Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
IEC 61363-1:1998 establishes procedures for calculating prospective short-circuit currents in AC electrical installations on ships and offshore units. Unlike land-based utility grids where fault currents are predominantly dictated by transformer impedance and upstream network capacity, marine power systems operate as isolated islands with relatively low short-circuit capacity. Generators constitute a much larger proportion of total system impedance, and their transient and subtransient behaviour dominates the early stages of a fault event.
The standard applies to low-voltage and medium-voltage marine installations up to 15 kV, covering both three-phase AC and single-phase AC systems. It addresses the calculation of:
The standard was developed in collaboration with major classification societies (Lloyd’s Register, DNV, ABS, Bureau Veritas) and directly supports marine switchgear selection and protection coordination studies.
The most critical distinction in marine short-circuit analysis lies in the modelling of synchronous generators. In a shipboard system, generators may contribute 60-80% of the total fault current, compared to less than 10% in most land-based industrial systems. IEC 61363-1 provides detailed equivalent circuit models that capture the subtransient, transient, and steady-state regimes.
| Parameter | Symbol | Typical Range (Marine Generator) | Impact on Fault Current |
|---|---|---|---|
| Subtransient reactance | Xd“ | 10-18% | Determines initial fault current peak |
| Transient reactance | Xd‘ | 18-30% | Governs current after 3-5 cycles |
| Synchronous reactance | Xd | 150-300% | Sets steady-state fault level |
| Stator resistance | Ra | 0.5-2% | DC component decay rate |
| Subtransient time constant | Td“ | 10-30 ms | Duration of subtransient phase |
| Transient time constant | Td‘ | 0.5-2.0 s | Duration of transient phase |
The symmetrical breaking current contributed by a generator at time t after fault inception is given by:
I_b_gen(t) = [(Xd" - Xd') · e-t/Td" + (Xd' - Xd) · e-t/Td' + Xd] / (√3 · Un)
A key engineering insight rarely emphasised in general textbooks is that the generator excitation system response significantly affects the fault current after approximately 100 ms. Modern brushless exciters with fast-acting AVRs can sustain generator fault current contribution longer than the subtransient data alone would suggest. For selectivity studies involving time-delayed overcurrent relays (typical settings: 0.2-0.4 s), this excitation boost must be considered or the relay coordination study will be unconservative.
Induction motors make a substantial contribution to marine short-circuit currents, particularly in systems with large pump, fan, and propulsion-related loads. IEC 61363-1 treats motor contributions as a decaying AC current superimposed on the generator-fed fault current.
The standard classifies motors into three groups:
The total short-circuit current at any location is the phasor sum of contributions from all generators and motors connected to the system, considering the impedance path from each source to the fault point. The standard provides a simplified algebraic summation method that yields conservative (slightly higher) values suitable for equipment rating, and an accurate phasor summation method for time-domain studies.
| Source | Ik” (kA) | ip (kA) | Ib @ 50ms (kA) | Ib @ 100ms (kA) |
|---|---|---|---|---|
| Generator #1 (2.5 MVA) | 18.2 | 46.4 | 14.8 | 12.1 |
| Generator #2 (2.5 MVA) | 18.2 | 46.4 | 14.8 | 12.1 |
| HV Motors (total 1.2 MW) | 8.5 | 18.7 | 4.2 | 2.1 |
| LV Motors (total 0.8 MW) | 5.6 | 12.3 | 2.8 | 1.4 |
| Total | 50.5 | 123.8 | 36.6 | 27.7 |
The rapid decay of motor contributions (time constants typically 30-80 ms) means that by 100 ms after fault inception, motor current has dropped by 60-80%. This has profound implications for protection grading — time-delayed breaker trips must be set with the understanding that motor-fed fault current decays significantly before the breaker opens.
The calculated short-circuit currents serve three primary engineering purposes in marine electrical design:
The standard explicitly addresses the unique marine scenario of parallel generator operation with unequal ratings, common in vessels with shaft generators or harbour generators. When generators of different ratings operate in parallel, the fault current distribution is strongly influenced by the relative subtransient impedances, and the smaller machine may experience a disproportionately high contribution during the first few cycles — a potential overstressing condition for its associated breaker.
No. IEC 60909 assumes an infinite bus supply which does not reflect the finite generator capacity in a shipboard system. Using IEC 60909 will overestimate steady-state fault currents and misrepresent the DC decay characteristics, leading to incorrect breaker selection and protection settings.
The 1998 edition covers only AC systems. For DC marine distribution (increasingly common in battery-hybrid and all-electric vessels), IEC 61660-1 provides the relevant short-circuit calculation methodology. However, the system modelling philosophy (source contribution decomposition, time-domain decay) established in IEC 61363-1 applies by analogy.
VFD-fed motors do not contribute to fault current in the same manner as direct-on-line motors because the VFD’s power electronics block regenerative current within 1-2 ms. IEC 61363-1 acknowledges this and permits exclusion of VFD-fed motor contributions from the calculation, provided the VFD is properly rated for through-fault capability.
For simple radial systems, the algebraic method in Annex A is sufficient. For meshed systems with multiple bus-tie breakers (common in DP3 vessels), time-domain simulation using IEC 61363-1 generator models is strongly recommended. Software tools such as ETAP, SKM PTW, and DIgSILENT PowerFactory all support IEC 61363-1 calculation modules.