Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
CSA C49.8-09 (2018) — Aluminum Alloy 1350 Bare Stranded Conductors for Electrical Purposes — specifies the material, construction, mechanical, and electrical requirements for concentric-lay-stranded conductors made from round aluminum alloy 1350 wires. These conductors, commonly referred to as all-aluminum conductors (AAC), are primarily intended for use in overhead transmission and distribution lines, as well as for other bare electrical applications where corrosion resistance and high electrical conductivity are required.
The standard covers conductor sizes from 2.59 mm² (approximately 14 AWG) up to 1250 mm² (approximately 2500 kcmil), and defines four stranding classes (A, B, C, and D) which differ in the number of wires and associated flexibility. It encompasses requirements for temper designations (H19 and H26), concentric stranding geometry, permissible joint types, and acceptance criteria for production and delivery. The standard is fully aligned with the requirements of the Canadian Electrical Code (CE 0.5-13) and is widely referenced by Canadian utilities and regulatory authorities.
The conductor wires must be drawn from aluminum alloy 1350 (EC grade), which has a minimum aluminum content of 99.50% and is capable of meeting the specified resistivity, tensile strength, and elongation values. The two permissible tempers are:
The maximum DC resistivity at 20 °C is specified as 0.028264 Ω·mm²/m. This ensures a conductivity of at least 61.0% IACS (International Annealed Copper Standard). The standard requires the measurement of resistance on full-length conductors after completion of stranding.
Individual wires must meet the following minimum properties after stranding:
| Nominal Diameter (mm) | Minimum Tensile Strength (MPa) | Minimum Elongation (%) |
|---|---|---|
| Up to 3.00 | 155 | 1.0 |
| 3.01 – 5.00 | 150 | 1.5 |
| 5.01 – 6.00 | 145 | 2.0 |
The completed stranded conductor must also meet a rated breaking strength (RBS) calculated from the wire strengths and stranding factor, and must be capable of supporting at least 95% of the specified RBS.
Conductors shall be constructed with a central core wire surrounded by one or more concentric layers of helically laid wires. The number of wires depends on the class and size. For example:
| Conductor Class | Range of Wire Count | Typical Lay Ratio (Layer pitch / layer diameter) |
|---|---|---|
| Class A | 7 – 37 | 10 – 16 |
| Class B | 7 – 61 | 10 – 16 |
| Class C | 19 – 91 | 10 – 16 |
| Class D | 37 – 169 | 10 – 16 |
The direction of lay alternates between layers (right hand for the outermost layer is typical). Joints in individual wires are only permitted prior to stranding and must be of the cold‑welded or resistance‑welded type; no tension‑ or heat‑affected joints are allowed within the finished conductor.
Manufacturers implementing CSA C49.8-09 (2018) must establish a quality management system that covers incoming material inspection, in‑process control, and final product verification. Key testing requirements include:
For implementation, manufacturers must also label each reel with the standard number, conductor size, stranding class, length, and weight. A certificate of compliance shall accompany each shipment unless otherwise agreed.
To claim compliance with CSA C49.8-09 (2018), manufacturers should:
The standard was reaffirmed in 2018, meaning it remains current without technical changes. Any future amendments will be issued by the CSA Group’s Technical Committee on Overhead Conductors. Users should verify that the edition referenced in their contract or purchasing specification matches the year – many utilities still cite the 2009 version, but the 2018 reaffirmation does not alter the requirements.
Article prepared for reference purposes. For the complete authoritative text, refer to CSA C49.8‑09 (R2018) published by the CSA Group. Last updated: 2026.