Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
IEC 61869-4-2013 is Part 4 of the IEC 61869 instrument transformer series, specifically addressing combined instrument transformers. A combined transformer integrates CT and VT elements within the same insulation enclosure (typically SF₆ gas-filled or oil-immersed), sharing a common high-voltage conductor and insulation system to save installation space and reduce costs.
The standard applies to combined transformers with rated voltages of 72.5 kV and above, covering electrical performance, insulation requirements, accuracy classes, temperature rise limits, and electromagnetic compatibility. Corrigendum cor1-2014 primarily corrected partial discharge measurement procedures and nameplate marking clauses — care should be taken to reference the corrected version.
A combined transformer must simultaneously satisfy the accuracy requirements of both CT and VT. The standard defines multiple accuracy classes ranging from metering grades (0.1, 0.2S) to protection grades (5P, 10P).
CT errors include current (ratio) error and phase displacement. In a combined structure, the presence of VT windings may alter the magnetic field distribution around the primary conductor, causing CT errors to deviate from expected values. Proper magnetic shielding (e.g., high-permeability alloy shields) is required during design to minimize this effect.
VT voltage error and phase displacement are primarily influenced by no-load current and leakage impedance. Combined transformers typically employ capacitive voltage divider (CVT) or inductive (IVT) designs. CVT designs are more common in combined transformers since the capacitor stack can simultaneously serve as insulation support.
| Accuracy Class | Application | Current Error Limit (±%) | Phase Displacement Limit (±minutes) | Combined Design Impact |
|---|---|---|---|---|
| 0.2S | Precision energy metering | 0.2 | 10 | Extra magnetic shielding |
| 0.5S | Boundary energy metering | 0.5 | 15 | Standard shielding |
| 1.0 | Distribution metering | 1.0 | 30 | Basic shielding |
| 5P | Overcurrent protection | 1.0 | 60 | Saturation characteristic |
| 10P | Earth fault protection | 3.0 | — | Remanence focus |
Insulation Design: The main insulation of a combined transformer must withstand the superimposed electric field stress of both CT and VT windings. The standard requires lightning impulse (LI), switching impulse (SI), and power-frequency voltage withstand tests. Altitude correction and pollution class considerations should follow IEC 60071-1.
Partial Discharge Measurement: Partial discharge (PD) level is a critical indicator of insulation quality. The standard specifies that at 1.2 Um/√3 voltage, PD levels must not exceed 10 pC (GIS type) or 20 pC (open-terminal type). Corrigendum cor1-2014 clarified test circuit connections and background noise subtraction methods.
Temperature Rise and Thermal Management: The combined structure causes CT and VT winding heat to accumulate. The standard specifies temperature rise limits (coil ≤ 65 K, core ≤ 50 K). For high-current applications (≥2000 A), forced air cooling or enlarged oil/SF₆ convection paths are recommended.
A: Key advantages include reduced installation space (approximately 40% footprint reduction), lower overall cost (shared insulation and enclosure), fewer sealing points reducing oil/gas leak risk, and simplified primary connections. Limitations include reduced flexibility after fixed CT/VT ratios are chosen and the need for complete replacement if either element fails.
A: Yes. Combined transformers typically feature multiple secondary windings: a high-accuracy winding (0.2S class) for metering and one or two protection-grade windings (5P or 10P class) for relaying. Each winding uses independent cores and shielding for electrical isolation and magnetic decoupling.
A: The corrigendum addressed: corrected detailed wiring diagrams for partial discharge test circuits, clarification of combined transformer nameplate marking format, and adjustment of ambient temperature correction factors for temperature rise tests. Users should reference the consolidated version incorporating the corrigendum.
A: SF₆ gas may liquefy at low temperatures (below -30°C), degrading insulation performance. In cold regions, low-temperature SF₆ mixtures (with N₂ or CF₄) or heating devices to maintain gas compartment temperature should be specified. The standard’s annex provides SF₆ gas pressure-temperature characteristic curves for design reference.