BS EN 61755 — Fibre Optic Connector Optical Interfaces Standard Series

Fibre Optic Interconnecting Devices and Passive Components — Connector Optical Interfaces

🔌 BS EN 61755 is the British Standard implementing the EN 61755 series, corresponding to IEC 61755, on fibre optic interconnecting devices and passive components, focusing on the connector optical interface. The series specifies the geometric and connection parameters of the fibre end face in connectors — including physical contact (PC), angled physical contact (APC) and reference-connection applications — so that connectors made by different manufacturers are interchangeable and mate reliably. It is developed under IEC/TC 86 (Fibre optics) and its subcommittee SC 86B (Fibre optic interconnecting devices and passive components), with the UK handled by GEL/86/2. The eight documents in this batch span editions from 2006 to 2017.

💡 The insertion loss and return loss of a fibre joint depend heavily on the end-face shape, radius of curvature and polish angle. 61755 turns “is the connector good” into measurable connection parameters — the geometric and optical basis of interoperability in high-density, high-speed optical networks.

1. Series Overview 📌

BS EN 61755 is divided into parts by interface type. Part 2 deals with connection parameters of single-mode physically contacting fibres (including reference connector applications), distinguishing non-angled (PC) and angled (APC) types; Part 3 covers a broader set of connector interface parameters, including specific ferrule or fibre types. The batch contains both mature PC/APC interface specifications and newer reference connector definitions.

⚠️ Several documents in this series are scanned versions whose full text could not be optically recovered; the related content has been prepared from public-domain knowledge. The authoritative source is the officially published BSI version.

2. Structure and Technical Contents 🧱

StandardYearCore subjectInterface type
BS EN 61755-2-42015Connection parameters of non-dispersion shifted single-mode PC fibres — non-angled, for reference connectionPC flat-end reference
BS EN 61755-2-52015Connection parameters of non-dispersion shifted single-mode PC fibres — angled, for reference connectionAPC angled-end reference
BS EN 61755-3-102017Connector interface parameters — non-angled (new interface form)General PC interface (newer)
BS EN 61755-3-312015Connector interface parameters — specific end-face geometryPC/APC refinement
BS EN 61755-3-322016Connector interface parameters — extended interface requirementsHigh-performance parameters
BS EN 61755-3-62006+A1:2012Connector interface parameters — non-angled physical contactMature PC interface
BS EN 61755-3-72009Connector interface parameters — angled physical contactAPC interface
BS EN 61755-3-82009Connector interface parameters — supplementary angled requirementsAPC supplement

3. Key Technical Requirements 🔧

3.1 Physical contact (PC/APC) end face

The standard centres on three core end-face quantities: radius of curvature, apex offset and fibre height (undercut or protrusion). A PC end face uses a slightly spherical polish so the cores contact tightly; an APC end face adds about an 8-degree angle to suppress return reflection. These geometric parameters directly determine insertion loss and return loss and are the core acceptance criteria for connector quality.

3.2 Reference connector applications (Parts 2-4 / 2-5)

Reference connectors are used for test systems and standards comparison. This part requires stricter end-face quality than ordinary connectors to guarantee repeatability and traceability of measurements; non-angled reference connectors suit general testing, while angled reference connectors are used where low return loss must be measured.

3.3 Consistency of connection parameters

The standard stresses that an “optical interface” must be defined jointly by geometric parameters and optical performance. Different parts give parameters for different ferrules (2.5 mm, 1.25 mm or ferrule-less designs) and fibre types; engineering selection must ensure the mating pair belongs to the same interface category and avoid mixing PC and APC.

🚨 PC and APC connectors must never be mated together: because their end-face angles differ, mating them produces very high insertion loss on one hand and can severely compress or scratch the end faces on the other, permanently damaging the connectors. The interface category must be unified across the whole fibre system.

4. Engineering Practice 🛠️

  • 📡 Data centres and telecom rooms: high-density patch cords are accepted against 61755 parameters to ensure insertion and return loss targets.
  • 🔬 Reference connection and testing: use the reference connectors defined in Parts 2-4/2-5 to establish a power-meter and OTDR test baseline.
  • 🏭 Production quality control: connector makers measure radius of curvature and apex offset in real time and feed back to the polishing process.
  • 🌐 High-speed coherent optics: coherent modules sensitive to return loss adopt APC interfaces validated per Parts 3-7/3-8.

5. Frequently Asked Questions ❓

❓ Q: What is the difference between PC and APC?
A: PC (physical contact) end faces are slightly spherical planes for general connections; APC (angled physical contact) adds about an 8-degree angle to the spherical face, greatly reducing return reflection, suited to high-speed, coherent and analogue-video applications sensitive to reflection.
❓ Q: Why are “reference connectors” needed?
A: Testing needs a baseline jumper of excellent, stable end-face quality as the “reference answer”; the reference connector definition guarantees the build consistency of such baselines so that results from different labs are comparable.
❓ Q: What is the effect of radius of curvature and apex offset?
A: Too small a radius or too large an apex offset makes the cores contact poorly, raising insertion loss and amplifying angular sensitivity; APC usually demands tighter tolerances on end-face geometry than PC.
❓ Q: How does this series differ from 61753 (performance standard)?
A: 61753 specifies the performance grades and tests of passive components (including connectors) under various environmental conditions; 61755 focuses on the geometric and optical parameter definition of the connector mating end face itself. They answer “how is the end face” versus “how is the component”.
❓ Q: How should the scanned parts be cited?
A: The scanned parts are summarised from public-domain knowledge and are suitable for understanding the technical framework; when quoting specific tolerances and return-loss limits for design and acceptance, use the controlled BSI text.
🔒