Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
IEC 61868-1998 “Live working — Care, maintenance and testing of tools” applies to all insulating tools used for AC or DC live working, including insulating sticks, operating rods, insulating tongs, voltage detectors, and general-purpose live working tools. The standard does not cover specialized equipment such as live working robots.
The core philosophy of the standard is “preventive maintenance over passive replacement.” Through daily inspection, periodic cleaning, proper storage, and scheduled electrical testing, insulation defects can be identified and rectified before they develop into hazardous failures. For live working tools, even minor surface damage (scratches, moisture absorption, carbon tracking) can lead to flashover under high voltage, posing serious risk to operator safety.
IEC 61868 specifies two main test categories: Type Tests and Routine Tests. For in-service tools, the focus is on routine tests, including electrical insulation tests and mechanical strength tests.
Insulation testing is the key method for verifying that tools meet insulation performance requirements. The test voltage depends on the tool’s maximum operating voltage class. The standard requires power-frequency AC voltage withstand tests with a duration of 1 minute, with no flashover or breakdown as the acceptance criterion.
The standard recommends routine test intervals not exceeding 6 months. Under severe environmental conditions (high humidity, chemical contamination, extreme temperatures), intervals should be shortened to 3 months. Each tool must have an independent maintenance record documenting manufacture date, commissioning date, test results, and maintenance history.
| Tool Type | Max Operating Voltage (kV) | Test Voltage (kV) | Test Interval | Acceptance Criterion |
|---|---|---|---|---|
| Insulating Stick | 12 | 44 | 6 months | No flashover/breakdown |
| Insulating Stick | 36 | 70 | 6 months | No flashover/breakdown |
| Insulating Stick | 72.5 | 105 | 6 months | No flashover/breakdown |
| Insulating Stick | 170 | 195 | 6 months | No flashover/breakdown |
| Voltage Detector | — | Rated voltage ×1.5 | 6 months | Audio/visual indication OK |
| Insulating Tongs | — | Rated voltage ×3 | 3 months | No flashover/breakdown |
Storage Environment Control: Storage conditions directly impact insulating tool service life. The standard recommends a storage temperature range of 10°C to 25°C with relative humidity not exceeding 60%. Tools should be stored vertically by hanging to avoid deformation. Insulating tools must not be mixed with ordinary tools to prevent oil and metal particle contamination of insulating surfaces.
Cleaning and Decontamination: Dirt and grease should be removed immediately after use. Use neutral detergents or isopropyl alcohol (concentration not exceeding 70%). Acetone, gasoline, or other solvents that attack insulating materials are strictly prohibited. After cleaning, tools should be air-dried at room temperature for at least 24 hours before insulation testing or storage.
A: Absolutely not. Tools beyond the test expiry date are considered “untested” — their insulation performance is unverified, and using them carries unacceptable safety risk. Even if tools appear intact, they must pass testing before being returned to service. It is recommended to label the next test due date directly on each tool.
A: In some cases, yes, but the DC test voltage should equal the peak AC test voltage (i.e., multiplied by √2). However, DC testing cannot fully reveal internal air gap discharge issues within insulating materials. The standard recommends AC withstand testing as the primary method; DC is considered only when AC test equipment is unavailable on site.
A: Insulation resistance testing provides a reliable indicator: under 500 V megger testing, the insulation resistance should be no less than 1000 MΩ. Values below this threshold indicate moisture absorption or surface contamination. Moisture-affected tools can be dried in a 40°C~50°C oven for 16~24 hours and then retested.
A: Generally not. In-service tools require only routine testing, with test voltages moderately below type test standards (approximately 75%~80% of rated test voltage). However, if a tool has undergone major repair or replacement of critical components, full type testing should be performed.