Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
CSA C227.3-06 (R2017) is a National Standard of Canada that specifies the requirements for instrument transformers used for electrical measurement and protective relaying. These transformers include current transformers (CTs) and voltage transformers (VTs) that step down high currents and voltages to levels suitable for meters, relays, and other instrumentation. The standard applies to both indoor and outdoor types, with primary voltage ratings typically up to 72.5 kV, and covers transformers intended for 50 Hz and 60 Hz power systems.
The scope of CSA C227.3-06 (2017) encompasses:
The standard defines accuracy classes for metering and relaying applications. Metering classes (0.15, 0.3, 0.6, 1.2) specify limits for ratio and phase angle errors at rated current and voltage. Relaying classes (C100, C200, C400, C800) are defined based on the secondary terminal voltage at which the CT can maintain rated accuracy under specified burdens. The table below summarizes the metering accuracy limits.
| Accuracy Class | Application | Ratio Error at Rated Current (±%) | Phase Angle Error at Rated Current (±Minutes) |
|---|---|---|---|
| 0.15 | High-accuracy revenue metering | 0.15 | 5 |
| 0.3 | Standard revenue metering | 0.3 | 10 |
| 0.6 | General metering | 0.6 | 20 |
| 1.2 | Switchboard meters | 1.2 | 40 |
For relaying CTs, the class designation (e.g., C200) indicates the secondary voltage achievable at 20 times rated current without exceeding the specified error. Relaying accuracy is critical for proper protection system coordination.
Each instrument transformer is assigned a standard burden rating (e.g., B-0.1, B-0.2, B-0.5, B-0.9 for CTs; W and X for VTs). The connected burden (sum of meter, relay, and wiring impedances) must not exceed the rated burden to maintain the declared accuracy class. Exceeding the burden can cause saturation in CTs and increased phase errors in VTs.
CSA C227.3-06 (2017) requires transformers to withstand certain dielectric tests, including power-frequency withstand voltage and lightning impulse. The test levels depend on the maximum system voltage. Typical values:
Marking must include the manufacturer, type, ratio, class, rated burden, and CSA certification mark.
Choose the transformer based on system voltage, continuous current, and application (metering vs. relaying). For metering, select a class that aligns with the revenue accuracy requirements mandated by the local utility. For relaying, ensure the C class provides the necessary saturation voltage to drive the relay at fault levels. When dual-purpose transformers are needed, consult the manufacturer for composite accuracy ratings.
The standard recommends that secondary circuits be wired with stranded copper wire of sufficient gauge to minimize voltage drop. Test switches (shorting blocks) must be installed to safely isolate CT secondaries without open-circuiting them. For VTs, fused disconnects or test switches with fuses are required.
Secondary circuits of CTs must be grounded at one point to prevent hazardous voltages in case of insulation breakdown. VTs require primary and secondary fusing. All metallic enclosures must be bonded to the grounding system.
CSA C227.3-06 (2017) is referenced by many Canadian provincial electrical codes and by Measurement Canada for meters used in trade. Compliance involves:
Products that meet the standard carry the CSA mark, which is recognized across Canada. Using non-certified transformers can lead to rejection by utilities, voided warranties, and potential liability.
Note: This article is based on the standard reaffirmed in 2017 and is current as of 2026. Always refer to the latest edition of CSA C227.3 for the most up-to-date requirements.