BS EN 60999 — Connecting Devices — Electrical Copper Conductors — Safety Requirements for Screw-Type and Screwless-Type Clamping Units Standard Series

Safety Requirements for Screw-Type and Screwless-Type Clamping Units (EN/IEC 60999 Series)

🔩 BS EN 60999 is the British Standard adopting, identically, the IEC 60999 European standard series for safety requirements for screw-type and screwless-type clamping units for electrical copper conductors. Developed under IEC/TC 23 (Electrical accessories) subcommittees, approved by CENELEC as EN 60999, and adopted in the UK by PEL/23 (PEL/23/2 connecting devices) and PEL/17/2 (low-voltage switchgear and controlgear), it defines the safety requirements for clamping units (terminals). Clamping units are key components carrying current and ensuring contact reliability in electrical connections; their safety requirements directly affect the long-term reliable operation of electrical installations.

💡 Screw and screwless terminals are among the most widely used connection methods in low-voltage installations. A clamping unit must provide adequate clamping force (low contact resistance) without damaging the conductor, while supporting the corresponding current-carrying capacity.

1. Scope and General Framework 📌

The BS EN 60999 series applies to screw-type and screwless-type clamping units for connecting electrical copper conductors in connecting devices. The series is divided into two parts by conductor cross-section:

  • Part 1: Conductors from 0.2 mm² up to 35 mm² (included): general requirements and particular requirements for this range.
  • Part 2: Conductors above 35 mm² up to 300 mm² (included): particular requirements for large cross-section conductors.

The documents are BS EN 60999-1:2000 (corresponding to IEC 60999-1:1999, superseding BS EN 60999:1993) and BS EN 60999-2:2003 (corresponding to IEC 60999-2:2003). ICS classification is 29.120.20 / 29.130.20.

⚠️ The boundary between the two parts is a conductor cross-section of 35 mm²: small and medium cross-section terminals use Part 1; large cross-section (>35 mm² to 300 mm²) terminals use Part 2. Selecting the wrong standard leads to mismatched test items and requirements.

2. Series Composition and Technical Points 🔧

StandardTitleConductor RangeIEC EquivalentStatus
BS EN 60999-1:2000General requirements and particular requirements for 0.2–35 mm²0.2 mm² to 35 mm²IEC 60999-1:1999Current (supersedes 1993)
BS EN 60999-2:2003Particular requirements for conductors above 35 mm² up to 300 mm²>35 mm² to 300 mm²IEC 60999-2:2003Current

1. General Requirements and Small/Medium Cross-Section (Part 1)

The framework of Part 1 (based on the digest contents listing) includes:

  • Scope: screw-type and screwless-type clamping units for connecting electrical copper conductors.
  • Terms and definitions: clamping unit, screw-type/screwless terminal, applicable conductors, etc.
  • General requirements and general notes on tests: test environment, samples, and conformity assessment.
  • Main characteristics: rated connection capacity, applicable conductor range (cross-section and construction), etc.
  • Connection of conductors: clamping capability, conductor insertion/withdrawal, and connection reliability.
  • Constructional requirements: terminal material, anti-loosening, and anti-misconnection requirements.

2. Large Cross-Section Conductors (Part 2)

Part 2 adds particular requirements for copper conductors above 35 mm² up to 300 mm² (included), covering clamping, tightening torque, conductivity, and test provisions for large cross-section conductors.

💡 Large cross-section terminals in Part 2 are commonly used for switchboard infeed, busbar connections, and high-power equipment wiring; clamping reliability and torque control directly affect contact resistance and heating safety.

3. Key Technical Requirements 🔬

Key safety requirements for clamping units include:

  • Clamping force and contact resistance: the clamping unit must provide sufficient clamping pressure to ensure a low, stable contact resistance and prevent overheating.
  • Current-carrying capacity and temperature rise: terminal temperature rise at rated current must not exceed limits.
  • Mechanical strength and endurance: the terminal must withstand the specified tightening torque (screw-type) and insertion/withdrawal cycles (screwless-type).
  • Conductor adaptability: reliable clamping of solid/stranded/fine-stranded copper conductors in the specified range without damage.
  • Anti-loosening and safety: anti-loosening construction, creepage and clearance, and prevention of inserting wrong cross-section conductors.
🚨 One of the common causes of electrical fires is loose terminals: poor contact causes local overheating, which over time ignites insulation and surrounding combustibles. Tighten to the specified torque and periodically check temperature.

4. Engineering Practice and Application 🛠️

  • 🔍 Selection: select terminals in the applicable standard range (Part 1/Part 2) by conductor cross-section and rated current, and confirm applicable conductor types.
  • 🔧 Installation: strip to the correct length, insert the conductor correctly, and tighten to the specified torque; for screwless terminals, insert fully per operating instructions.
  • 📊 Inspection: check that the terminal clamps the conductor body (not the insulation), with no burrs or loose connections.
  • 📋 Maintenance: periodically re-check temperature and torque on critical circuit terminals, and act on heating promptly.

5. Frequently Asked Questions ❓

❓ Q: How are Part 1 and Part 2 selected?
A: By conductor cross-section: 0.2 mm² to 35 mm² (included) uses Part 1; above 35 mm² to 300 mm² (included) uses Part 2. Choose the standard corresponding to the terminal’s rated connection capacity.
🔩 Q: What is the difference between screw-type and screwless terminals?
A: Screw-type terminals clamp the conductor via a screw/screw, requiring tools and a specified torque; screwless terminals self-lock via a spring or similar structure, quick to operate, but require full insertion and matching cross-section.
🔌 Q: Why can loose terminals cause fire?
A: Looseness increases contact resistance; current flow causes intensified local heating, and excessive temperature rise ignites insulation material which may spread into a fire. Thus tightening torque and periodic checks are vital.
📊 Q: How is clamping quality ensured?
A: Follow process requirements for strip length, insertion depth, and tightening torque; use certified terminals meeting BS EN 60999; perform pull/temperature-rise verification and visual inspection after installation.
🔒