BS EN 62021 — Insulating Liquids Determination of Acidity Standard Series (Potentiometric, Colourimetric and Non-Aqueous Potentiometric Titration)

Insulating Liquids — Determination of Acidity: Potentiometric Titration, Colourimetric Titration and Non-Aqueous Potentiometric Titration

🛢️ BS EN 62021 is the British Standard (BSI) series adopting the IEC 62021 family for the determination of acidity in insulating liquids, providing standardised test methods for acidic content in electrical insulating liquids such as transformer oil. The series comprises 62021-1 (Automatic potentiometric titration), 62021-2 (Colourimetric titration) and 62021-3 (Non-aqueous potentiometric titration), developed under BSI Technical Committee GEL/10 (Fluids for electrotechnical applications). Acidity (acid value) is a key indicator of insulating-oil ageing and service life, directly relevant to the health assessment of oil-filled electrical equipment.

💡 Acid value is the “health indicator” of transformer oil: organic acids produced during oil oxidation corrode insulating paper, accelerate ageing and reduce insulation performance, so routine acidity measurement is a core element of oil supervision.

1. Series Structure and Scope 📌

StandardTitleCore Content
BS EN 62021-1Automatic potentiometric titrationDetermination of acidity of insulating liquids using an automatic potentiometric titrator, applicable to acid content in electrical insulating liquids.
BS EN 62021-2Colourimetric titrationDetermination of acidity by indicator colourimetric titration, applicable to lighter-coloured insulating liquids.
BS EN 62021-3Non-aqueous potentiometric titrationPotentiometric titration in non-aqueous media for acidity, applicable to mineral oils and synthetic esters.
⚠️ The methods differ in applicable sample range and measurement principle: choose the appropriate part based on sample type, colour and expected acidity; report the method used with the result.

2. Principle and Significance of Acidity Determination 🔧

The acidity of an insulating liquid is generally expressed as the milligrams of potassium hydroxide (KOH) needed to neutralise the acidic substances in 1 g of liquid (mg KOH/g). In-service transformer oil oxidises under the action of oxygen, temperature and moisture, producing various organic acids (naphthenic acids, fatty acids, aldehyde-ketone oxidation products, etc.), and the acid value rises progressively with ageing.

Significance of Acidity Determination

  • Ageing assessment: acid value is a direct measure of oil oxidative ageing, used to judge whether oil needs replacement or reclamation.
  • Insulation protection: acidic substances accelerate the degradation of insulating paper, shortening equipment life.
  • Equipment condition monitoring: routine acidity monitoring is a key basis for preventive maintenance and condition-based maintenance of transformers.
✅ Combined with dissipation factor, moisture, breakdown voltage and other indicators, acidity enables comprehensive evaluation of insulating-oil operating condition and remaining life — an important part of the oil-supervision standard system.

3. Test Method Essentials 🔬

62021-1 Automatic Potentiometric Titration

Uses an automatic potentiometric titrator, titrating the sample with potassium hydroxide (or potassium ethoxide) standard solution and determining the endpoint from the potential-volume curve, automatically computing the acid value. Suited to darker samples where the endpoint is hard to judge visually.

62021-2 Colourimetric Titration

Uses an indicator such as phenolphthalein for colourimetric titration, judging the endpoint by indicator colour change. Simple and low-cost in equipment, suited to lighter-coloured insulating liquids, but endpoint judgement is difficult for dark samples.

62021-3 Non-Aqueous Potentiometric Titration

Performs potentiometric titration in non-aqueous media (e.g., toluene/ethanol mixed solvent or pyridine system) for mineral oils and synthetic esters, overcoming the limitations of aqueous titration and improving applicability and endpoint determination accuracy.

🚨 The titrants and solvents used are flammable chemicals; operate in a fume hood away from ignition sources and follow laboratory safety procedures.

4. Operation and Quality Control 🛠️

  • 🔍 Sampling: sample per the standard, avoiding contamination and moisture absorption; mix samples thoroughly.
  • 🔧 Reagent standardisation: standardise the titrant with a primary standard to ensure accurate concentration.
  • 📊 Blank test: perform and subtract a blank to avoid the effect of background acidity from solvent and reagents.
  • 📋 Parallel determination: run parallel determinations per requirements and check repeatability against the allowed deviation.

5. Frequently Asked Questions ❓

❓ Q: Why determine the acidity of insulating liquids?
A: Acidity reflects oxidative ageing; acidic substances corrode metal parts, accelerate insulating-paper ageing and reduce insulation performance — a key indicator for transformer-oil supervision.
❓ Q: How do the three parts differ?
A: 62021-1 uses automatic potentiometric titration for dark samples; 62021-2 uses indicator colourimetric titration for light samples; 62021-3 uses non-aqueous potentiometric titration for better applicability to mineral oils and synthetic esters.
❓ Q: How is the acidity result expressed?
A: Generally as milligrams of KOH per gram of sample (mg KOH/g); a higher value indicates more severe oil ageing.
🔍 Q: What does acidity measurement mean for equipment maintenance?
A: Routine acid-value monitoring detects oil ageing early, guiding oil replacement, reclamation or filtration decisions and preventing insulation degradation — an important part of preventive maintenance.
❓ Q: What safety precautions apply?
A: Titrants and solvents are flammable; operate in a fume hood away from ignition sources, and use protective gloves and goggles to avoid skin contact.
🔒