BS EN 61869 — Instrument Transformers Series (Current, Voltage, Combined, Capacitor and Low-Power Transformers)

Instrument transformers (general / current transformers / voltage transformers / combined / capacitor / low-power)

⚡ BS EN 61869 is the British Standards series implementing European Norm EN 61869 (identical to IEC 61869) for instrument transformers. Prepared by UK Technical Committee PEL/38 (Instrument transformers), it supersedes the earlier EN 60044 series. Instrument transformers transform high voltage and large current into secondary quantities acceptable to measuring and protective devices, and are the fundamental equipment for metering, measurement, protection and monitoring in power systems. The series defines the general and additional requirements for each type and is the core reference for the design, manufacture, testing and selection of instrument transformers.

💡 An instrument transformer scales the primary voltage/current to the secondary by accuracy class. Current transformers (CT) usually have a 5 A (or 1 A) secondary rating, while voltage transformers (VT) are typically 100 V or 100/√3 V. Their accuracy (e.g. 0.2, 0.5, 5P, 10P) and secondary burden directly affect metering and protection performance.
⚠️ Scan-version note: Part 4, Part 5 and Part 6 of this six-part series were available only as scanned documents (SCAN) in the source material. Their technical content in this article is summarized from public domain knowledge; the official BSI publication takes precedence.

1. Series Overview and Scope 📌

The series applies to current transformers, voltage transformers, combined transformers, capacitor voltage transformers and low-power instrument transformers for measurement and protection. Part 1 gives general requirements (definitions, accuracy classes, ratings, insulation, tests and marking); the parts give additional requirements by transformer type.

Instrument transformers must satisfy both measurement accuracy (metering) and protection characteristics (e.g. composite error and transient behavior of CTs; voltage and phase-angle errors of VTs). Their accuracy class, secondary burden, insulation level and temperature rise are the key selection parameters, and the standard gives unified definitions and test methods.

2. Structure of the Series 📋

StandardTitleContent SummaryStatus
BS EN 61869-1:2009General requirementsGeneral requirements: definitions, accuracy, ratings, insulation and testsPublished 2009; from IEC 61869-1:2007 (with European modifications)
BS EN 61869-2:2012Additional requirements for current transformersAdditional requirements for CTs (composite error, protection classes, transient)Published 2012; supersedes EN 60044-1/-6
BS EN 61869-3:2011Additional requirements for inductive voltage transformersAdditional requirements for inductive VTsPublished 2011; supersedes EN 60044-2
BS EN 61869-4:2014Additional requirements for combined transformersAdditional requirements for combined (current+voltage) transformersScan version
BS EN 61869-5:2011 (2015)Additional requirements for capacitor voltage transformersAdditional requirements for capacitor voltage transformers (CVT)Scan version
BS EN 61869-6:2016Additional general requirements for low-power instrument transformersAdditional requirements for low-power instrument transformers (LPIT, electronic/sensing)Scan version

3. Key Technical Requirements 🔧

3.1 General requirements (Part 1)

Part 1 specifies rated primary/secondary values, accuracy classes, secondary burden, insulation level, temperature rise, mechanical strength and test requirements, and defines the nameplate and marking. The general requirements apply to all types and are the reference basis for the parts.

3.2 Current transformers (Part 2)

Part 2 specifies accuracy for measuring classes (e.g. 0.2/0.5) and protection classes (e.g. 5P, 10P, TP types), the composite-error limits and transient characteristics (time constant, remanence factor, etc.), ensuring correct protection operation under short-circuit and transient conditions.

3.3 Voltage, combined and capacitor types (Parts 3, 4, 5)

Part 3 specifies the voltage error and phase displacement, rated voltage factor and ferroresonance behavior of inductive VTs; Part 4 covers combined current+voltage transformers; Part 5 covers capacitor voltage transformers (CVT), whose accuracy is affected by the capacitor divider and intermediate transformer, requiring special transient-response verification.

3.4 Low-power instrument transformers (Part 6)

Part 6 addresses low-power instrument transformers (LPIT), including Rogowski coils, electronic sensing and transformers with digital interfaces, specifying output, accuracy, insulation and EMC requirements to meet the needs of smart substations and digital metering.

🚨 The secondary circuit of a current transformer must never be opened: once open, the whole primary current flows as magnetizing current, inducing dangerously high voltage at the secondary terminals that endangers people and equipment. The secondary circuit must be reliably earthed and protected from accidental disconnection; the transient behavior of protection-class CTs must be coordinated with the protection relays.

4. Engineering Practice and Applications 🔩

  • 🔍 Design and selection: Choose transformers by metering accuracy (0.2/0.5) and protection characteristics (5P/TP), and verify the secondary burden and ratings.
  • 🔧 Installation and wiring: Never open a CT secondary, never short a VT secondary; get polarity, ratio and earthing right, and make the secondary conductor cross-section and length satisfy the burden.
  • 📊 Calibration and testing: Before commissioning, test ratio, polarity, excitation characteristic and insulation; periodically verify metering transformers to maintain the accuracy class.
  • 📋 Operation and maintenance: Regularly check secondary wiring, earthing and insulation, and monitor noise, heating and oil level (oil-filled) to prevent misoperation from dampness or looseness.

5. Frequently Asked Questions ❓

❓ Q: Why must the CT secondary never be open?
A: In normal operation the secondary and primary ampere-turns nearly balance and the core flux density is low; once the secondary opens, the whole primary current becomes magnetizing current, the core saturates sharply, and the secondary induces a very high voltage (thousands of volts), endangering people and equipment and possibly damaging insulation.
❓ Q: What is the difference between measuring and protection classes?
A: Measuring classes (0.2, 0.5) guarantee accuracy near rated current for metering and measurement; protection classes (5P, 10P, TP) guarantee operation within the composite-error limit under short-circuit current for relay protection.
❓ Q: What is the difference between a capacitor voltage transformer (CVT) and an inductive one?
A: A CVT uses a high-voltage capacitor divider to reduce voltage before an intermediate transformer; insulation cost is low and it suits EHV, but accuracy is affected by the divider ratio and transient response. Inductive (electromagnetic) VTs are simple and stable and are mostly used at medium voltage.
🔍 Q: Why is the content of Parts 4, 5 and 6 flagged as scan versions?
A: These three documents were available only as scanned copies in the source material, so this article summarizes them from public domain knowledge. Specific accuracy limits, test parameters and acceptance values should be taken from the official text published by BSI.
🔒