CSA C22.2 No. 188-18: Standard for Splice and Tap Connectors for Use with Aluminum and Copper Conductors

Comprehensive overview of the scope, technical requirements, and compliance criteria for connectors in electrical installations

CSA C22.2 No. 188-18 is a key standard under the Canadian Electrical Code (CEC) that specifies safety and performance requirements for splice and tap connectors intended for use with aluminum, copper, or aluminum‑copper conductors. Published in 2018, it supersedes earlier editions and aligns with modern installation practices and materials. This article provides a detailed look at the scope, technical requirements, implementation considerations, and compliance notes for this standard.

Scope and Purpose

CSA C22.2 No. 188-18 applies to connectors used to join or terminate (splice or tap) conductors in electrical systems. The standard covers connectors rated up to 1000 V ac/dc and includes types such as mechanical connectors, compression connectors, and insulation-piercing connectors. It is specifically written for:

  • Solid or stranded aluminum conductors
  • Solid or stranded copper conductors
  • Aluminum‑to‑copper transitions

Connectors must be suitable for use in dry or wet locations, as indicated by the manufacturer. The standard does not cover welding or exothermic connectors, crimp-style terminations for pre-insulated terminals, or connectors intended solely for underground use (those are covered by other CSA standards).

Scope Note: Connectors listed under CSA C22.2 No. 188-18 are intended for permanent installations within buildings, industrial facilities, and similar settings. Always check the manufacturer’s markings for the specific conductor materials and temperature ratings allowed.

Technical Requirements

The standard prescribes rigorous test methods to ensure connectors maintain low resistance, mechanical integrity, and thermal stability over time. Key requirements include:

1. Materials and Construction

  • All metallic parts must resist corrosion and be compatible with the conductor material.
  • Insulating bodies (if any) must pass flame tests per CSA C22.2 No. 0.17.
  • Contact surfaces must be free of burrs, sharp edges, or contaminants.

2. Electrical Performance

Connectors must demonstrate:

  • Temperature Rise: Under rated current, the temperature rise of the connector shall not exceed that of a reference conductor by more than 20 °C (for aluminum) or 15 °C (for copper).
  • Dielectric Withstand: Withstand a test voltage of 1500 V ac (or 2250 V dc) between live parts and any accessible metal.
  • Resistance: After thermal cycling, the DC resistance of a connector-plus-conductor assembly must not exceed 150 % of the resistance of an equivalent length of conductor.
Thermal Cycling: Aluminum connectors are particularly sensitive to differential expansion. CSA C22.2 No. 188-18 requires up to 500 thermal cycles for connectors used with aluminum conductors to verify long-term stability.

3. Mechanical Strength

  • Pull-Out Test: Each connector must withstand the specified axial tensile load (e.g., 100 lbf for 14 AWG, up to 2000 lbf for 500 kcmil) without dislodging.
  • Torsion Test: For connectors that allow rotation of the conductor, a torque test ensures the connection does not loosen.

4. Marking and Instructions

Connectors must be permanently marked with:

  • Manufacturer’s name or trademark
  • Catalog number
  • Conductor size range (e.g., 14–2 AWG)
  • Material compatibility (AL, CU, AL/CU)
  • Maximum voltage and temperature rating
Table 1 – Typical Test Parameters for Splice/Tap Connectors (Excerpt from CSA C22.2 No. 188-18)
Test Requirements for Copper (CU) Requirements for Aluminum (AL)
Temperature rise limit (above ambient) ≤ 15 °C ≤ 20 °C
Thermal cycles (minimum) 250 500
Pull-out force (14 AWG) 100 lbf (445 N) 100 lbf (445 N)
Dielectric test voltage 1500 V ac 1500 V ac

Implementation Highlights

When designing or specifying connectors under this standard, engineers and installers should keep these points in mind:

  • Conductor Preparation: Clean aluminum conductors immediately before insertion to remove oxide film. Use an approved inhibitor compound if required by the connector instructions.
  • Torque Control: Mechanical connectors (set‑screw or clamp type) must be tightened to the torque specified by the manufacturer, as verified by a calibrated torque tool.
  • Compatibility with Insulation: Ensure that the connector’s temperature rating matches the conductor’s insulation rating (typically 90 °C for building wire).
  • Multi‑Conductor Connectors: Some splice blocks accept more than one conductor per port. Verify that each conductor is properly seated and the connector is rated for the fill.
Best Practice: Always use connectors that are listed (third‑party certified) to CSA C22.2 No. 188-18. The certification mark on the product provides assurance that the connector has passed all required tests, including thermal cycling for aluminum.

Compliance Notes

Meeting CSA C22.2 No. 188-18 is mandatory for connectors installed in electrical equipment covered by the Canadian Electrical Code. Key compliance aspects include:

  • Certification Bodies: CSA Group, UL, and other recognized agencies test connectors to this standard. Look for the CSA mark or other approved certification mark.
  • Field Assessment: When a connector is not certified, it may be subject to field evaluation by a provincial authority or inspection agency. This is rarely a viable alternative for production use.
  • Retrofit and Replacement: Connectors marked to older editions (e.g., No. 188-13) are generally acceptable unless the installation requires features only defined in the 2018 edition (e.g., clearance for higher fault currents).
  • Changes from Previous Edition: The 2018 edition introduced more stringent thermal cycling requirements for aluminum connectors and updated the dielectric test to include DC voltage values.
Non‑compliance Risk: Using a connector not certified to this standard can void the equipment’s warranty and may lead to overheating, fire, or electric shock. In Canada, non‑compliant connectors may result in an order to remove and replace at the installer’s cost.

Frequently Asked Questions

Q: Can I use a connector marked “CU/AL” on a copper conductor if the connector is listed to the new 2018 standard?
A: Yes, provided the connector is certified for both materials. However, the installer must follow the specific preparation instructions for aluminum when an aluminum conductor is used. For copper, no special inhibitor is typically required, but always confirm with the manufacturer’s instructions.
Q: What is the difference between a “splice” and a “tap” connector in the context of this standard?
A: A splice connector joins two or more conductors to form an electrical continuous path. A tap connector diverts a branch conductor from a main conductor (e.g., service drop). Both types are covered under CSA C22.2 No. 188-18, but tap connectors may have additional tests for mechanical loading on the main conductor.
Q: Does the standard apply to connectors used in data or telecommunications circuits?
A: No. The standard is limited to power and lighting circuits rated up to 1000 V. Connectors for low‑voltage control, signaling, or communication cables fall under other CSA standards (e.g., CSA C22.2 No. 225 for telecommunications cables).
Q: How do I verify that a connector is compliant with the 2018 edition?
A: Check the product’s certification marking. It usually includes the standard number (e.g., “CSA C22.2 No. 188-18”) or a reference to the current edition. The manufacturer’s technical data sheet should also list the standard for which the connector is certified.

Article published: 2026. This content is based on the requirements of CSA C22.2 No. 188-18 (2018 edition) and the Canadian Electrical Code, Part I. Always consult the official standard issued by CSA Group for the definitive text.

📥 Standard Documents Download

🔒
Please wait 10 seconds, the download links will appear after the ad loads

Leave a Reply

Your email address will not be published. Required fields are marked *