⚙️ BS EN 61804 is the British adoption of the IEC 61804 series for function blocks (FB) for process control and the Electronic Device Description Language (EDDL), entrusted to Technical Committee AMT/7 (Industrial communications: process measurement and control, including fieldbus). This batch covers four documents: BS EN 61804-2:2007 (specification of FB concept, identical to IEC 61804-2:2006, partially superseding the 2004 edition), BS EN 61804-3:2015 (EDDL syntax and semantics, identical to IEC 61804-3:2015, replacing the 2011 edition), BS EN 61804-4:2016 (EDD interpretation, identical to IEC 61804-4:2016, first edition), and BS EN 61804-5:2015 (scan version). Together with IEC 61499 (function block architecture), the series supports the standardization of distributed process control systems and is foundational for intelligent instrument and control system integration, device description and engineering-tool interoperability.
💡 EDDL (Electronic Device Description Language) is a language that “describes rather than programs” a device: it describes the parameters, menus, diagnostics and engineering information of intelligent instruments in a unified text format, so that devices from different vendors appear consistently in a unified engineering tool — the key to solving “device description fragmentation”.
1. Series Overview and Structure 📌
The BS EN 61804 series is organized around function blocks and EDDL:
- BS EN 61804-2:2007 (FB concept): specifies the conceptual model, data types, algorithms and connections of function blocks for process control — the foundational specification of the FB architecture.
- BS EN 61804-3:2015 (EDDL syntax and semantics): specifies the syntax, semantics and lexical rules of the EDDL language — the normative language definition for writing electronic device descriptions (EDDs).
- BS EN 61804-4:2016 (EDD interpretation): specifies the interpretation and execution mechanism of EDDs, enabling EDDL descriptions to be interpreted and executed by engineering tools.
- BS EN 61804-5:2015: further content on EDDL (scan version).
⚠️ Some documents (e.g. BS EN 61804-5:2015) are scanned copies with limited extractable text; the corresponding content here is based on public domain knowledge. For specific clauses, refer to the official BSI published versions.
2. Function Block Concept (Part 2) 🔧
BS EN 61804-2 specifies the conceptual model of function blocks for process control. A function block is an abstraction encapsulating an algorithm, parameters and interfaces into a reusable control component. Technical points include:
- FB model: a function block contains input/output (I/O) parameters, internal parameters, an algorithm and execution control;
- Data types and connections: definitions of basic data types, structured types and rules for connecting function blocks;
- Algorithm and scheduling: execution period, trigger mode and scheduling mechanisms of FB algorithms;
- Link with IEC 61499: the FB concept aligns with IEC 61499 (function blocks for industrial-process measurement and control), supporting distributed control.
✅ Function blocks encapsulate control logic as reusable, parameterizable “software components”, enabling control engineers to build control schemes through graphical configuration without writing low-level code, significantly improving engineering efficiency and maintainability.
3. EDDL Syntax and Semantics (Part 3) 💡
BS EN 61804-3:2015 is the normative language definition of EDDL, specifying:
- Lexical and syntactic rules: keywords, identifiers, statement structures and expression rules of EDDL source files;
- Data types: definitions of variables, arrays, records, enumerations, strings and other types;
- Device description elements: how to describe device variables, methods, menus, dialog boxes, help texts, units, alarms and diagnostic information;
- 2015 update: aligned with related standards, refining semantic and syntactic definitions to support richer device description capability.
💡 For instrument vendors, EDDL replaces vendor-specific configuration software with a unified “device description”; for users and engineering integrators, EDDL lets instruments from different vendors appear consistently in a unified engineering tool (e.g. DCS, asset-management tools) without installing proprietary plug-ins.
4. EDD Interpretation (Part 4) 🔍
BS EN 61804-4:2016 specifies the interpretation and execution mechanism of EDDs — the key step for EDDL deployment:
- Interpreted execution: specifies how the interpreter reads and executes EDDL source files to generate device interfaces and interaction logic;
- Runtime model: defines access, update and error-handling behaviour of EDDs at runtime;
- Host system integration: specifies how EDDs are loaded and used by host systems such as engineering tools and asset-management software;
- Consistency: ensures the same EDD presents consistently and behaves predictably across different host systems.
🚨 EDDL is often contrasted with FDT (Field Device Tool)/DTM: EDDL focuses on “describing device data and interface”, while FDT/DTM focuses on “encapsulating device drivers as plug-ins”. When integrating, choose the appropriate device-integration technology based on device type and engineering-tool support.
5. Engineering Application 🛠️
The BS EN 61804 series is widely applied in process industry automation:
- Intelligent instrument integration: device description and unified engineering presentation of pressure, temperature, flow and level transmitters;
- Control system configuration: building control loops (PID, split-range, sequential) with function blocks for graphical configuration;
- Asset management and predictive maintenance: using EDDL device diagnostics for condition monitoring, alarm management and maintenance decisions;
- Engineering-tool interoperability: different DCS/PLC and asset-management platforms sharing the same EDDL device description, reducing engineering integration cost.
⚠️ Pay attention to version compatibility when using EDDL: different versions (e.g. 61804-3 2011/2015) and host tools may support EDDL features differently; the EDD should declare the EDDL version it follows and be verified in the target tool before commissioning.
6. Frequently Asked Questions ❓
❓ Q: What is the relationship between function blocks and EDDL?
A: Function blocks (FB) are used to build control logic and algorithm components; EDDL is used to describe device parameters, interfaces and diagnostics. Both are parts of process-automation standardization, acting at the control-logic and device-integration levels respectively.
❓ Q: What is the difference between EDDL and FDT/DTM?
A: EDDL is a “device description language” describing devices in a unified text format with strong cross-tool reusability and no plug-in required; FDT/DTM is a “device type manager” (plug-in driver) encapsulating device drivers as installable components. They suit different scenarios and are often complementary.
❓ Q: Why unify device descriptions (EDD)?
A: If each vendor has a proprietary configuration tool, engineering integration requires installing many proprietary programs at high maintenance cost. A unified EDD lets devices appear consistently in standardized engineering tools, achieving “plug-and-play” and reducing integration and maintenance cost.
🔍 Q: What advantage does function-block configuration have over traditional ladder/text programming?
A: Function blocks express control algorithms and connections graphically, making them easy to understand, reuse and maintain, suitable for process control loops (PID, cascade, split-range); traditional programming languages suit logic and sequential control, and the two are often combined.
🔧 Q: Why is EDD version compatibility important?
A: Host tools’ support for EDDL features evolves with versions; if an EDD declares features the tool does not support, device interfaces may miss functions or display incorrectly. Ensure the EDD and engineering-tool versions match and are fully verified.