Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
IEC 61138 — Live working — Cables for earthing and short-circuiting equipment — is the definitive international standard governing flexible power cables used in temporary earthing and short-circuiting assemblies for live working (also referred to as “live line work” or “hot sticking” in North America). The standard applies to single-core and multi-core flexible cables rated for use in AC systems with nominal voltages not exceeding 25 kV phase-to-phase.
The fundamental engineering purpose of these cables is to create a deliberately low-impedance path to earth that can safely conduct the full prospective fault current until protective devices operate, while maintaining galvanic integrity and preventing dangerous voltage gradients from developing across the work zone. This is fundamentally different from ordinary power cables, which are designed primarily for continuous current-carrying capacity with short-circuit withstand as a secondary consideration.
Conductor design is arguably the most critical element differentiating IEC 61138 cables from general-purpose power cables. The standard mandates the use of Class 5 or Class 6 flexible copper conductors as defined by IEC 60228. These conductors consist of very fine individual wires — typically 0.21 mm diameter or finer — assembled in a concentric-lay or bunch-stranded configuration. For larger cross-sectional areas (50 mm² and above), a multiple-strand construction is employed, where several pre-stranded bundles are themselves stranded together in a second operation.
The rationale for such fine stranding is threefold. First, it dramatically reduces the cable’s bending stiffness, allowing it to be handled manually without excessive force. Second, it distributes cyclic bending strain across many individual wire surfaces, greatly improving fatigue life. Third, the increased surface-area-to-cross-section ratio improves heat dissipation under short-circuit conditions. The standard requires cables to pass a bending test at both room temperature and −25 °C without conductor fracture or insulation cracking — a demanding specification that directly validates field performance in winter conditions.
IEC 61138 specifies thermosetting elastomeric compounds — principally ethylene-propylene rubber (EPR) or equivalent high-performance rubber blends — for both insulation and sheath. Thermoset materials are chosen over thermoplastics (PVC, polyethylene) for several fundamental technical reasons:
The outer sheath — typically chloroprene rubber (CR) or chlorinated polyethylene (CPE) — provides mechanical protection against abrasion, cutting, and environmental degradation. The standard specifies minimum tensile strength, elongation at break, and retention of these properties after accelerated thermal ageing.
| Parameter | Requirement | Remarks |
|---|---|---|
| Insulation material | EPR or equivalent elastomer | Thermosetting, not thermoplastic |
| Insulation thickness (min.) | ≥ 1.5 mm (basic insulation) | Depends on voltage grade & conductor size |
| Earthing cable colour | Green/yellow (dual colour) | Per IEC 60445 safety colour code |
| Short-circuit cable colour | Black | Quick field identification |
| Rated voltage U₀/U | 0.6/1 kV and above | For LV and MV distribution systems |
| AC test voltage | 3.5 kV for 5 minutes | Routine factory test |
| Continuous operating temp. | 90 °C (conductor) | Normal load conditions |
| Short-circuit temp. (max.) | 250 °C (conductor) | Duration ≤ 5 s |
Every length of IEC 61138 cable must pass a routine AC voltage withstand test at the factory. For cables rated 0.6/1 kV, the test voltage is 3.5 kV (AC, 50/60 Hz) applied between conductor and earth (water bath or metallic foil electrode) for 5 minutes without flashover or breakdown. For higher voltage ratings, the test voltage scales accordingly.
Beyond the routine test, type tests include partial discharge measurement for cables rated above 6/10 kV. Although earlier editions of IEC 61138 did not mandate partial discharge testing, modern industry practice — and the current edition — increasingly requires PD measurement at 1.5 to 2 times the rated voltage to ensure the insulation system is free of voids, contaminants, or interfacial defects that could initiate premature electrical treeing and eventual failure under repeated switching or transient overvoltage stresses.
The most critical performance attribute of earthing and short-circuiting cables is their ability to withstand the immense thermal energy of a fault current without fusion or insulation collapse. The conductor’s short-circuit current capacity is governed by the adiabatic heating relationship:
I²t ≤ K² × S²
Where I is the short-circuit current in amperes, t is the fault duration in seconds, S is the conductor cross-sectional area in mm², and K is a material-dependent constant (approximately 115–135 for copper, depending on the permissible temperature rise of the adjacent insulation).
This relationship has profound practical implications. Consider a 50 mm² cable subjected to a 25 kA fault with a clearing time of 0.5 seconds: the I²t value is 312.5 × 10⁶ A²s, yielding an equivalent thermal stress of 125 A²s/mm² — well within the copper conductor’s capacity but approaching the limit for the insulation system. Increasing the clearing time to 2 seconds (e.g., with a downstream fuse coordination issue) drives the stress to 500 A²s/mm², which may exceed the cable’s rated short-circuit withstand.
IEC 61138 subjects cables to a battery of mechanical type tests that are either absent or less stringent in general-purpose cable standards:
These tests directly replicate the mechanical stresses encountered in field use: cables dragged over gravel and concrete, stepped on, pinched between equipment cases, and bent around sharp edges in freezing weather. Passing these tests gives engineers confidence that the cable will perform its safety function even after extended service in harsh environments.
Selecting the appropriate IEC 61138 cable for a specific installation requires a systematic evaluation of several interdependent factors:
Even the highest-quality IEC 61138 cable requires diligent field care to maintain its protective function. The following practices are recommended:
Not recommended. While IEC 61138 cables are technically capable of carrying current, they are optimised for temporary deployable use. The finely stranded conductors and elastomeric insulation are more expensive and more susceptible to mechanical damage from crushing and sustained vibration than the armoured or heavy-duty cables typically specified for fixed installations. For permanent wiring, use cables designed to IEC 60502 or national wiring regulations.
Compliant cables are marked on the insulation surface with the manufacturer’s name, standard reference (IEC 61138), conductor cross-section, voltage rating, and year of manufacture. For procurement, require the supplier to provide a type test certificate from an accredited third-party laboratory such as TÜV, UL, KEMA, or DEKRA. Be wary of cables that claim “IEC 61138 equivalent” without formal certification.
Although the standard qualifies cables at −25 °C, practical field experience recommends warming cables stored below −15 °C before deployment — for example, by storing them in a heated vehicle or shelter for several hours before use. Forcing a frozen cable to bend can create invisible micro-cracks in the insulation that may not cause immediate failure but can grow under subsequent electrical and thermal stress. Some manufacturers offer Arctic-grade variants rated to −40 °C for particularly severe environments.
IEC 60245 (Harmonised rubber-insulated cables) covers general-purpose rubber cables for a wide range of applications. IEC 61138 is a specialised derivative that adds requirements specifically for live working earthing and short-circuiting: cold bending at −25 °C, colour coding per IEC 60445 (green/yellow for earthing), enhanced abrasion resistance, and explicit short-circuit thermal withstand verification. In practice, while an IEC 60245 cable may physically fit, it has not been tested or certified for the unique safety-critical demands of live working earthing applications.