⚡ BS EN 60383 is the British Standards Institution series that adopts European Standard EN 60383, which is itself identical to the International Electrotechnical Commission (IEC) 60383 series, covering insulators for overhead lines with a nominal voltage above 1 kV. The series separates requirements and testing at two structural levels: individual insulator units on one hand, and insulator strings and insulator sets on the other. It establishes definitions, test methods and acceptance criteria for ceramic and glass insulators used in a.c. systems, and serves as a key reference for insulation coordination, line insulation design, insulator procurement, and operation and maintenance of power transmission networks.
The BS EN 60383 series is the UK implementation of the IEC 60383 (formerly IEC 383) family, prepared under the direction of the Electrotechnical Sector Board with technical work led by Subcommittee PEL/36/2, Line insulators, of Technical Committee PEL/36, Insulators for power systems. The series supersedes earlier national documents such as the BS 137 series, aligning UK requirements with international and European practice.
The series applies to insulators for overhead lines with a nominal voltage above 1 kV in a.c. systems. It covers two product levels: single insulator units (ceramic or glass) and insulator strings and insulator sets, where the unit is the basic building block and the string or set is the complete insulating structure assembled from units.
| Standard Number | Title | IEC Reference | Main Content |
|---|---|---|---|
| BS EN 60383-1:1998 (incl. A11:1999) | Insulators for overhead lines with a nominal voltage above 1 kV — Part 1: Ceramic or glass insulator units for a.c. systems — Definitions, test methods and acceptance criteria | IEC 60383-1:1993 | Definitions, test methods and acceptance criteria for single ceramic/glass insulator units, including mechanical, electrical and thermal tests |
| BS EN 60383-2:1995 | Insulators for overhead lines with a nominal voltage above 1 kV — Part 2: Insulator strings and insulator sets for a.c. systems — Definitions, test methods and acceptance criteria | IEC 60383-2:1993 | Definitions, electrical characteristics and test procedures for insulator strings and sets |
Part 1 establishes a systematic terminology for ceramic and glass insulator units, covering basic concepts such as insulator, insulator unit, string, set, and flashover, together with electrical characteristic parameters including dry lightning impulse withstand voltage, 50% dry lightning impulse flashover voltage, wet power-frequency withstand voltage, wet power-frequency flashover voltage, wet switching impulse withstand voltage, and 50% wet switching impulse flashover voltage. Part 2 extends the definitions to insulator strings and sets and specifies how their electrical characteristics are determined.
The series lays down common rules for high-voltage testing: tests shall be carried out in a standard reference atmosphere, and correction factors are provided for converting results obtained under non-standard ambient conditions (temperature, pressure, humidity). This ensures that withstand and flashover values are comparable and reproducible between laboratories.
Wet power-frequency and wet switching impulse tests are performed with artificial rain. The series specifies the properties of the artificial rain — including rainfall intensity, droplet angle, and water conductivity — so that wet-test conditions are consistent across laboratories. These tests verify the external insulation withstand capability of insulators in rainy conditions, a key criterion for judging external insulation performance.
The series defines the installation and arrangement of the test object (insulator unit, string, or set) during electrical tests, including orientation, clearance to ground, and distance from other objects, so that results are not distorted by stray capacitance or nearby objects. Correct arrangement ensures the applied test voltage truly stresses the insulator as intended.
| Test Category | Object Under Test | Key Parameters | Typical Criterion |
|---|---|---|---|
| Dry lightning impulse tests | Unit / string / set | Impulse withstand voltage, 50% flashover voltage | No flashover or puncture at the specified impulse voltage |
| Wet power-frequency tests | Unit / string / set | Power-frequency withstand and flashover voltage | Withstand requirement met under artificial rain |
| Wet switching impulse tests | String / set | Switching impulse withstand voltage, 50% flashover voltage | Withstand requirement met under artificial rain |
| Mechanical tests | Unit / string / set | Mechanical failing load, residual strength | Required mechanical safety factor satisfied |
In practical overhead line work, the BS EN 60383 series informs the following areas: