Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
ASTM D1679-02 specifies a crosslinked synthetic rubber insulating compound engineered for electrical wires and cables. This type of insulation is suitable for continuous operation at conductor temperatures not exceeding 75°C in both dry and wet locations, and for operating voltages not exceeding 2000 V.
The standard specifies that tests be performed on insulated wire or cable solely to determine the properties of the insulation material itself, rather than to evaluate the conductor or completed cable assembly. Whenever two sets of values are presented in different units, the first set is the standard.
D1679-02 sets clear benchmarks for insulation performance. The insulation must meet specific thickness requirements and demonstrate robust electrical properties under precise test conditions.
| 📏 Property | 🎯 Requirement | 📐 Standard Reference |
|---|---|---|
| Conductor Temperature (Max) | 75°C | Section 1.2 |
| Operating Voltage (Max) | 2000 V | Section 1.2 |
| Min. Insulation Thickness | 90% of avg (Table 1A, D470) | Section 4.2 |
| AC Withstand Test Voltage | Per Table 1A (D470) for 5 min | Section 5.2 |
| Insulation Resistance Constant | 4000 MΩ-1000 ft (305 m) @ 60°F (15.6°C) | Section 5.3.1 |
The standard defines specific high-pressure aging protocols to validate long-term material stability under oxidative conditions.
| 🟦 Aging Type | ⚡ Condition (Pressure / Temp) | ⏱️ Duration |
|---|---|---|
| Air Aging | 80 psi (0.55 MPa) / 127°C | 20 hours |
| Oxygen Aging | 300 psi (2.1 MPa) / 80°C | 168 hours |
Insulation resistance values are standardized to a temperature of 60°F (15.6°C). If measurements were taken at a different temperature, they must be corrected using the factors provided in Table 2 of Test Methods D 470, or by applying the specific 1°F coefficient available from the insulation manufacturer.
This insulation is designed for continuous operation at conductor temperatures not exceeding 75°C in both dry and wet locations.
The standard covers applications with operating voltages not exceeding 2000 V.
Aging is explicitly defined as exposure to either of the following conditions: air at 80 psi (0.55 MPa) and 127°C for 20 hours, or exposure to oxygen at 300 psi (2.1 MPa) and 80°C for 168 hours.
The required minimum thickness for the insulation is at least 90% of the average thickness specified in Table 1A of Test Methods D 470.