Scope and Applicability
CSA C22.2 No. 0.4-17, part of the Canadian Electrical Code (CE Code) Part II series, establishes the minimum requirements for the bonding and grounding of electrical equipment and exposed non-current-carrying metal parts that may become energized. The standard applies to equipment rated up to 750 V and is intended to ensure a safe path for fault current, limit touch voltages, and reduce the risk of electric shock and fire.
Key areas addressed include:
- General requirements for bonding conductors and connections
- Grounding electrode systems and connections
- Equipotential bonding in hazardous locations and around swimming pools
- Requirements for separately derived systems
- Provisions for maintenance and testing of grounding systems
Important: CSA C22.2 No. 0.4-17 is intended to be used in conjunction with the CE Code Part I (CSA C22.1) and other relevant Part II product standards. Compliance with this standard alone does not guarantee full code compliance unless all applicable requirements are met.
Technical Requirements
Bonding Conductors and Connections
The standard specifies minimum sizing rules for bonding conductors based on the rating of the overcurrent device protecting the circuit. Bonding jumpers must be installed at service equipment, at the source of separately derived systems, and around conduits and other metal raceways that could interrupt the grounding path. All bonding connections must be mechanically secure and electrically continuous, using listed connectors or exothermic welding.
Grounding Electrode System
CSA C22.2 No. 0.4-17 defines requirements for grounding electrodes, including:
- Metal water pipe grounding (must be supplemented by at least one additional electrode)
- Concrete-encased electrodes (Ufer grounds)
- Ground rings and driven rods
- Plate electrodes
Resistance of a single electrode must not exceed 25 ohms; if higher, a second electrode must be added. The standard also permits the use of structural steel and continuous metal underground water pipe as electrodes under specific conditions.
Table 1 — Minimum Sizes for Bonding Conductors (Based on Overcurrent Device Rating) | Overcurrent Device Rating (A) | Copper Conductor (AWG/kcmil) | Aluminum or Copper-clad Aluminum (AWG/kcmil) |
| 60 | 10 | 8 |
| 100 | 8 | 6 |
| 200 | 4 | 2 |
| 400 | 2 | 1/0 |
| 600 | 1/0 | 3/0 |
| 800 | 2/0 | 4/0 |
Equipotential Bonding
In areas susceptible to voltage gradients (e.g., swimming pools, spas, and livestock facilities), the standard requires bonding all metal parts together to create an equipotential plane. Conductors must be sized at minimum 6 AWG copper (or equivalent) and must be connected to the grounding system.
Separately Derived Systems
Generators, transformers, and other separately derived systems must have a bonding jumper installed at only one location—either at the source or at the first disconnecting means—to prevent parallel neutral paths. The standard clarifies the methods for grounding these systems and the rules for connecting the grounded conductor to the grounding electrode at the source.
Tip: When designing separately derived systems, always verify that the system bonding jumper is connected on the line side of the overcurrent protection for the derived system to comply with CSA C22.2 No. 0.4-17 requirements.
Implementation Highlights
Successful implementation of CSA C22.2 No. 0.4-17 requires careful coordination between design, installation, and inspection. Key considerations include:
- Continuity Testing — All bonding and grounding paths must be verified for low impedance using an ohmmeter or micro-ohmmeter before energization.
- Corrosion Protection — Connections buried in earth or exposed to corrosive environments must be protected by approved corrosion-resistant materials or coatings.
- Maintenance Provisions — Grounding electrodes and connections must be accessible for periodic inspection and testing. The standard recommends annual testing of ground resistance.
Best Practice: Document all bonding and grounding connections in as-built drawings. Include test results for ground resistance and continuity to simplify future maintenance and code compliance checks.
Compliance Notes
To demonstrate compliance with CSA C22.2 No. 0.4-17, manufacturers and installers should pay attention to the following:
- Listed Equipment — All grounding and bonding devices must be listed or certified to the appropriate CSA product standards.
- Labeling — Service equipment and separately derived systems must be permanently labeled with the type of grounding system and the location of the system bonding jumper.
- Derating for Multiple Grounding Electrodes — When multiple electrodes are used, the resistance of the grounding electrode system is the parallel combination; the standard requires that the overall resistance be less than 25 ohms.
- Hazardous Locations — Additional requirements from CSA C22.2 No. 0.4-17 and the CE Code Part I apply in Class I, II, and III hazardous locations. Bonding must be continuous and fault paths must have sufficiently low impedance to clear ground faults promptly.
Non-Compliance Risk: Inadequate bonding or grounding is a leading cause of electrical fires and lethal shock hazards. Authorities having jurisdiction (AHJs) may reject installations that do not meet the bonding conductor sizing requirements or that fail to provide a low-impedance path for fault current. Always refer to the latest edition of CSA C22.2 No. 0.4 and the CE Code for up-to-date requirements.
Q: Is CSA C22.2 No. 0.4-17 the same as the grounding requirements in the Canadian Electrical Code Part I?
A: No. CSA C22.2 No. 0.4-17 is a Part II standard that provides detailed design and construction requirements for bonding and grounding components. The CE Code Part I (CSA C22.1) gives the installation rules. Both documents must be used together for complete compliance.
Q: Can I use aluminum conductors for bonding under this standard?
A: Yes, but only if they are listed for the purpose and installed in a manner that prevents galvanic corrosion when in contact with dissimilar metals. The standard requires bonding conductors to be copper, aluminum, or copper-clad aluminum, sized per Table 1 (as shown above).
Q: Does this standard apply to existing installations?
A: Requirements in CSA C22.2 No. 0.4-17 are primarily for new equipment and installations. However, when existing systems are modified or extended, the new work must comply with the latest edition of the standard.