BS EN 61439 — Low-Voltage Switchgear and Controlgear Assemblies Series (General Rules, Power Assemblies, Distribution Boards and Busbar Trunking)

Low-voltage switchgear and controlgear assemblies (general rules / power assemblies / distribution boards / public networks / busbar trunking)

⚙️ BS EN 61439 is the British Standards series implementing European Norm EN 61439 (identical to IEC 61439) for low-voltage switchgear and controlgear assemblies. UK participation was entrusted to Subcommittee PEL/17/3 (Low voltage switchgear and controlgear assemblies) under Technical Committee PEL/17 (Switchgear, controlgear and HV-LV coordination). The series defines the construction, performance, testing and safety requirements for LV assemblies and is the core reference for the design, manufacture and certification of LV distribution cabinets, control panels, power distribution boxes and distribution boards.

💡 An “assembly” is a combination of circuit breakers, disconnectors, contactors, protection relays and other components arranged in a cabinet (or box) to a defined scheme. LV assemblies supply end users directly, so their internal separation, temperature rise and short-circuit withstand are directly related to the safety of people and equipment.
⚠️ Scan-version note: Part 4, Part 5 and Part 6 of this six-part series were available only as scanned documents (SCAN) in the source material. Their technical content in this article is summarized from public domain knowledge; the official BSI publication takes precedence.

1. Series Overview and Scope 📌

The series applies to low-voltage switchgear and controlgear assemblies with rated voltage not exceeding 1000 V a.c. (or 1500 V d.c.). Part 1 specifies general rules; Part 2 addresses power switchgear and controlgear assemblies (PSC); Part 3 addresses distribution boards intended to be operated by ordinary persons (DBO); Parts 4/5 address assemblies for public networks; Part 6 addresses busbar trunking systems (busways).

The standard is built around “construction design — performance verification — type testing”, requiring assemblies to meet temperature-rise, dielectric, short-circuit protection and mechanical-operation requirements in defined environmental and operating conditions, while ensuring the safety of operators and maintenance personnel.

2. Structure of the Series 📋

StandardTitleContent SummaryStatus
BS EN 61439-1:2011General rulesGeneral rules: definitions, construction, performance, tests and safety requirementsPublished 2011; identical to IEC 61439-1:2011
BS EN 61439-2:2011Power switchgear and controlgear assembliesSupplementary requirements for PSC assembliesPublished 2011; includes UK National Annex NA
BS EN 61439-3:2012 (2015)Distribution boards intended to be operated by ordinary personsDistribution boards for operation by ordinary persons (DBO)Published 2012 (confirmed 2015)
BS EN 61439-4:2013Particular requirements for assemblies for public networksParticular requirements for assemblies for public networksScan version
BS EN 61439-5:2015Assemblies for power distribution in public networksAssemblies for power distribution in public networks (PSCA)Scan version
BS EN 61439-6:2012Busbar trunking systems (busways)Busbar trunking systems (busways)Scan version

3. Key Technical Requirements 🔧

3.1 General rules (Part 1)

Part 1 specifies ratings (rated voltage, current, short-circuit withstand, frequency), construction forms (fixed/withdrawable), internal separation forms (separating busbars, functional units, terminals, etc.), temperature-rise limits, dielectric performance and short-circuit protection coordination, together with type and routine test items. It also sets enclosure protection (IP) and mechanical impact resistance (IK) requirements.

3.2 Power assemblies and distribution boards (Parts 2 and 3)

Part 2 gives more specific performance and test requirements for PSC (power switchgear and controlgear) assemblies; Part 3 specifies misuse-prevention, indication and protection requirements for DBO (distribution boards operated by ordinary persons) so that lay users can operate them safely.

3.3 Public-network assemblies and busbar trunking (Parts 4, 5, 6)

Parts 4/5 specify the construction, insulation and test requirements of assemblies connected to public networks (PSCA); Part 6 specifies temperature-rise, short-circuit, fire and installation requirements of busbar trunking systems. As the main large-current distribution trunk, busbar trunking demands special attention to the reliability of its conductor joints and insulating supports.

🚨 Type testing of assemblies (temperature rise, short-circuit withstand, dielectric) is the key to guaranteeing performance and safety. An unverified assembly may suffer arc faults, cabinet deformation or even personal injury under short circuit or overload. At procurement, require type-test reports and temperature-rise data to BS EN 61439.

4. Engineering Practice and Applications 🔩

  • 🔍 Design and selection: Select assemblies by rated current, short-circuit withstand and outgoing-circuit count, and verify the internal separation form and IP protection grade.
  • 🔧 Installation and wiring: Install busbars, cables and components per the manufacturer’s drawings and specifications, ensuring connection torque and phase sequence and watching temperature rise and ventilation inside the cabinet.
  • 📊 Type and routine testing: Verify temperature-rise, short-circuit withstand and dielectric test reports; before dispatch, check circuit continuity, insulation resistance and mechanical operation.
  • 📋 Operation and maintenance: Periodically check loose busbar connections, overheated components and insulation ageing, and clean accumulated dust to prevent local overheating and arc risk.

5. Frequently Asked Questions ❓

❓ Q: How do BS EN 61439 and IEC 60439 relate?
A: IEC 61439 is the successor to IEC 60439, reorganizing and strengthening the general rules and part requirements for LV assemblies. BS EN 61439 adopts the EN text identical to the IEC content and supersedes the old BS EN 60439 series.
❓ Q: What does the internal separation form (Form) mean?
A: Form indicates the degree of separation between the different functional units inside an assembly (busbars, functional units, outgoing terminals, etc.), e.g. Forms 1–4. Higher forms give better arc protection and maintenance safety but cost more space and money.
❓ Q: What is the difference between PSC and DBO?
A: PSC (power switchgear and controlgear assemblies) are used for industrial power distribution and control operated by trained personnel; DBO (distribution boards operated by ordinary persons) are used in residential and commercial premises by lay users and need additional misuse-prevention and protection requirements.
🔍 Q: Why is the content of Parts 4, 5 and 6 flagged as scan versions?
A: These three documents were available only as scanned copies in the source material, so this article summarizes them from public domain knowledge. Specific ratings, test conditions and acceptance values should be taken from the official text published by BSI.
🔒