IEC 60331-25: Fire-Resisting Cables — The “Lifeline” Maintaining Circuit Integrity During Fire

When Fire Breaks Out, Emergency Lighting and Fire Pump Cables Must Keep Working — For How Long?

IEC 60331-25:1999 specifies fire-resisting cables (cables maintaining circuit integrity under fire conditions). Unlike flame-retardant cables (IEC 60332, preventing flame propagation), fire-resisting cables must continue functioning during a fire — a mandatory requirement for fire pumps, emergency lighting, smoke extraction fans, and fire alarm system cables.

StandardCable TypeTest RequirementApplication
IEC 60332Flame-RetardantSingle wire, no flame propagationGeneral building wiring
IEC 60331Fire-Resisting750–950°C flame + mechanical shock, maintain circuit integrityFire safety equipment supply

The core technology: mica tape wrapped between the conductor and XLPE insulation. Mica (KAl₂(AlSi₃O₁₀)(OH)₂) has a melting point exceeding 1,200 °C and forms a ceramic-like insulating layer under fire conditions. The mica tape overlap ratio and thickness are the core manufacturing parameters determining fire survival time.

TNLab — Flame-retardant cables slow fire spread. Fire-resisting cables keep critical equipment running during a fire. They are not the same thing.