Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
ASTM D4314-12, issued under the fixed designation D4314, was last revised in 2012 and specifies crosslinked chlorosulfonated polyethylene (CSM) compounds—also widely known in the industry as CSPE—for use as outer coverings or jackets on electrical cables. The standard establishes three distinct service categories: General-Purpose, Heavy-Duty, and Extra-Heavy-Duty, each tailored to meet increasing demands for mechanical toughness and environmental protection.
The values stated in inch-pound units are regarded as the standard; values in parentheses are mathematical conversions to SI units provided for information only. The specification explicitly warns that these jacket materials are not recommended for cables installed at ambient temperatures lower than -25°C.
| 🟦 Jacket Classification | 📐 Service Level | 📏 Minimum Installation Temp | 🎯 Aging Condition (Air) | ⚡ Aging Condition (Oil) |
|---|---|---|---|---|
| General-Purpose | Standard electrical cable covering | -25 °C | 100 °C / 168 h | 121 °C / 18 h |
| Heavy-Duty | Enhanced mechanical and environmental resistance | -25 °C | 100 °C / 168 h | 121 °C / 18 h |
| Extra-Heavy-Duty | Maximum mechanical and chemical protection | -25 °C | 100 °C / 168 h | 121 °C / 18 h |
To conform to this specification, the jacket material must meet the physical property requirements prescribed in **Table 1** of the standard. These requirements cover minimum tensile strength, minimum elongation at break, and retention of these properties after specified aging cycles. All physical testing, sample preparation, and conditioning must be performed strictly in accordance with Test Methods D470 (Crosslinked Insulations and Jackets for Wire and Cable).
For applications requiring sunlight and weather resistance, the jacket must also satisfy the “Weatherability for Colored Materials” criteria found in Specification D1248. Specimens for these weatherability evaluations are prepared following the protocols in Test Methods D470.
| 📐 Property Measured | 🟦 Governing Standard / Test Method | 🎯 Requirement Source |
|---|---|---|
| Tensile Strength (min) | D470 | Per jacket type, Standard Table 1 |
| Elongation at Break (min) | D470 | Per jacket type, Standard Table 1 |
| Air Oven Aging (100 °C / 168 h) | D470 | % Retention per Table 1 |
| Oil Immersion Aging (121 °C / 18 h) | D470 | % Retention per Table 1 |
| Sunlight & Weather Resistance | D1248 (Weatherability) / D470 (Specimen Prep) | Requirements per Specification D1248 |
Sampling of the finished jacket material for qualification testing must strictly follow the procedures detailed in **Test Methods D470** to ensure the sample is representative of the production lot. For definitions of technical terms used in this standard—beyond the specific aging definition—users are directed to **Terminology D1711** (Relating to Electrical Insulation). Selecting the correct jacket classification (General-Purpose, Heavy-Duty, or Extra-Heavy-Duty) requires an assessment of the cable’s expected mechanical stress, temperature extremes, and chemical exposure over its service life.
CSM stands for Chlorosulfonated Polyethylene. The standard confirms that the abbreviation CSPE is also used extensively in the Wire and Cable industry to refer to the same material.
These crosslinked chlorosulfonated polyethylene compounds are specifically intended for use as outer coverings or jackets on electrical cables requiring general-purpose, heavy-duty, or extra-heavy-duty service protection.
The standard explicitly states that these jacket materials are not recommended for cables installed at a temperature lower than -25°C.
For the purposes of this standard, “aging” is specifically defined as the exposure of the material to circulating air at 100°C for 168 hours, or immersion in oil at 121°C for 18 hours.