🚃 BS EN 50123 is the UK adoption of the European EN 50123 series (Railway applications — Fixed installations — D.C. switchgear), prepared by CENELEC TC 9X (Electrical and electronic applications for railways) and SC 9XC (Electric supply and earthing systems for public transport equipment — fixed installations), with BSI Technical Committee GEL/9 (Railway electrotechnical applications) and GEL/9/3 (Fixed equipment) responsible in the UK. D.C. switchgear in traction power supply systems (metro, light rail, commuter rail and D.C. sections of electrified railways) carries the core functions of power distribution, short-circuit interruption and safe isolation for maintenance. The series is technically aligned with the IEC 61992 series and is the authoritative basis for the design, testing, selection and acceptance of D.C. switchgear. This article is written from the readable parts and summarises the scanned parts on the basis of public domain knowledge.
The BS EN 50123 series applies to D.C. switchgear and assemblies in fixed railway installations with a working voltage up to about 3 kV D.C., covering: D.C. circuit breakers, disconnectors, switch-disconnectors, earthing switches, switchgear assemblies, and measuring, control and protection devices. D.C. traction supply is characterised by high short-circuit currents and very fast current rise rates (high di/dt), imposing special requirements on breaking capability and selective protection.
The series is technically aligned with IEC 61992 under the CENELEC/CEN procedures; national implementation of the series in Europe is the European recognised text of IEC 61992. When designing, tendering and accepting, the ratings (rated voltage, rated current, rated short-circuit breaking current, time constant, etc.) and test requirements of D.C. switchgear follow this series.
Eight documents of the series are covered in this batch. The table lists the parts, editions and themes. Parts 1, 2 and 3 are readable; Parts 4, 6, 7-1, 7-2 and 7-3 are scans.
| Part | Edition | Theme | Status |
|---|---|---|---|
| BS EN 50123-1 | 2003 | General (common requirements and definitions) | Readable |
| BS EN 50123-2 | 2003 | D.C. circuit breakers | Readable |
| BS EN 50123-3 | 2003+A1:2013 | Indoor d.c. disconnectors, switch-disconnectors and earthing switches | Readable |
| BS EN 50123-4 | 2003+A1:2013 | Outdoor d.c. disconnectors, switch-disconnectors and earthing switches (scan) | Scan |
| BS EN 50123-6 | 2003+A1:2014 | D.C. switchgear assemblies (scan) | Scan |
| BS EN 50123-7-1 | 2003 | Measuring, control and protection devices — application guide (scan) | Scan |
| BS EN 50123-7-2 | 2003 | Isolating voltage transformers and other voltage monitoring devices (scan) | Scan |
| BS EN 50123-7-3 | 2003 | Requirements for other measuring/protection devices (scan) | Scan |
Part 1 specifies the scope, normative references, terms and common test conditions of the series, establishing the rating system of D.C. switchgear (rated voltage, rated current, rated frequency/time constant, rated short-circuit breaking current, etc.) and the type-test framework — the master entrance to all subsequent parts.
Part 2 specifies the requirements and tests of D.C. circuit breakers — the core part of the series. Key points include: rated short-circuit breaking current and the short-circuit time constant (reflecting supply-circuit inductance), breaking capability verification (including near faults and high di/dt conditions), the limit number of closing/opening operations, mechanical and electrical life, and protection/control circuit requirements (shunt trip, undervoltage, overcurrent). The D.C. breaker must identify and force-interrupt the D.C. current during its rise; its design verification is performed in specified test circuits (with optional TRV parameters).
Part 3 (indoor) and Part 4 (outdoor) specify requirements for D.C. disconnectors, switch-disconnectors and earthing switches. Disconnectors provide electrical isolation for maintenance (they do not interrupt load current, or only open no-load current); earthing switches earth the circuit reliably during faults and maintenance to protect personnel. The standards cover contact wear, operating mechanisms, interlocking (e.g. mechanical/electrical interlocks with breakers and earthing) and mechanical operating life tests.
Part 6 specifies requirements for D.C. switchgear assemblies (enclosures, busbars, installation, internal-arc tests); the Part 7 series covers measuring, control and protection devices in traction D.C. systems: 7-1 provides an application guide (protection configuration and setting coordination), 7-2 covers isolating voltage transformers and other voltage monitoring devices, and 7-3 covers other related devices. Sound protection coordination (combinations of overcurrent, di/dt and du/dt criteria) is the basis of selective protection for D.C. feeders.