📐 BS EN 60079 is the British national implementation by BSI of the CENELEC EN 60079 series, which is identical or closely correlated with the IEC 60079 family — the global reference for the design, selection, installation and maintenance of electrical equipment and protection systems in explosive atmospheres (flammable gases, vapours, dusts and fibres). The series comprises around 30 documents covering general equipment requirements, each major type of protection (flameproof enclosure “d”, increased safety “e”, intrinsic safety “i”, pressurization “p”, encapsulation “m”, oil immersion “o”, powder filling “q”), area classification for gas and dust, installation, inspection and maintenance. It is the compliance cornerstone for the oil, chemical, pharmaceutical, mining, food-processing and coating industries.
BS EN 60079 guides the design, selection, installation and maintenance of electrical equipment and protection systems for explosive atmospheres, as well as hazardous-area assessment. It is organized into parts: part 0 states general equipment requirements; part 1 covers flameproof enclosures “d”; part 7 increased safety “e”; part 11 intrinsic safety “i”; part 18 encapsulation “m”; while parts 10-1 (gas) and 10-2 (dust) address area classification. The series closely follows IEC 60079, marking CENELEC common modifications adopted in the UK where they occur.
The table below lists representative parts of the series and their technical subjects:
| Standard | Subject | Key technical content |
|---|---|---|
| BS EN 60079-0 | Equipment — General requirements | Common requirements: terminology, temperature classes, Equipment Protection Levels (EPL), mechanical strength, joints, fasteners, earthing, marking and test procedures |
| BS EN 60079-1 | Flameproof enclosures “d” | Enclosure withstands internal explosions without propagating; flange gaps, joint widths, shaft clearances and type tests |
| BS EN 60079-2 | Pressurization “p” | Maintains positive internal pressure with protective gas to exclude the explosive mixture |
| BS EN 60079-7 | Increased safety “e” | Enhanced construction, insulation and temperature rise for apparatus with no arcing parts |
| BS EN 60079-10-1 | Area classification — Gas | Zone 0, 1, 2 classification principles and extent estimation |
| BS EN 60079-10-2 | Area classification — Dust | Zone 20, 21, 22 classification principles |
| BS EN 60079-11 | Intrinsic safety “i” | Energy limiting so circuits cannot ignite the atmosphere; ia/ib levels |
| BS EN 60079-14 | Electrical installations design/selection/erection | Design, selection and erection of electrical installations (used with part 17) |
| BS EN 60079-17 | Inspection and maintenance | Inspection, periodic verification and maintenance of Ex installations |
| BS EN 60079-18 | Encapsulation “m” | Potentially arcing parts embedded in resin to isolate them |
Part 0 establishes for all Ex equipment the temperature classes (T1–T6, maximum surface temperature from 450 °C down to 85 °C), the EPL framework (Ga/Gb/Gc for gas, Da/Db/Dc for dust) and the classification of Group II (gas) and Group III (dust) apparatus. Each protection technique then adds its own detail:
BS EN 60079-10-1 (gas) and -10-2 (dust) provide the methodology for hazardous-area classification. Gas atmospheres are divided by frequency and duration of occurrence into Zone 0 (continuous or long-lasting), Zone 1 (likely in normal operation) and Zone 2 (short-lived under abnormal conditions); dust atmospheres map to Zones 20/21/22. Classification inputs include the release-source grade (continuous, primary, secondary), ventilation/dilution capability and accumulation risk. Equipment selection then follows the required EPL: Zone 1 typically calls for flameproof “d” or intrinsic safety; Zone 2 may use increased safety “e” or non-sparking apparatus.