Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
IEC 61378-1:2011 applies to converter transformers for all types of industrial applications, including variable frequency drives (VFDs), DC power supplies, electrochemical plants (aluminium smelters, chlor-alkali), electric arc furnace power supplies, and high-voltage DC (HVDC) transmission auxiliary systems. The standard covers oil-immersed and dry-type transformers with two or more windings, designed for operation with one or more windings connected to a converter bridge.
The fundamental difference between a converter transformer and a conventional power transformer lies in the nature of the load current. A converter transformer winding connected to a converter bridge carries a current rich in harmonics (typically 6-pulse: 5th, 7th, 11th, 13th; 12-pulse: 11th, 13th, 23rd, 25th) and may be subject to DC current components from asymmetric converter firing. These harmonics cause additional winding losses (eddy current and circulating current), stray flux heating in structural components, and increased core losses.
| Parameter | Conventional Power Transformer | Converter Transformer | Design Implication |
|---|---|---|---|
| Load current waveform | Sinusoidal (THD < 2%) | Non-sinusoidal (THD 10-30%) | Increased winding eddy losses |
| Voltage waveform | Sinusoidal | Fundamental + harmonics + DC offset | Combined AC+DC dielectric design |
| Winding connection | Standard vector groups | Extended delta, double-star, zigzag | Phase-shifting for harmonic cancellation |
| Load losses | I²R + eddy + stray (standard ratios) | I²R + eddy (2-3x higher) + stray + harmonic | Larger conductors, reduced current density |
| No-load losses | At pure sinusoidal voltage | At fundamental voltage + harmonics | Increased core loss from harmonic voltages |
| DC bias tolerance | Not required | Must withstand DC component from firing asymmetry | Core design for DC flux tolerance; series blocking capacitor sometimes needed |
| Short-circuit impedance | Standard range (6-15%) | Often higher (10-25%) for current limiting | Limits converter fault current; affects reactive power |
IEC 61378-1 establishes methods for determining the rated power and load capability of converter transformers based on the harmonic current spectrum of the connected converter. The standard defines the concept of equivalent continuous rated current, which accounts for the additional heating effect of harmonic currents. The winding loss calculation uses the harmonic loss factor FHL (ratio of total load loss under harmonic current to the load loss at fundamental current) and the eddy loss factor FHL-EC specifically for eddy losses.
For a typical 6-pulse converter drive, the harmonic spectrum includes the 5th (20% of fundamental), 7th (14%), 11th (9%), 13th (8%), and higher-order harmonics. The resulting winding eddy loss can be 1.5-2.5 times the eddy loss for a pure sinusoidal current of the same RMS value. The standard provides detailed equations for calculating these factors based on the known harmonic spectrum, enabling the transformer designer to accurately determine the winding temperature rise.
| Converter Type | Pulse Number | Characteristic Harmonics | Typical FHL | Application |
|---|---|---|---|---|
| 6-pulse thyristor | 6 | 5, 7, 11, 13, 17, 19… | 1.15-1.35 | VFDs, small rectifiers (< 5 MW) |
| 12-pulse thyristor | 12 | 11, 13, 23, 25, 35, 37… | 1.05-1.15 | Large drives, electrochemical (> 5 MW) |
| 24-pulse (multi-winding) | 24 | 23, 25, 47, 49… | 1.02-1.08 | Very large rectifiers, harmonic-sensitive plants |
| PWM active rectifier | Not fixed | Near-sinusoidal current | 1.01-1.05 | Modern regenerative VFDs, UPS systems |
One of the unique aspects of IEC 61378-1 is its treatment of dielectric testing for converter transformers, which must withstand combined AC and DC voltages during operation. The valve-side windings experience a superimposed DC voltage component that displaces the AC voltage reference, creating a combined stress that conventional power transformer insulation systems are not designed to handle.
The standard specifies a dielectric test sequence that includes: AC withstand test (applied between windings and ground), DC withstand test (applied to valve-side windings at 1.5-2.0 times the rated DC voltage), and partial discharge measurement (critical for converter transformers because the harmonic-rich voltage waveform continuously stresses the insulation with high dv/dt, which can initiate and sustain partial discharge at lower peak voltages than power frequency).
The combined AC-DC dielectric design must account for the fact that the voltage distribution across the winding under DC stress is resistive (determined by insulation resistivity) rather than capacitive (determined by insulation permittivity as in AC). This creates a voltage distribution that is strongly temperature-dependent, since the resistivity of oil-impregnated paper insulation decreases exponentially with increasing temperature. At full load with hot oil, the DC voltage distribution may shift significantly compared to the cold condition, potentially overstressing the line-end turns of the valve-side winding.
Converter transformers almost always require on-load tap changers (OLTCs) to compensate for the voltage drop in the converter bridge under varying load conditions and to adjust the DC output voltage. IEC 61378-1 specifies that the tapping range, step voltage, and OLTC type must be selected considering the converter’s firing angle range. The tapping range for typical industrial converter transformers is ±10-20% in 1.25% or 2.5% steps.
The standard requires that the tap changer be rated for the harmonic-rich current, not just the fundamental current. The harmonic content increases the RMS current for the same DC output power, and the tap changer’s thermal capability must be verified for the total RMS current including harmonics. This is a frequently overlooked detail that can lead to OLTC contact overheating and premature failure.
A: Not recommended. Standard power transformers are designed for sinusoidal load current. When subjected to converter-fed harmonic currents, the winding eddy losses can increase by 50-150%, leading to unacceptable temperature rise, accelerated insulation aging, and reduced service life. Additionally, the dielectric design does not account for combined AC+DC voltage stress on the valve-side windings.
A: The valve-side winding is connected to the converter bridge and experiences harmonic currents and combined AC-DC voltage stress. The line-side winding is connected to the AC power system and experiences near-sinusoidal conditions. The two sets of windings have fundamentally different design requirements — the valve-side winding requires enhanced eddy loss capability, combined AC-DC insulation, and sometimes DC bias tolerance.
A: The short-circuit impedance of a converter transformer is typically higher (10-25%) than for a conventional power transformer (6-12%). Higher impedance limits the DC fault current through the converter thyristors/diodes but increases reactive power consumption (commutation reactive power). The optimum impedance is a trade-off between fault current limitation and reactive power compensation cost, typically optimised at 12-18% for most industrial applications.
A: IEC 61378-1 covers industrial converter transformers. For HVDC converter transformers rated above HVAC voltages, IEC 61378-2 (the HVDC-specific supplement) provides additional requirements for higher DC voltage withstand, space charge management, and the more extensive type testing required for HVDC applications. Both standards share the same fundamental methodology, but Part 2 includes the additional margin and testing required for utility-scale HVDC (typically 80-800 kV DC).