Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
CSA B626-09 (R2015) is a Canadian standard published by the Canadian Standards Association (CSA) that specifies minimum requirements for the design, fabrication, testing, and installation of aboveground shop-fabricated steel tanks intended for the storage of flammable and combustible liquids. This standard, reaffirmed in 2015, remains a key reference for engineers, fabricators, and regulatory authorities across Canada.
The standard applies to atmospheric, aboveground, vertical or horizontal steel tanks that are fabricated at a manufacturing facility and shipped to the installation site. It covers tanks with a capacity not exceeding 250,000 L (66,000 US gal) and designed for a maximum allowable working pressure (MAWP) of 17 kPa (2.5 psi) gauge. Tanks under this scope are typically used at commercial, industrial, and bulk storage facilities where flammable and combustible liquids (Classes I, II, and IIIA as defined in the National Fire Code of Canada) are stored.
Steel plates and shapes used in tank construction must meet the requirements of ASTM A36, ASTM A283, ASTM A516, or other CSA-approved carbon steel specifications. All materials must be suitable for the intended service temperature and compatible with the stored liquid.
The standard prescribes minimum shell plate thicknesses based on tank diameter, height, and specific gravity of the stored product. For vertical tanks, a minimum thickness of 4.76 mm (3/16 in.) is required for tank shells, while bottoms must be no less than 4.76 mm. Horizontal tanks (single-wall or double-wall) must have shell thicknesses calculated to withstand hydrostatic pressure plus a corrosion allowance of at least 1.6 mm.
All tank openings for fill, vent, gauge, and withdrawal pipes must be located above the maximum liquid level and sized appropriately. Nozzle necks must be made of steel with a minimum thickness of Schedule 40 pipe. Closures such as bolted manways must be provided for tank cleanout and inspection.
Exterior surfaces require a protective coating system suitable for the environment. For underground burial (if allowed by local codes), additional cathodic protection may be required. Double-wall tanks are permitted as a means of secondary containment, with an interstitial space that can be monitored for leaks.
Each tank fabricated under CSA B626-09 must pass a series of tests before leaving the shop. The key tests are summarized in the table below.
| Test Type | Pressure / Load | Duration | Acceptance Criteria |
|---|---|---|---|
| Hydrostatic (shell & bottom) | 1.5 × MAWP or water head to top of shell + 15 kPa, whichever is greater | ≥ 10 minutes | No leakage, no permanent deformation |
| Leak (air or inert gas) | 35 kPa (5 psi) gauge | Sufficient to verify holding pressure | No pressure drop (within tolerance) after stabilizing |
| Vacuum (if applicable) | 8.5 kPa (2.5 in. Hg) | 5 minutes | No buckling or collapse |
| Interstitial space (double-wall) | 35 kPa (5 psi) or as specified | As per manufacturer | No leakage from inner or outer shell |
CSA B626-09 (R2015) is referenced in the National Fire Code of Canada and many provincial fire regulations as the accepted standard for shop-fabricated aboveground tanks. To claim compliance, the manufacturer must hold a valid product certification from an accredited certification body (e.g., CSA Group). This typically involves:
Reaffirmed in 2015, the standard continues to provide a consistent basis for safety and performance. Users should verify if a newer edition (e.g., B626-14 or later) has been adopted in their jurisdiction, as some provinces may have transitioned to more recent versions.
© 2026 – Technical Article based on CSA B626-09 (R2015). This content is for informational purposes and should not replace the full standard text.