Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
🔌 The BS EN 61850 series is the UK implementation by BSI of IEC 61850, defining the architecture, data models, services and engineering configuration of communication networks and systems for power utility automation, including substation automation. It is the international core standard family for the information model of smart substations and the smart grid. The series was prepared under the responsibility of UK Technical Committee PEL/57 (Power Systems Management and Associated Information Exchange), classified under ICS 33.200. Each part is identical to the corresponding IEC 61850 document. The series comprises 13 parts covering general requirements, system and project management, functional communication, SCL configuration description, ACSI abstract communication services, common data models, object models, real-time Ethernet mapping, sampled-value transmission and conformance testing.
Conventional substation secondary systems rely on a large number of panels and point-to-point copper cabling, with poor interoperability. IEC 61850 reshaped the integration of power automation systems through “unified data models + standard services + file-based engineering configuration”, enabling interoperability between IEDs (Intelligent Electronic Devices) from different vendors and significantly reducing design, commissioning and operation workloads. BS EN 61850 formally introduces this international standard into the UK.
The standard is divided into groups: -3 general requirements (environment, EMC, quality), -4 system and project management, -5 functional communication requirements, -6 SCL configuration language, -7 data modelling (-7-1 basic architecture, -7-2 ACSI, -7-3 common data classes, -7-4 logical nodes, -7-410 hydro, -7-420 distributed energy resources), and -8-1 and -9-2 communication mappings and -10 conformance testing. This batch includes -3, -4, -5, -6, -7-1/-7-2/-7-3/-7-4/-7-410/-7-420, -8-1, -9-2 and -10 (13 documents in total).
| Part | Subject | Core Content |
|---|---|---|
| BS EN 61850-3 | General requirements | Equipment environment, EMC, supply and quality |
| BS EN 61850-4 | System and project management | Engineering process, documentation, quality |
| BS EN 61850-5 | Functional communication requirements | Functional and communication performance |
| BS EN 61850-6 | SCL configuration description | Engineering configuration format (SCL/XML) |
| BS EN 61850-7-1 | Basic architecture and model principles | Information model and service architecture |
| BS EN 61850-7-2 | ACSI abstract communication services | Abstract services (read/write/report/control) |
| BS EN 61850-7-3 | Common data classes | Common Data Class (CDC) definitions |
| BS EN 61850-7-4 | Compatible logical nodes & data objects | Logical Nodes (LN) and Data Objects (DO) |
| BS EN 61850-7-410 | Hydroelectric applications | Hydro-specific logical nodes (+A1:2016) |
| BS EN 61850-7-420 | Distributed energy resource (DER) applications | PV, storage and other DER logical nodes |
| BS EN 61850-8-1 | MMS / Ethernet mapping | Mapping of ACSI to MMS (incl. GOOSE) |
| BS EN 61850-9-2 | Sampled values (SV) transmission | Process-bus sampled-value real-time transport |
| BS EN 61850-10 | Conformance testing | Device conformance test procedures |
The original scope is confirmed as “general requirements”. It specifies requirements for equipment used in power-automation environments regarding temperature, humidity, vibration, EMC and power quality. The 2014 edition supersedes the 2002 edition and provides the basic guarantee for reliable operation of equipment in the harsh electromagnetic environment of substations.
The original scope is confirmed as “system and project management”. The 2011 edition was revised to extend its scope from substation automation systems to all power utility automation systems, and specifies engineering design, configuration management, version control, acceptance testing and documentation — central to delivery quality.
The original scope is confirmed as “conformance testing”. The 2013 edition (Ed.2) added conformance test clauses for server devices relative to the 2005 edition, and specifies verification and declaration (PICS/MICS) that a device’s claimed capabilities match its actual implementation — a prerequisite for multi-vendor interoperability.