Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
CAN CSA C50089-99 (2016) is the Canadian national adoption of the international standard IEC 60898-1 for low-voltage circuit-breakers used for overcurrent protection in household and similar installations. This standard, originally published in 1999 and reaffirmed in 2016, ensures alignment with modern electrical safety and performance requirements across Canada.
The standard applies to air-break circuit-breakers designed for operation by uninstructed persons, with rated voltages up to 415 V AC (50/60 Hz) and rated currents up to 125 A. These devices are intended for use in residential, commercial, and light industrial settings where protection against overloads and short circuits is required. The circuit-breakers covered are typically of the miniature circuit-breaker (MCB) type, either fixed or plug-in mounting, and are suitable for use in enclosures or distribution boards.
The standard also covers circuit-breakers that incorporate both overcurrent and residual current protection (RCBOs) when conforming to the relevant parts of the IEC 61009 series; however, the primary scope remains on overcurrent protection.
Important exclusions: Molded-case circuit-breakers (MCCBs) are covered by a separate standard (CSA C22.2 No. 5), and high-voltage equipment is outside the scope. The standard does not apply to circuit-breakers for DC circuits unless specifically designed and tested in accordance with additional requirements.
Circuit-breakers under this standard are classified according to their overcurrent trip characteristic (B, C, or D), rated current (In), rated short-circuit capacity (Icn), and rated voltage (Ue). Table 1 summarizes the standard preferred values.
| Parameter | Standard Values / Ranges |
|---|---|
| Rated voltage (Ue) | 230/400 V AC (single/three-phase), also 120/240 V AC for North American practice |
| Rated current (In) | 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A (preferred series) |
| Rated short-circuit capacity (Icn) | 1.5, 3, 6, 10, 15, 25 kA (depending on application) |
| Insulation voltage (Ui) | Minimum 500 V AC |
| Number of poles | 1, 2, 3, 4 (with or without protected neutral) |
The operating time–current curves define the zones within which the circuit-breaker must trip under overload and short-circuit conditions. The standard defines three common trip characteristics (B, C, D) and may include others for specific installations. Table 2 gives the instantaneous trip thresholds and typical application.
| Trip Characteristic | Instantaneous Trip Range (multiples of In) | Typical Application |
|---|---|---|
| B | 3 In to 5 In | Resistive loads, general lighting, socket outlets |
| C | 5 In to 10 In | Mixed inductive and resistive loads, small motors, fluorescent lighting panels |
| D | 10 In to 20 In | Highly inductive loads, transformers, welding equipment, motor starters |
In addition to the instantaneous trips, the standard specifies conventional overload trip times: for currents above the rated current but below the instantaneous threshold, the circuit-breaker must operate within certain time limits (e.g., >1 hour for In and <1 hour for 1.45 In under reference conditions) to protect the cable insulation.
Circuit-breakers must withstand a dielectric test at 2,000 V AC (or 2,500 V for rated voltage >300 V) between live parts and between live parts and exposed conductive parts. The minimum creepage and clearance distances are defined for the rated insulation voltage.
The rated short-circuit capacity (Icn) is verified by type tests. The circuit-breaker must interrupt the fault current and subsequently withstand the prescribed dielectric tests. For Icn values, the standard distinguishes between the ultimate short-circuit capacity (Icu) and service short-circuit capacity (Ics). The standard requires that after breaking the test fault, the device shall operate correctly at 80% of Icn for Ics.
Each circuit-breaker must be permanently marked with: manufacturer’s name or trademark, type designation, rated voltage and current, breaking capacity, trip characteristic symbol (B, C, D), and relevant standard reference (CAN CSA C50089-99). The marking must be legible and durable.
When designing or installing electrical systems using circuit-breakers conforming to CAN CSA C50089-99 (2016), several practical aspects should be considered:
To claim compliance with CAN CSA C50089-99 (2016), circuit-breakers must undergo type testing by an accredited laboratory. The tests include verification of: dielectric properties, temperature rise under rated conditions, short-circuit performance (both Icu and Ics), endurance (mechanical and electrical), and trip characteristic accuracy.
Certification by a recognized body such as CSA Group or Intertek provides confidence that the product meets the standard. In Canada, provincial electrical codes (e.g., Canadian Electrical Code, CSA C22.1) often require that circuit-breakers be listed or certified to this standard (or other applicable CSA standards) for use in permanent installations.
Manufacturers must maintain consistency of production through routine tests and quality management systems. The standard also references requirements for reliability and environmental performance, including resistance to heat, fire, and tracking.
As CAN CSA C50089-99 (2016) is a reaffirmed standard, users should stay informed about any amendments or new editions, such as the adoption of more recent IEC versions. Regular review of certified products and updated standards is recommended.
For further information, consult the official CSA Store for the full text of CAN CSA C50089-99 (R2016).
© 2026 Technical Standards Review. All rights reserved.