Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
ANSI Z21.80-19 / CSA 6.22-19 is the harmonized North American standard for line pressure regulators intended for use with natural gas, manufactured gas, and liquefied petroleum (LP) gases in the vapor phase. The standard covers regulators that reduce high inlet pressure to a lower, more stable outlet pressure for delivery to downstream equipment such as appliances, burners, or distribution piping. Typical applications include residential, commercial, and industrial gas supply systems where precise pressure control is essential for safe and efficient operation.
This standard applies to regulators with inlet pressures up to 125 psi (860 kPa) and outlet pressure ranges up to 5 psi (34.5 kPa). It does not cover service regulators used at utility meter outlets or appliance regulators that are integral to combustion equipment. The 2019 edition incorporates updated test procedures, materials requirements, and overpressure protection provisions aligned with current industry practices and safety codes such as NFPA 54 and CSA B149.1.
Regulators must be constructed from materials compatible with the intended gas composition and operating environment. All wetted components must resist corrosion and permeation, particularly when exposed to natural gas or propane. The standard mandates robust housing designs capable of withstanding a hydrostatic test at 1.5 times the rated inlet pressure without leakage or permanent deformation. Internal relief devices must be designed to vent excess pressure safely without causing flame propagation or igniting gas.
Diaphragm materials are required to have a minimum thickness of 0.020 in (0.51 mm) for metallic diaphragms, and elastomeric diaphragms must be tested for gas permeation at elevated temperatures. Valve seats must resist swelling and sticking due to gas absorption. All external adjustments, such as set point springs, must be protected from tampering or unintentional adjustment, typically by a sealed cap or lockable design.
| Regulator Class | Max Inlet Pressure (psi) | Outlet Pressure Range (in. wc) | Minimum Lockup Pressure | Maximum Capacity (ft³/h) |
|---|---|---|---|---|
| Class I | 2 | 3.5 – 5.0 | 6.2 in. wc | 2,000 |
| Class II | 5 | 5.0 – 14.0 | 15.5 in. wc | 5,000 |
| Class III | 10 | 14.0 – 28.0 | 30.0 in. wc | 10,000 |
| Class IV | 125 | 28.0 – 60.0 in. wc | 62.0 in. wc | 25,000 |
Table 1: Performance classification and capacity limits per ANSI Z21.80-19 / CSA 6.22-19.
Regulator capacity is determined under defined test conditions with air or natural gas at 60 °F and 0.6 specific gravity. The standard requires that the regulator must maintain outlet pressure within ±10% of the set point over the entire flow range from 10% to 100% of rated capacity. Lockup pressure – the maximum outlet pressure at zero flow – must not exceed 150% of the set point for most classes. Overpressure protection is mandatory: either an internal relief device, a separate pressure limiting device, or design certification that the downstream equipment can withstand full inlet pressure without failure.
Every regulator covered by ANSI Z21.80-19 must include overpressure protection (OPP) unless the system design already provides equivalent safety. The standard defines three acceptable OPP methods: (1) a self-contained relief valve that opens at a predetermined outlet pressure, (2) a downstream pressure limiting device, or (3) a failure mode that ensures the regulator closes upon sensing excess pressure. The relief capacity must be at least equal to the regulator’s capacity at the maximum inlet pressure.
Proper selection of a line pressure regulator requires careful matching of capacity, pressure range, and gas composition to the application. Installers should verify that the regulator class corresponds to the maximum possible inlet pressure expected under both normal and emergency conditions. The standard provides detailed formulas for calculating flow rates through various pipe sizes and configurations, which should be used to avoid undersizing – a common cause of erratic outlet pressure and premature wear.
Field adjustment of the set point is allowed only if the regulator is designed for external adjustment and the adjustment mechanism is sealed after verification during commissioning. The standard recommends annual inspection of relief vents and sensing lines to prevent blockages from insects, corrosion, or ice. For LP gas installations, the regulator must be installed in the vapor space of the tank and the vent line must terminate in a safe area away from potential ignition sources.
Compliance with ANSI Z21.80-19 / CSA 6.22-19 is typically certified by third-party agencies such as CSA Group, UL, or Intertek. Testing covers design review, material analysis, hydrostatic strength, diaphragm and seat leakage, capacity verification, lockup pressure, and relief valve operation. Production models must pass a consistent quality assurance program that includes batch sampling of relief settings and a minimum of one regulator per 500 units tested for capacity under maximum inlet pressure.
Marking requirements are stringent: each regulator must bear a permanent label showing the manufacturer’s name, model number, date of manufacture, inlet/outlet pressure ratings, gas type compatibility, and the certification mark of the approval agency. The standard also requires that installation instructions and overpressure protection documentation accompany each unit shipped.
For existing installations, regulators originally certified to earlier editions (e.g., Z21.80-15) may continue in service if they meet local code requirements and remain in good working condition. New installations, however, must use regulators listed to the current 2019 edition to meet the latest safety criteria.