Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
ASTM D2220-21 covers a thermoplastic insulation made from poly(vinyl chloride) (PVC) or copolymers of vinyl chloride and vinyl acetate. It is recommended for use in power and control circuits where the conductor temperature does not exceed 75 °C. The specific application range depends directly on the insulation thickness as defined in the scope.
| 📏 Insulation Thickness | ⚡ Voltage Rating | 🌧️ Environmental Rating |
|---|---|---|
| 15 mils (0.38 mm) | < 300 V | Dry locations only |
| 30 mils | 600 V | Dry or wet locations |
The insulation must conform to the physical properties prescribed in Table 1, which include the response of the material to aging in air and oil at specified temperatures. Additionally, a vertical flame test conducted in accordance with ASTM D8354 is required. The electrical requirements follow a strict sequence and are detailed in Table 2.
| 🟦 Property | 📐 Requirement / Test Method | 🎯 Key Details |
|---|---|---|
| Aging (Air & Oil) | Specific temp/time (Table 1) | Measures the material’s response to thermal exposure |
| Flammability | Vertical Flame Test (D8354) | Mandated by the physical properties requirements |
| AC Withstand Voltage | Voltage per Table 2 | Omitted if the DC voltage test is performed |
| Insulation Resistance | Per Table 2 | Tested after the AC test, before the DC test |
| DC Withstand Voltage | Voltage per Table 2 | Performed last in the mandatory sequence |
The standard provides essential guidance for installations involving mechanical stresses. For cables subject to high mechanical demands, such as submarine cables or long vertical risers, the minimum conductor sizes specified in Table 2 may not be mechanically adequate and require separate evaluation.
A specific increase in insulation thickness is required for buried installations. For single-conductor cables installed in underground ducts or direct earth burial, the standard mandates adding 15 mils (0.38 mm) to the insulation thickness values specified in Table 2. The standard thicknesses listed in Table 2 primarily apply to aerial cables and conductors installed in above-ground conduits.
Insulation conforming to ASTM D2220-21 is specifically designed for continuous operation at conductor temperatures not higher than 75 °C.
For a 600 V voltage rating in a wet location, the standard strictly requires a minimum insulation thickness of 30 mils. The 15 mil thickness is restricted to dry locations and voltages below 300 V.
The mandatory test sequence is the AC voltage test, followed by the insulation resistance test, and finally the DC voltage test. The AC test is typically omitted if the DC test is performed.
Flammability is assessed using the vertical flame test, which must be conducted in accordance with ASTM Test Method D8354. This is part of the physical property requirements prescribed in Table 1 of the standard.