at break values before and after thermal aging. For common PVC compounds, the standard requires tensile strength ≥ 12.5 N/mm² and elongation ≥ 150% (unaged). After aging in an air oven at 80 ± 2 °C for 7 days, retained tensile strength must be ≥ 85% and retained elongation ≥ 80%. These tests ensure the cord can withstand installation pulling forces and long-term thermal stress without cracking.
Flexible cords are subjected to a repeated flexing test using a standard flexing apparatus. The cord is passed over a series of pulleys and a reciprocating carriage applies ≥ 10,000 flexing cycles at a specified rate. After the test, the cord must withstand a voltage withstand test at 2000 V for 5 minutes with no breakdown. This simulates the repeated bending that occurs when an appliance cord is routinely handled, wrapped, and stored.
| Test | Condition | Acceptance Criterion |
|---|---|---|
| Tensile strength (PVC insulation) | Unaged | ≥ 12.5 N/mm² |
| Elongation (PVC insulation) | Unaged | ≥ 150% |
| Tensile retention | 7 d / 80 °C aging | ≥ 85% |
| Flexing endurance | ≥ 10,000 cycles | No breakdown at 2 kV |
| Crush resistance | 1 kN over 100 mm | No conductor exposure |
| Abrasion resistance | To specified depth | Insulation intact |
The cord must withstand a crushing force of 1 kN applied over a 100 mm length without exposing conductors. This is particularly relevant for cords laid on floors where furniture legs or casters may apply concentrated loads. Impact resistance is verified using a spring-loaded hammer test (2 J impact energy) that simulates accidental striking of the cord.
Insulation and sheath materials must not deform or flow at temperatures likely to be encountered in service. The standard specifies a heat-pressure test in which a sample is subjected to a defined pressure at elevated temperature (typically 90 ± 2 °C for PVC cords) for 1 hour. The indentation depth after recovery must not exceed 50% of the original wall thickness. This prevents conductor exposure when cords are routed near heat sources or subjected to sustained high ambient temperatures.
All cords covered by IEC 62038 must pass a flame propagation test. A 600 mm vertical sample is exposed to a 175 mm high propane burner flame (1 kW nominal heat output) for 60 seconds. The charred or flaming portion must not reach within 50 mm of the upper clamp, and any flaming droplets must not ignite underlying combustible material. This requirement is critical for preventing fire propagation along cable runs in buildings.
The insulation resistance between conductors and between each conductor and water (after immersion) must be ≥ 0.01 MΩ·km at 70 °C when measured at 500 V DC. This test verifies that the insulation compound provides adequate ionic purity and does not contain conductive contaminants. Low insulation resistance is a strong indicator of poor compounding quality or moisture ingress during manufacturing.
Each completed cord must withstand a 2000 V (for 300/300 V rated cords) or 2500 V (for 450/750 V rated cords) AC test voltage applied between conductors and between all conductors collectively to water for 5 minutes without breakdown. The leakage current during the test must not exceed 2 mA per meter of cord length.
The electrical resistance of each conductor must not exceed the values specified in IEC 60228 for the nominal cross-sectional area. For example, a 1.0 mm² annealed copper conductor must have a maximum DC resistance of 18.2 Ω/km at 20 °C. Excessive resistance indicates undersized conductors or poor-quality copper, both of which lead to overheating under load.
IEC 60227 (Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V) is a product standard for PVC cables that specifies detailed construction and performance requirements. IEC 62038 is a safety standard with test methods that may be referenced by product standards. In practice, compliance with IEC 60227 typically also satisfies the requirements of IEC 62038 for PVC cords, but the latter provides a broader framework applicable to multiple insulation types.
Yes, but with additional requirements. Outdoor cords must pass a cold impact test at -25 °C and a UV resistance test (720 h exposure per ISO 4892-2). The jacket material must be UV-stabilized, typically with 2-3% carbon black or a suitable hindered amine light stabilizer (HALS) package. Standard indoor PVC cords without UV stabilization will embrittle within 6-12 months of outdoor exposure.
The two numbers represent the rated voltage between conductor and earth / between conductors. A 300/300 V cord is suitable for applications where the voltage to earth does not exceed 300 V and the voltage between conductors does not exceed 300 V. A 450/750 V cord has a higher insulation level and is used for three-phase industrial connections where phase-to-phase voltage is 400 V. Common household cords in 230 V systems use 300/500 V rated cords.
IEC 62038 addresses factory-new cords. Field repairs (e.g., fitting a new plug or splicing a damaged section) fall outside the standard’s scope. However, any repair must restore the original level of safety. In practice, this means using the same or better grade of insulation material, maintaining conductor continuity and cross-section, and verifying insulation resistance and voltage withstand after repair. Many national wiring regulations prohibit splicing of flexible cords altogether.