Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
ANSI Z21.40.2a-1997 (R2017) – Gas-Fired Absorption Summer Air Conditioning Appliances – establishes minimum safety and performance requirements for factory‑built, gas‑fired absorption cooling equipment. Developed jointly with the Canadian Gas Association (CGA, now part of CSA Group), this binational standard applies to appliances used in residential, commercial, and industrial space‑conditioning applications that utilize an absorption cycle to produce chilled water or conditioned air. The addendum ‘a’ included editorial clarifications and updated references to companion standards such as ANSI Z21.40.1 (for winter heating) and ANSI Z21.40.3 (for heat pump packages).
Published in 1997 and reaffirmed in 2017 without substantive changes, the addendum refined the scope to explicitly exclude appliances that incorporate vapor‑compression cycles for supplementary cooling. It also aligned test pressure categories with the latest editions of NFPA 54/ANSI Z223.1 (National Fuel Gas Code) and CAN/CSA B149.1 (Natural Gas and Propane Installation Code).
All appliances covered by ANSI Z21.40.2a must be designed to withstand maximum operating gas supply pressures of ½ psig (3.5 kPa) for natural gas and ½ psig (3.5 kPa) for propane, unless otherwise specified by the manufacturer. The standard mandates that the generator, absorber, condenser, and evaporator satisfy proof‑pressure tests at 2.0 times the maximum allowable working pressure, with no permanent deformation or leakage. Controls must include automatic gas shutoff valves that close within 10 seconds of a flame failure. Additionally, electrical ignition systems must meet the requirements of ANSI Z21.20 (automatic gas ignition systems).
The standard specifies minimum cooling capacities and coefficient of performance (COP) at rated conditions (indoor temperature 80°F / 26.7°C dry bulb, outdoor temperature 95°F / 35°C dry bulb). Table 1 summarizes the key performance requirements for two common appliance classes.
| Parameter | Class A (Residential) | Class B (Commercial) |
|---|---|---|
| Rated cooling capacity (Btu/h) | ≥ 36,000 | ≥ 120,000 |
| Minimum COP at full load | 0.50 | 0.55 |
| Maximum sound level (dBA at 3 ft) | 55 | 65 |
| Maximum gas consumption (Btu/h per ton) | 24,000 | 22,000 |
| Electrical standby power (W) | ≤ 10 | ≤ 25 |
Testing must be conducted at a gas supply pressure of 7 inches water column (1.74 kPa) for natural gas and 11 inches water column (2.74 kPa) for propane. All cooling capacity tests use a recirculating chilled‑water loop with a 12°F (6.7°C) temperature differential across the evaporator. The standard also requires a simulated wind test (up to 25 mph / 11 m/s) for outdoor units to verify stable combustion and adequate draft. Any flue gas spillage during this test constitutes a failure.
The test regimen comprises three main phases:
ANSI Z21.40.2a-1997 (R2017) is referenced by the U.S. Department of Energy (DOE) for federal energy conservation standards and is accepted by Canadian provincial authorities through the CSA B149 series. Manufacturers selling absorption cooling equipment in North America should use the current edition of the standard in conjunction with the relevant installation codes.
The standard’s reaffirmation in 2017 confirmed that no technical changes were necessary. However, with the increasing interest in natural‑gas‑fired heat pumps and triple‑effect absorption cycles, a future revision may introduce higher efficiency tiers and updated test conditions to reflect modern design practices. Users of this standard are advised to monitor the CSA Group’s annual updates for any proposals to modify ANSI Z21.40.2a.
Last updated: 2026