Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
IEC 61439-5 is part of the comprehensive IEC 61439 series of standards for low-voltage switchgear and controlgear assemblies (ACS). The series replaced the earlier IEC 60439 standard family and introduced significant changes in verification methods, temperature rise limits, and short-circuit rating definitions. Part 5 specifically covers assemblies for public electricity distribution networks, including those installed outdoors (street cabinets, kiosk substations) and in public buildings, where access by non-skilled persons is possible.
The standard applies to assemblies with a rated voltage not exceeding 1000 V AC (at 50/60 Hz) or 1500 V DC. It covers assemblies used for distribution of electrical energy in public networks, typically incorporating incoming feeders, outgoing feeders, metering equipment, and control/protection devices. The scope includes both type-tested assemblies (TTA) and partially type-tested assemblies (PTTA), though the emphasis is on verification through a combination of type testing and derived rules established in IEC 61439-1.
Temperature rise limits are a critical aspect of IEC 61439-5. The standard defines maximum temperature rise values for various components within the assembly, including busbars, connections, switchgear components, and external enclosures. For assemblies installed in public areas, the external enclosure temperature rise is particularly important — limits are set to prevent burns to the public and degradation of adjacent materials.
| Component / Location | Maximum Temperature Rise (K) | Measurement Method | Reference Ambient |
|---|---|---|---|
| Busbars (bare copper) | 105 | Thermocouple / RTD | 35°C |
| Busbar joints and connections | 70 | Thermocouple | 35°C |
| External enclosure (metallic) | 30 | Contact thermometer | 35°C |
| External enclosure (non-metallic) | 35 | Contact thermometer | 35°C |
| Internal wiring | 70 (depends on insulation class) | Thermocouple | 35°C |
IEC 61439-5 defines the short-circuit withstand rating (Icw) for assemblies in public distribution networks. Typical rated short-time withstand currents range from 10 kA to 50 kA for 1 second duration, depending on the transformer capacity and network fault level at the installation point. The standard specifies three methods for short-circuit verification: type testing, extrapolation from tested configurations (derived rules), and calculation. The derived rules allow manufacturers to rate assembly variants without testing each configuration, significantly reducing certification costs.
For outdoor public distribution assemblies, the standard mandates minimum IP ratings based on installation location. IP34D (protected against sprayed water and wire access) is the minimum for outdoor cabinets, while IP54 (dust-protected and splash-proof) is typically required for locations with higher contamination risk. The standard also specifies IK code requirements for mechanical impact resistance — IK10 (20 J impact energy) is commonly required for publicly accessible enclosures.
The verification framework in IEC 61439-5 represents a significant evolution from its predecessor. The standard recognizes three verification routes: design verification by testing (type tests), design verification by derived rules (extrapolation from tested configurations), and design verification by calculation. This flexible approach allows manufacturers to optimize their certification strategy based on product portfolio breadth and cost considerations.
The derived rules for temperature rise verification are particularly valuable. They allow engineers to predict the thermal behavior of assembly variants based on tested reference configurations, considering factors such as enclosure size, busbar cross-section, number of outgoing circuits, and installed power dissipation. Similarly, short-circuit withstand can be verified by calculation using the adiabatic heating equation (I²t = k²S²) with appropriate material constants defined in the standard.
| Verification Aspect | Type Test Preferred | Derived Rules Apply | Calculation Method |
|---|---|---|---|
| Temperature rise | Full assembly | Enclosure variants, busbar extensions | For simple configurations only |
| Short-circuit withstand | Busbar system, main circuits | Branch circuits from main | Adiabatic I²t, peak current |
| Dielectric properties | Full assembly | Component substitution | Not applicable |
| Mechanical operation | Mechanisms, interlocks | Similar mechanisms | Not applicable |
| Degree of protection (IP) | Enclosure type | Geometrically similar enclosures | Not applicable |
Assemblies for public distribution face unique design challenges. They must be tamper-resistant to prevent unauthorized access (requiring specialized tool-operated fasteners), while remaining serviceable by utility personnel. Cable termination compartments must accommodate a wide range of incoming cable sizes and types, with adequate space for bending radii and gland plates. The standard provides guidance on minimum clearances and creepage distances that must be maintained between live parts and between live parts and the enclosure.
Metering compartments in public distribution assemblies require particular attention. IEC 61439-5 references national metering regulations that often impose additional requirements on sealing, access restriction, and accuracy verification. The segregation of metering from non-metering compartments is typically required, with separate locking arrangements to prevent meter tampering.
Under IEC 61439, the distinction between TTA and PTTA is less rigid than under the previous IEC 60439 series. The standard provides a unified verification framework where any combination of type testing, derived rules, and calculation can be used. PTTA assemblies typically use tested main busbar systems with derived rules applied to branch configurations. The manufacturer must document the verification methods used in the technical documentation.
The required Icw is determined by the fault level at the point of installation. For secondary distribution substations, typical transformer sizes of 315 kVA to 1000 kVA correspond to prospective fault currents of 10 kA to 25 kA at the LV terminals. The Icw should be at least equal to the prospective RMS short-circuit current. A safety margin of 10–20% is recommended to account for future grid upgrades.
While IEC 61439-5 does not directly address seismic requirements, IEC 61439-1 Appendix F provides guidance on seismic qualification for assemblies. For public distribution in seismic zones, additional bracing, flexible busbar connections, and enhanced enclosure anchoring are recommended. The assembly should be verified to withstand the response spectrum defined in relevant building codes (e.g., IBC, Eurocode 8).
IEC 61439-5 requires the manufacturer to provide: a rating plate with all specified electrical ratings, a wiring diagram or schedule, instruction manuals for installation, operation and maintenance, and a declaration of conformity with the standard. For assemblies incorporating metering, additional documentation required by the local metering authority must also be provided.