Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
CSA C22.2 No. 338-19, titled Portable Power Distribution Units, establishes the safety and performance requirements for portable equipment intended to distribute electrical power in temporary installations. These units are commonly used in construction sites, outdoor events, film productions, emergency response setups, and any location where a reliable and safe temporary power distribution system is needed. The standard covers units rated up to 600 V ac maximum, with a rated current not exceeding 400 A per circuit, and includes provisions for both single-phase and polyphase systems.
The scope encompasses all enclosed assemblies that incorporate overcurrent protection, receptacles, cord connectors, and may include control devices, meters, and ground-fault circuit-interrupter (GFCI) protection. It specifically excludes permanently installed distribution equipment, portable generators, and power taps covered under other CSA standards. The standard is intended to be used in conjunction with the Canadian Electrical Code, Part I (CSA C22.1), and provides detailed construction, performance, and marking requirements to ensure safe operation in demanding environments.
All portable power distribution units must be housed in an enclosure that provides a minimum of Type 3R protection as defined by CSA C22.2 No. 94.1, or a higher rating if specified. Enclosures must be constructed from non-combustible or self-extinguishing materials and be resistant to corrosion. For units intended for outdoor use, the enclosure must be weatherproof and have provisions for drainage. All doors and covers must be lockable or require a tool to open, preventing unauthorized access.
Each branch circuit must be provided with overcurrent protection rated at not more than 50 A unless specifically permitted for higher-rated loads. The standard mandates GFCI protection for all 125 V, 15 A and 20 A receptacles intended for use by personnel. For other receptacles, ground-fault protection of equipment (GFPE) set at 30 mA or less is required. The GFCI or GFPE devices must be of the class or type specified by the manufacturer and comply with CSA C22.2 No. 144.1.
Clearances between live parts and the enclosure, as well as phase-to-phase and phase-to-ground spacings, shall conform to Table 1. These distances ensure that the unit can withstand the specified voltage levels and environmental conditions without flashover or tracking.
| Rated Voltage (V ac) | Minimum Clearance (mm) | Minimum Creepage Distance (mm) |
|---|---|---|
| 0 – 150 | 3.5 | 5.0 |
| 151 – 300 | 6.0 | 8.0 |
| 301 – 600 | 12.0 | 16.0 |
Table 1: Minimum clearance and creepage distances for live parts in portable power distribution units.
All receptacles and cord connectors must be listed for the purpose and comply with applicable CSA standards (e.g., CSA C22.2 No. 42 for receptacles). They must be configured to prevent interchangeability between different voltages and phase configurations, using a mechanical keying system or a reduced neutral blade. Each receptacle shall be marked with its nominal voltage and current rating on the face of the unit.
The unit shall include a main bonding jumper that connects the equipment grounding conductor to the neutral (if supplied) at the service disconnecting means. All non-current-carrying metal parts must be bonded to the equipment grounding terminal. A permanent warning label is required if the neutral is not bonded in the unit. Grounding electrode conductor (GEC) terminals must be provided where required by the Canadian Electrical Code.
Every unit must be permanently marked with the manufacturer’s name, catalogue number, electrical ratings, and a warning that the unit is intended for temporary use. The marking must also include the CSA certification mark. Installation and operating instructions must be supplied with each unit, detailing proper grounding, load balancing, and placement for weather protection.
Units undergo a series of type and routine tests during certification. These include dielectric voltage-withstand tests, insulation resistance tests, and short-circuit current tests. The standard also requires a mechanical impact test to simulate rough handling on construction sites. The unit must retain functionality and not expose live parts after a 5 N·m impact.
To address outdoor use, the standard requires that the unit withstand moisture, dust, and temperature extremes without degradation. The enclosure must provide effective sealing against water ingress, and internal components must be protected from condensation. Units are also tested for resistance to corrosion and UV exposure if intended for prolonged outdoor service.
Compliance with CSA C22.2 No. 338-19 is assessed through testing by a recognized certification body (e.g., CSA Group, Intertek, UL). Manufacturers must submit a representative sample for evaluation. Once certified, units are subject to periodic factory inspections to ensure ongoing conformity. The standard also references other CSA C22.2 standards for specific components, such as enclosures, switches, and grounding accessories.
Portable power distribution units are covered in Section 32 of the Canadian Electrical Code, Part I. Installers must ensure that the installation complies with all applicable CEC rules, including bonding and grounding requirements (Section 10), overcurrent protection (Section 14), and GFCI protection (Section 26). CSA C22.2 No. 338-19 fills in the product-specific safety details.
Although designed for temporary use, units must be inspected before each deployment. Check for signs of physical damage, moisture ingress, loose connections, and proper operation of GFCI devices. The standard recommends a detailed inspection every 12 months or after 500 hours of use, whichever comes first, including a recalibration of GFCI/GFPE devices.
CSA C22.2 No. 338-19 is part of the broader C22.2 series of standards published by the Canadian Standards Association. Always refer to the latest edition for compliance. This article is for informational purposes and should not replace the full standard text.
© 2026 Canadian Technical Publications. All rights reserved.