Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
CSA C22.2 No. 265-12 (2017) is a critical standard within the Canadian Electrical Code (CE Code) series, governing low-voltage AC power circuit breakers rated for use at voltages not exceeding 1000 V and frequencies of 50 or 60 Hz. This standard is essential for manufacturers, installers, and specifiers seeking to ensure safety, performance, and interoperability of circuit protection devices in commercial, industrial, and utility applications across Canada.
This standard applies to low-voltage AC power circuit breakers intended for installation in accordance with the Canadian Electrical Code, Part I. It covers circuit breakers with continuous current ratings typically up to 5000 A and interrupting capacities up to 200 kA rms symmetrical depending on the voltage rating. The standard includes:
Circuit breakers covered by this standard are designed to protect electrical circuits from overcurrent and short-circuit conditions and may incorporate integral trip units (thermal-magnetic or electronic) or be operated by remote control. The standard excludes high-voltage circuit breakers, DC circuit breakers, and devices used primarily for motor control or industrial control equipment.
Enclosures must be constructed of materials that provide adequate mechanical strength, corrosion resistance, and dielectric properties. Non-metallic enclosures must meet flammability ratings as defined in the standard. Clearances and creepage distances are specified to prevent arc tracking and ensure safe operation under polluted conditions. Internal wiring must be suitable for the temperature rise and voltage stress expected during normal and fault conditions.
Trip units must provide accurate overcurrent protection within defined time-current characteristics. For thermal-magnetic units, the thermal element is calibrated for ambient temperature compensation, typically at 40 °C. Electronic trip units must include provisions for field adjustment of long-time pickup, short-time pickup, instantaneous pickup, and ground-fault protection where required. The standard mandates clearance between the breaker’s continuous current rating and the trip unit settings to prevent nuisance tripping.
Interrupting ratings are verified through short-circuit testing at specific voltage, current, and power factor values. The standard defines required test sequences to demonstrate the breaker’s ability to close onto, carry for a specified duration, and interrupt fault currents up to its rated maximum. After the test, the breaker must remain mechanically functional and able to carry rated current without excessive temperature rise.
Mechanical endurance requires the breaker to survive a specific number of open/close operations without maintenance (e.g., 10,000 for molded-case types). Electrical endurance testing is conducted at rated current and voltage to verify contact life. Temperature rise limits are defined for terminals, accessible parts, and internal components at 100 % rated continuous current. Dielectric tests include impulse withstand (1.2/50 μs waveform) and power-frequency voltage withstand applied between live parts and ground, and across open contacts.
| Parameter | Requirement | Test Voltage | Typical Values |
|---|---|---|---|
| Dielectric Withstand (Power Frequency) | No flashover or breakdown | Up to 2.5 kV for 1 minute | 2.5 kV for 600 V class |
| Impulse Withstand | No disruptive discharge | 5 kV to 12 kV | 1.2/50 μs waveform |
| Temperature Rise at Terminals | ≤ 65 °C rise above ambient | Rated continuous current | Full-load test |
| Short-Circuit Interrupting | Clear fault within specified time | Rated voltage/rated short-circuit current | Power factor 0.15–0.50 |
Certification to CSA C22.2 No. 265-12 (2017) requires a series of type tests performed on representative samples. These include calibration and accuracy verification of trip units, temperature rise tests at rated current, dielectric withstand tests (impulse and power frequency), short-circuit interruption tests at multiple levels, and endurance tests (mechanical and electrical). Routine tests are mandatory on every manufactured unit to verify dielectric integrity and trip mechanism operation.
Short-circuit tests are conducted at a power factor determined by the voltage rating, typically between 0.15 and 0.50 for high-current faults. The breaker must demonstrate that it clears the fault, contains any arc, and remains capable of normal operation after the test (at reduced ratings if applicable). Ground-fault protection devices must be tested separately to ensure coordination and tripping in accordance with the standard’s selectivity requirements.
To achieve compliance, a manufacturer must submit a technical file including construction drawings, material specifications, trip unit design, and test plans. The certification body will conduct an initial factory inspection and sample testing. If all requirements are met, the manufacturer receives a certificate and may mark the product with the appropriate CSA mark (commonly the CSA-Mark or CSA-US depending on target market).
The 2017 edition introduced major changes including:
Electrical engineers and contractors should note that breakers certified to this standard may not automatically be accepted in installations using legacy equipment. Compatibility with existing switchgear, bus bar systems, and coordination with upstream overcurrent devices must be evaluated case by case.