D2526-02 – Standard Test Method Technical Guide

The ASTM D2526-02 standard defines the properties and test methods for ozone-resisting crosslinked silicone rubber insulation used in wire and cable. This material is engineered for high-temperature performance up to 125°C and voltage ratings up to 5000 V, ensuring reliability in demanding environments.

📐 Scope and Classification

This specification covers an ozone-resisting crosslinked silicone rubber insulating compound for electrical wires and cables. It is suitable for conductor sizes up to 1000 kcmil (507 mm²) at a maximum of 5000 V for both single-and-multiple-conductor cables. Minimum conductor sizes and insulation thicknesses are detailed in Table 1 of the standard.

Values presented in dual units prioritize the first set as standard, with informational equivalents in parentheses.

🟢 Tip: Tests on insulated wire or cable are intended to determine the property of the insulation material, not the conductor or cable completion.

⚙️ Test Requirements and Procedures

The insulation shall meet physical properties as per Table 2 and electrical requirements defined in the standard. Key tests include partial discharge, AC voltage withstand, insulation resistance, and DC voltage testing, performed in that order when specified.

🟦 Parameter 📏 Specification
Partial Discharge Extinction Level (100% Insulation) 4.0 kV
Partial Discharge Extinction Level (133% Insulation) 5.0 kV
AC Voltage Withstand Test Duration 5 minutes
Insulation Resistance Constant at 60°F ≥ 4000 MΩ·1000 ft
Accelerated Aging Temperature 200 ± 2°C
Accelerated Aging Duration 168 hours

For insulation resistance, temperature correction factors from Table 2 of Test Methods D 470 should be applied if test temperature deviates from 60°F.

📊 Compliance and Performance Data

The standard requires that each length of completed power cable rated for 2001 to 5000 V with insulation shielding must have a partial discharge extinction level as specified. The insulation must also withstand the AC voltage test for 5 minutes as per Table 1 values.

⚠️ Note: For cables with ungrounded neutral (133% insulation level), the partial discharge extinction level is higher at 5.0 kV.

Physical property compliance is confirmed through testing to Table 2 of D2526, ensuring the material’s robustness under operational conditions.

❓ Frequently Asked Questions

🔍 What is the maximum operating temperature for this insulation?

The insulation is suitable for continuous operation at conductor temperatures up through 125°C for power cable applications.

💡 What are the partial discharge extinction level requirements?

For cables rated at 2001 to 5000 V, the partial discharge extinction level is 4.0 kV for 100% insulation level and 5.0 kV for 133% insulation level.

⚡ How is insulation resistance tested and corrected?

Insulation resistance is tested per D 470, and the value is corrected to 60°F using correction factors from D 470, with a minimum requirement of 4000 MΩ·1000 ft.

📌 What is the defined aging condition for the insulation material?

The aging condition is exposure to air at 200 ± 2°C for 168 hours.

📥 Standard Documents Download

🔒
Please wait 10 seconds, the download links will appear after the ad loads

Leave a Reply

Your email address will not be published. Required fields are marked *