๐ BS EN 60702 is the British Standards Institution (BSI) implementation of the European Standard EN 60702 (derived from IEC 60702) covering mineral insulated (MI) cables and their terminations. MI cables consist of a copper conductor, an inorganic mineral (magnesium oxide) insulation and a copper sheath, offering excellent high-temperature, fire-resistant, mechanical and smoke-free properties. They are widely used in fire alarm systems, fire-fighting installations, high-temperature furnaces, mines and chemical plants where fire resistance and reliability are critical. This series unifies requirements for MI cables and terminations up to 750 V and the guidance for use, and is an important standard in the UK/European fire-resistant cable family. The UK participation is entrusted to Subcommittee GEL/20/17 (Electric cables โ low voltage) under Technical Committee GEL/20 (Electric cables); ICS is 29.060.20.
๐ก The “mineral insulation” of MI cable is the core of its fire resistance: magnesium oxide insulation and the copper sheath do not burn, drip or emit harmful gases at high temperature, and even if the sheath is locally damaged they retain a degree of insulation, making them especially suitable for fire-protection and high-temperature applications.
1. Series Overview and Scope ๐
The British Standards in this batch cover three parts:
| Standard | Part Content | Corresponding IEC |
| BS EN 60702-1:2002+A1:2015 | Part 1: Cables | IEC 60702-1:2002 (with amendment 1:2015) |
| BS EN 60702-2:2002+A1:2015 | Part 2: Terminations | IEC 60702-2:2002 (with amendment 1:2015) |
| BS EN 60702-3:2016 | Part 3: Guidance for use | IEC 60702-3:2016 |
Parts 1 and 2 supersede their earlier editions (Part 1 supersedes BS EN 60702-1:2002, Part 2 supersedes BS EN 60702-2:2002, both withdrawn in February 2018); Part 3 supersedes BS 6207-3:2001 (withdrawn in May 2019). Amendment A1:2015 updated Annex ZA.
โ ๏ธ MI cables are hard and have a large bend radius, and termination requires special tools and techniques. Improper installation (e.g., excessive bending, poor termination sealing) damages the insulation, causing a drop in insulation resistance and even short-circuit.
2. Cable Requirements (Part 1) ๐
BS EN 60702-1 specifies requirements for mineral insulated cables:
- Construction: copper conductor, magnesium oxide (MgO) insulation, copper sheath (optionally with an outer sheath);
- Ratings: rated voltage (โค750 V), conductor size, current-carrying capacity, insulation resistance;
- Performance: insulation resistance, voltage withstand, sheath sealing, bending and mechanical strength;
- Tests: insulation resistance measurement, voltage withstand, sheath integrity, dimensions and marking.
MgO insulation is highly hygroscopic, so cable ends are normally pre-sealed to prevent moisture ingress; moisture-proof sealing must be applied at the termination during installation. The standard specifies conductor material, MgO purity and sheath thickness.
๐จ Insulation resistance of MgO drops sharply when it absorbs moisture. During storage, transport and installation, keep the cable ends sealed; after cutting, immediately perform termination sealing and verify insulation resistance.
3. Termination Requirements (Part 2) ๐ฉ
BS EN 60702-2 specifies requirements for MI cable terminations:
- Termination structure: sealing, insulator, conductor exit and connecting terminal;
- Moisture-proof sealing: the termination must effectively prevent moisture ingress to keep insulation resistance stable;
- Electrical performance: contact resistance, voltage withstand, insulation resistance and temperature rise;
- Test methods: sealing, electrical performance and environmental endurance tests.
The termination is the critical weak point of an MI cable system; its sealing quality directly determines the long-term insulation performance. The standard specifies termination material, construction, dimensions and tests.
4. Guidance for Use (Part 3) ๐
BS EN 60702-3 provides guidance for use of MI cables and their terminations:
- Laying: allowable bend radius, laying method, fixing spacing and supports;
- Termination work: cutting, sheath removal, sealing, connection and insulation testing;
- Environment: selection and protection for temperature, humidity and corrosive environments;
- Maintenance: insulation-resistance monitoring, inspection and replacement principles.
The guidance helps installation and maintenance personnel operate correctly, avoiding premature failure from poor workmanship.
๐ก MI cables suit surface and buried laying; use a dedicated bending tool and control the bend radius when bending; add an appropriate outer sheath or protection in corrosive environments.
5. Engineering Application and Practice ๐ ๏ธ
- ๐ Selection: choose conductor size, sheath type and whether an outer sheath is needed by load current, voltage and installation environment.
- ๐ง Installation: use dedicated tools for cutting and termination; keep the end sealed; control bend radius; fix correctly.
- ๐ Insulation testing: measure conductor-to-sheath insulation resistance with a megohmmeter before and after installation to confirm dryness and sealing.
- ๐ Maintenance: periodically monitor insulation resistance and termination condition; investigate sealing and moisture causes when resistance drops.
When installing MI cables, the copper sheath provides both electrical protection and mechanical strength, but it is important to maintain the integrity of the sheath and the sealing at the terminations. The cable should be bent with a suitable bending tool and the minimum bending radius should not be less than that recommended by the manufacturer to avoid kinking and damage to the insulation. Where the cable passes through walls or floors, a protective sleeve may be required. The termination must be fitted with a moisture-proof seal, and the insulation resistance should be checked after installation to confirm that no moisture has entered. In corrosive or wet environments, an appropriate outer sheath or a protective coating should be applied, and the cable should be supported at suitable intervals to prevent sagging and mechanical stress.
6. Frequently Asked Questions โ
โ Q: What are the characteristics of mineral insulated cable?
A: With magnesium oxide as inorganic insulation and a copper sheath, it offers high-temperature resistance, fire resistance, high mechanical strength and is smoke-free and non-toxic โ suited to fire-protection and high-temperature applications.
โ Q: Why must MI cable ends be sealed?
A: MgO insulation is highly hygroscopic; when it absorbs moisture the insulation resistance falls. Sealing prevents moisture ingress and ensures long-term insulation performance.
โ Q: What is the relationship between the three parts of BS EN 60702?
A: Part 1 specifies cables; Part 2 specifies terminations; Part 3 provides guidance for use. They are used together.
๐ Q: What should be noted when installing MI cable?
A: Use dedicated tools for cutting and termination, control bend radius, keep ends sealed, and measure insulation resistance before and after installation.
โ Q: Where is MI cable suitable?
A: Fire alarm systems, fire-fighting installations, high-temperature furnaces, mines, chemical plants and other applications requiring fire resistance and reliability; also for surface and buried laying.