Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
ASTM D4246-14 (Reapproved 2020) defines the requirements for an ozone-resistant thermoplastic elastomer (TPE) insulation compound. This standard is specifically formulated for electrical wires and cables of 14 AWG and larger, designed to withstand demanding environmental conditions.
The insulation is rated for continuous operation at a maximum conductor temperature of 90 °C in dry locations, with a maximum operating voltage of 2000 V. The compound must be capable of installation without cracking at temperatures as low as –40 °C. A key parameter defined within this standard is the “aging” procedure, which mandates exposure of the material to air at 121 °C for 168 h.
| 🟦 Parameter | 📏 Specification / Value | 📐 Notes |
|---|---|---|
| Conductor Size | 14 AWG and larger | Minimum size covered |
| Max Conductor Temp | 90 °C | Continuous, dry locations |
| Max Operating Voltage | 2000 V | Upper voltage limit |
| Min Installation Temp | –40 °C | Cold bend requirement |
Physical properties, including insulation thickness and tensile/elongation characteristics, are evaluated according to the methods referenced in the standard (D470 and D2633). The minimum average thickness of the insulation is specified in Table 1(a) of Test Methods D470, with the critical requirement that no measured value shall be less than 90 % of the specified average thickness.
The AC voltage test requires each insulated conductor to withstand a potential for 5 minutes at the voltage listed in the “Ozone-resisting Insulations” columns of Table 1(a) in D470. The insulation resistance must correspond to a minimum constant of 10 000 at 60 °F (15.6 °C), with temperature corrections applied using Table 2 of Test Methods D470.
| ⚡ Electrical Test | 🎯 Requirement | 📌 Reference Method |
|---|---|---|
| AC Voltage (if performed) | 5 min withstand at specified voltage | D470, Table 1(a) |
| Insulation Resistance | Min constant of 10,000 (corrected to 60 °F) | D470, Table 2 (Correction Factors) |
| DC Voltage | As specified (alternative to AC test) | D470, Table 1(a) |
| Insulation Thickness | Min 90% of specified average | D470, Table 1(a) |
🔍 What conductor sizes does ASTM D4246 cover?
The standard covers insulating compounds for electrical wire and cables that are 14 AWG and larger. It does not apply to smaller gauge magnet wire or other fine wiring.
⚡ What is the maximum operating voltage for this ozone-resistant insulation?
The insulation is suitable for circuits where the operating voltage does not exceed 2000 V. For higher voltage applications, a different insulation standard must be consulted.
📌 How is “aging” specifically defined in the context of this standard?
Unlike general thermal aging, ASTM D4246 strictly defines the aging act as exposure of the materials to air at 121 °C for 168 hours. This specific protocol ensures uniform testing across manufacturers for thermal endurance and ozone resistance.
💡 What is the minimum insulation thickness allowed by this specification?
While the specific average thickness depends on the conductor size (per Table 1(a) of D470), the standard explicitly requires that the minimum thickness at any point shall be at least 90 % of the specified average thickness.