IEC 61513-2011 establishes requirements and recommendations for the overall I&C architecture and for I&C systems important to safety in nuclear power plants. The standard applies to all I&C functions and systems that contribute to safety, including the reactor protection system, engineered safety features actuation systems, safety display systems, and auxiliary supporting systems. It covers the complete lifecycle from concept through design, implementation, commissioning, operation, maintenance, and decommissioning.
The standard introduces a safety classification framework that categorises I&C systems based on their safety significance. Class 1 systems perform safety functions whose failure could lead to a design basis accident directly. Class 2 systems perform functions that mitigate design basis accidents or support Class 1 functions. Class 3 systems perform safety-related functions with less severe consequences. Non-classified I&C systems have no direct safety function but may influence safety through operator information or process control. This graded approach ensures that the rigour of design, qualification, and quality assurance is proportional to the safety significance of the system.
IEC 61513 specifies detailed design requirements for each safety class:
| Requirement Area | Class 1 (Highest) | Class 2 | Class 3 |
|---|---|---|---|
| Redundancy | 2× or 4× division (typically 4× for RPS) | Single or 2× depending on application | Single channel acceptable |
| Diversity | Required for CCF prevention | Recommended where practical | Not required |
| Separation (physical & electrical) | Complete physical, electrical, and functional | Separation from Class 1; graded within Class 2 | Separation from Class 1 & 2 |
| Self-Diagnostic Coverage | ≥ 98% | ≥ 95% | ≥ 90% |
| Software V&V Independence | Independent team (organisational separation) | Independent team (may share organisation) | Same team with independent reviewer |
| Qualification (environmental) | Full DB accident conditions | DB accident conditions (reduced severity) | Normal plus abnormal conditions |
| Seismic Qualification | SSE level (0.3g–0.5g ZPA) | SSE level | OBE level or better |
| EMI/RFI Immunity | Severe (20 V/m field strength) | Severe (20 V/m) | Moderate (10 V/m) |
The standard requires that the I&C architecture incorporate diversity to protect against common cause failures (CCFs) that could defeat redundant channels. For critical safety functions, the standard recommends a diverse actuation system (das) that uses different technology, different principle of operation, or different manufacturer than the primary protection system. For example, a primary reactor protection system using a microprocessor-based platform should be backed by a diverse system using hardwired analogue technology or a different type of programmable platform. The diverse system must be capable of bringing the plant to a safe shutdown condition independently of the primary system.
The implementation of IEC 61513 requirements in a modern nuclear power plant I&C upgrade presents several significant engineering challenges. One of the most demanding is meeting the separation requirements between redundant divisions while maintaining the ability to perform cross-division communication for coordinated actuation. The standard permits communication between divisions only through isolated data links that prevent any credible failure in one division from degrading another. Typical implementations use fibre-optic communication with optical isolators providing guaranteed electrical isolation of at least 20 kV.
The software V&V requirements under IEC 61513 are among the most stringent in any industry. For Class 1 software, the standard requires that V&V be performed by a team that is organisationally independent from the software development team, with a separate reporting line and budget. The V&V activities must cover all lifecycle phases and include: requirements tracing, design review, code inspection, static analysis, dynamic testing, integration testing, and formal verification of critical algorithms. The standard also requires the use of software tools that are qualified for the target safety class — meaning that tools used for code generation or verification must themselves be validated or produce outputs that can be independently verified.
The standard also addresses the important issue of I&C system modernisation in existing plants. For plants undergoing I&C upgrades, IEC 61513 provides guidance on the transition strategy, including the management of mixed analogue/digital systems during the transition period. Key considerations include: maintaining the safety function during cutover, ensuring that hybrid configurations do not introduce new CCF vulnerabilities, and validating that the upgraded system meets current (not original) safety requirements. The standard recommends a phased approach where non-safety systems are upgraded first to gain experience, followed by Class 3, Class 2, and finally Class 1 systems.
IEC 61513 is the overarching I&C system standard covering architecture, design, and qualification for all safety classes. IEC 61226 specifically addresses the classification of I&C functions according to their safety significance and defines the criteria for assigning functions to Classes 1, 2, and 3. The two standards are complementary and are intended to be used together.
While IEC 61513 predates the comprehensive cybersecurity standards now applicable to nuclear I&C (particularly IEC 62645), it requires that digital safety systems incorporate provisions for security. This includes physical access control to safety system cabinets, secure communication protocols, and protection against malicious code. The standard requires that security measures do not degrade safety performance or create spurious actuation paths.
The I&C architecture refers to the overall structure and organisation of all I&C systems and functions within a nuclear power plant. It defines how systems are organised into divisions, how they communicate, how they interact with plant operators, and how the defence-in-depth principle is implemented at the I&C level. The architecture must be documented in an I&C architecture description that is maintained throughout the plant lifecycle.
Yes, COTS equipment can be used, but it must be qualified for the target safety class. The qualification process for COTS equipment is more demanding because the design information (failure modes, failure rates, design assumptions) may not be fully available from the vendor. The standard requires additional verification and validation activities for COTS equipment, including failure mode analysis, extended environmental testing, and independent assessment of the vendor’s quality processes.