Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
CAN CSA E598-2-19-98, titled Luminaires — Part 2: Particular Requirements — Section 19: Air-Handling Luminaires, is the Canadian adoption of the international standard IEC 60598-2-19. This standard specifies safety and performance requirements for luminaires that are intended to be integrated into heating, ventilation, and air conditioning (HVAC) systems, where the fixture becomes part of the air distribution path.
The standard covers luminaires designed for use in air-handling environments, including supply air, return air, and combined supply/return systems. It applies to luminaires that operate at mains voltage up to 1,000 V and that are installed in accordance with the Canadian Electrical Code (CE Code).
This standard does not apply to emergency luminaires, portable luminaires, or luminaires installed in hazardous locations unless specifically referenced. All luminaires covered by this standard must be classified according to their air-handling capability: Type A (supply), Type B (return), Type C (supply and return), or Type D (no air-handling).
The technical requirements address electrical, mechanical, thermal, and fire safety aspects. Key parameters include:
Luminaires must withstand the maximum temperature that can occur under both normal operation and abnormal conditions (e.g., blocked air passages). The manufacturer must specify the allowable ambient temperature and the minimum airflow rate. Temperature rise tests are performed at rated airflow to ensure that all components stay within their temperature limits.
The enclosure must have sufficient mechanical strength to withstand normal handling and installation. Additionally, the luminaire must be able to support the weight of any air-moving accessories (grilles, dampers) that are attached to it.
Clearance and creepage distances must meet values specified in the standard, with additional margins if the luminaire is exposed to condensation from air-handling. Earthing continuity must be tested with specified current.
The luminaire construction must prevent the spread of fire. All internal wiring and components are enclosed in a fire-resistant case. Luminaires classified for use in supply or return air paths must also limit the spread of flame along the air path. The standard includes tests for ignitability and flame propagation.
| Classification | Air Path Role | Testing Conditions |
|---|---|---|
| Type A | Supply air only | Tested with airflow from plenum to room |
| Type B | Return air only | Tested with airflow from room to plenum |
| Type C | Combined supply & return | Tested in both directions at specified rates |
| Type D | No air-handling function | Tested with minimal or no airflow |
The standard requires that each luminaire be permanently marked with its type classification (A, B, C, or D) and the minimum airflow rate (L/s or CFM) required for safe operation. Installation instructions must clearly indicate the intended placement in the ductwork or plenum.
Manufacturers and designers must pay close attention to the interaction between the luminaire and the HVAC system. Key factors include:
The standard also requires that luminaires be designed for easy cleaning and that the materials used do not degrade under the influence of humid air. Surfaces exposed to the airstream must be smooth and free of sharp projections that could accumulate dirt or impede airflow. In addition, materials should be inherently corrosion-resistant or protected by an adequate finish.
In Canada, compliance with CAN CSA E598-2-19-98 is typically verified through third-party certification by an accredited testing laboratory, such as CSA Group or Intertek. The manufacturer must submit samples for testing according to the relevant clauses of the standard. After passing the tests, the product is licenced to bear the CSA mark or another approved certification mark.
Updates to the standard are harmonised with changes in IEC 60598-2-19. The year 1998 indicates the edition adopted; subsequent amendments (e.g., A1, A2) have been issued. It is the user’s responsibility to verify the current consolidated version.
| Test | Reference Clause | Acceptance Criteria |
|---|---|---|
| Temperature rise (normal) | Clause 12 | No component exceeds its rated max. temperature |
| Temperature rise (abnormal) | Clause 13 | No ignition; temperature limit for accessible parts ≤ 130 °C |
| Dielectric strength | Clause 10 | 1.5 kV for 1 minute; no flashover or breakdown |
_________________________________________________________________