BS EN 50268 — Common Test Methods for Cables Under Fire Conditions: Smoke Density Measurement Standard Series

Common Test Methods for Cables Under Fire Conditions — Measurement of Smoke Density (EN 50268-1 / 50268-2)

🔥 BS EN 50268 is the CENELEC standard series on the fire-behaviour test methods for cables, specifically the measurement of the smoke density of cables burning under defined conditions. It comprises two parts: BS EN 50268-1 specifies the test apparatus, while BS EN 50268-2 specifies the test procedure. Published in the UK by BSI Technical Committee GEL/20 (Electric cables), Subcommittee GEL/20/3 (Insulation and sheath), the series superseded the earlier BS 7622 series and is a key basis for cable smoke-density evaluation and the selection of low-smoke, low-toxicity cables.

💡 In a cable fire, what threatens lives is often not the flame itself but the large volume of toxic smoke and dense fumes that destroy visibility. Low-smoke cables produce low smoke density when burning, buying precious time for evacuation. Smoke density is therefore one of the key indicators of cable fire safety.

1. Standard Series Overview 📌

When a cable bundle or cable route ignites, the sheath, insulation, and filler materials burn and generate large amounts of smoke. The density of this smoke (its ability to block light) directly affects visibility and the escape environment at the fire scene. BS EN 50268 provides a standardised apparatus and procedure to measure the smoke density produced by cables burning under defined conditions, giving a unified quantitative method for smoke-density grading, product comparison, and fire-safety assessment of cables.

The series is divided into two parts. Part 1 specifies the structure and technical requirements of the test chamber, light source, and photometric system. Part 2 specifies specimen preparation, burning conditions, measurement procedure, data processing, and result expression. The two parts are used together to form a complete smoke-density measurement method.

2. Series Composition and Technical Points 📋

StandardTitleMain Content
BS EN 50268-1:2000Common test methods for cables under fire conditions — Measurement of smoke density of cables burning under defined conditions — Part 1: ApparatusStructure and technical requirements of the test chamber, light source, photodetection, and recording system
BS EN 50268-2:2000Common test methods for cables under fire conditions — Measurement of smoke density of cables burning under defined conditions — Part 2: ProcedureSpecimen preparation, burning conditions, measurement procedure, data processing, and result expression
⚠️ Smoke-density results are highly dependent on burning conditions: the number and arrangement of specimens, the ignition method, and ventilation all significantly affect the measured values. The test must be performed strictly under the conditions of Part 2 for results to be comparable.

3. Key Technical Requirements 🔧

3.1 Test apparatus (Part 1)

  • Test chamber: an enclosed test volume whose inner walls do not absorb smoke, with volume and structural dimensions meeting the standard.
  • Light source and photometric system: a standard light source at one end of the chamber and a photodetector at the other, measuring the transmittance of light through the smoke.
  • Burning apparatus: provides the specified ignition and burning conditions, such as a flame burner with its gas supply and flow control.
  • Recording system: records the transmittance variation with time in real time for calculating smoke-density parameters.

3.2 Test procedure (Part 2)

Prepare the specimen as specified (number, length, and arrangement of cable segments), place it in the chamber, ignite it, and continuously measure the transmittance change over the specified time, from which the smoke density is calculated. The standard sets explicit requirements for test environment, burning time, data sampling, and repeatability so that results from different laboratories are comparable.

3.3 Expression of smoke density

Smoke density is usually expressed as optical density or its time-integrated form. The higher the optical density, the denser the smoke and the poorer the light transmission. The goal for low-smoke cables is a low optical density produced under the specified test conditions, i.e., low smoke density.

4. Engineering Practice 🛠️

  • 🔍 Cable selection: in tunnels, metros, high-rise buildings, and crowded places sensitive to smoke hazards, give priority to cables verified as low-smoke by this standard series.
  • 🔧 Product certification: cable manufacturers complete the smoke-density test to this standard and issue a test report as the basis for low-smoke performance claims and third-party certification.
  • 📊 Fire design: incorporate cable smoke-density data into fire-smoke analysis to evaluate the impact of smoke spread and visibility loss on evacuation in fire scenarios.
  • 📋 Procurement and acceptance: check the cable smoke-density test report during procurement to confirm the product meets the required smoke-density class.

5. Frequently Asked Questions ❓

❓ Q: Why is smoke more dangerous than the flame itself in a cable fire?
A: Cable sheaths and insulation generate large volumes of toxic smoke (e.g., carbon monoxide, hydrogen halides) and dense fumes that cause asphyxiation and poisoning, and rapidly reduce visibility, hindering evacuation and firefighting — the main cause of casualties in cable fires.
❓ Q: Are smoke density and flame retardancy the same thing?
A: No. Flame retardancy reflects the cable’s resistance to flame spread (whether it self-extinguishes easily), while smoke density reflects how much and how dense the smoke produced is when the cable burns. A cable can be flame-retardant yet produce dense smoke — the two are independent performance dimensions.
❓ Q: What is the application advantage of low-smoke cables?
A: Low-smoke cables produce little, low-density smoke in a fire, prolonging visibility time and aiding evacuation and rescue. They are widely used in tunnels, metros, high-rise buildings, and crowded places.
❓ Q: How is comparability of smoke-density results across laboratories ensured?
A: Strictly follow the apparatus requirements of Part 1 and the procedure of Part 2, control the consistency of specimen number and arrangement, burning conditions, sampling, and data processing, and verify repeatability and reproducibility as required by the standard.
🔒